KNOX BOX
CODE DATA
ALARM PANEL
PS
FE
FE PS
FREESTANDING FIRE DEPARTMENT CONNECTION
PROPERTY IS LOT 4A, BLOCK 1, AMARILLO MEDICAL CENTER UNIT NO. 21. PROPERTY IS NORTH
FE
FLOOD PLAIN DATA
PS
KEYED NOTES: 56" 1.
12"
42" MIN
2 1
5.
4 5 3
6.
36" LONG REAR GRAB BAR AND 42" LONG SIDE GRAB BAR, TYPICAL. 33" TO 36" TOP OF BAR ACCESSIBLE TOILET PAPER HOLDER. RECESSED TOWEL DISPENSER / WASTE RECEPTACLE - AS DETERMINED BY GENERAL CONTRACTOR. MOUNT TOP OF DISPENSING SLOT NO HIGHER THAN 48" A.F.F. SOAP DISPENSER, IF PROVIDED, TO BE LOCATED AS SHOWN. VERIFY W/ GENERAL CONTRACTOR. MOUNT W/ TOP NO HIGHER THAN 48" A.F.F. 24" WIDE X 36" HIGH PLATE GLASS MIRROR MINIMUM. MOUNT BOTTOM OF REFLECTING SURFACE NO HIGHER THAN 40" A.F.F.(TOP OF REFLECTIVE SURFACE MUST BE AT LEAST 74" A.F.F.) FLUSH VALVE
ACCESSIBILITY NOTES: (BASED UPON 2012 INTERNATIONAL BUILDING CODE, CHAPTER 11, TEXAS ACCESSIBILITY STANDARDS, 2012, AND THE AMERICANS WITH DISABILITIES ACT) WATER CLOSET:
PROPOSED ADDITION WILL BE AT SAME FINISHED FLOOR ELEVATION - 3666.67.
PLANS
1
4
2
TOILET PAPER HOLDERS: MOUNTING HEIGHT TO BE 15" MIN, 48" MAX. TO PAPER FLOW SHALL BE CONTINUOUS WITH NON-RESTRICTED DELIVERY. DISPENSER SHALL BE 7" MIN. TO 9" MIN. IN FRONT OF WATER CLOSET, MEASURED TO CENTER OF DISPENSER. MIRROR:
ELEVATIONS
REFLECTING SURFACE SHALL BE AT LEAST 18" WIDE,WITH THE BOTTOM EDGE TO BE MOUNTED AT LEAST 30" BUT NOT MORE THAN 40" A.F.F. TOP OF MIRROR MUST BE AT LEAST 74" HIGH.
DISPENSERS: OUTLETS FOR ALL DISPENSERS SHALL BE NO MORE THAN 48" A.F.F., OPERATING MECHANISMS SHALL NOT EXCEED 48" FORWARD REACH OR 48" SIDEWAYS REACH.
11" MIN KNEE CLR @ 9"
RESTROOM DETAILS
DOOR HARDWARE: LEVERS SHALL BE INSTALLED INSTEAD OF KNOBS. SIGNAGE: PROVIDE SIGNS WITH THE INTERNATIONAL SYMBOL FOR ACCESSIBILITY AT ENTRANCE DOORS AND TOILET ROOMS. MOUNT SIGNS 60" TO CENTER LINE OF SIGN ON THE WALL ADJACENT TO THE LATCH SIDE OF THE DOOR. CONTROLS: INSURE THAT ALL CONTROLS, OPERATING MECHANISMS, AND HARDWARE ARE 48" A.F.F. MAXIMUM.
PROJECT TEAM
FUNCTIONAL NARRATIVE
COVER SHEET SURVEY SITE DEMO PLAN, DETAILS SITE PLAN, DETAILS LANDSCAPE PLAN, DETAILS IRRIGATION PLAN GENERAL NOTES FOUNDATION PLAN FRAMING PLAN FOOTING SCHEDULE AND FOUNDATION DETAILS FOUNDATION DETAILS SLAB ON GRADE AND FOUNDATION DETAILS COMPOSITE STEEL FLOOR FRAMING STEEL COLUMN AND WIND BRACE DETAILS STEEL FRAMING SECTIONS AND DETAILS STEEL FRAMING SECTION AND DETAILS SIMPLE BEAM CONNECTION DETAILS
S-12 A-1 A-2 A-3 A-4 A-5 A-6 A-7 A-8 A-9 A-10 A-11 A-12 A-13 A-14 A-15 A-16 A-17
TYPICAL STEEL DETAILS DEMOLITION PLAN / SITE DETAILS DIMENSION PLAN / PLAN DETAILS ANNOTATION PLAN LARGE SCALE PLANS CEILING PLAN ROOF PLAN EXTERIOR ELEVATIONS WALL SECTIONS WALL SECTIONS, DETAILS INTERIOR ELEVATIONS INTERIOR ELEVATIONS INTERIOR ELEVATIONS INTERIOR ELEVATIONS, DETAILS ALUMINUM FRAMES DOOR SCHEDULE, ELEVATIONS FINISH PLAN, FINISH SCHEDULE, FINISHES FIXTURES, FURNISHINGS, & EQUIPMENT PLAN
TOP OF SEAT TO BE 17" TO 19" A.F.F. SPRING LOADED SEATS NOT PERMITTED.
LAVATORY: RIM HEIGHT TO BE 34" MAX, A.F.F. BOTTOM OF FRONT EDGE TO BE 29" MIN. A.F.F. PROTECT AND INSULATE EXPOSED PLUMBING AND DRAIN PIPES.
5
PER TDSHS AMBULATORY SURGICAL CENTER LICENSING RULES, NOVEMBER 25, 2010, SECTION 135.52 (3)(B)(i) New construction. When a new ASC is constructed in a designated 100- year
15,230 SQUARE FEET / 100 = 152 OCCUPANTS.
flood plain, the building finished floor elevation shall be one foot above the set base flood plain
TOTAL OCCUPANT COUNT IS 152.
8"
requirements. WALL. MOUNTING SHALL BE HORIZONTAL, NOT LESS THAN 33" NOR MORE THAN 36" A.F.F., AND EACH BAR SHALL WITHSTAND AT LEAST 250 POUNDS OF FORCE APPLIED EITHER VERTICALLY OR HORIZONTALLY.
8" MIN KNEE CLR @ 27"
SQ. FT. = 36 OCCUPANTS. THE PROPOSED ADDITION IS MINIMALLY 17' ABOVE THE SET BASE FLOOD ELEVATION AS DESCRIBED
TOTAL OCCUPANT COUNT IS 50.
ON FEMA MAP IDENTIFIED ABOVE. TOTAL OCCUPANT COUNT FOR BUILDING IS 202.
ACCESSIBILITY STANDARDS
INDEX OF DRAWINGS G-1 C-1 C-2 C-3 L-1 L-2 S-1 S-2 S-3 S-4 S-5 S-6 S-7 S-8 S-9 S-10 S-11
2. 3.
4.
6 1
3649. EXISTING FINISHED FLOOR ELEVATION IS 3666.67.
DENOTES TWO HOUR FIRE SEPARATION BARRIER.
48" MIN
DENOTES ONE HOUR FIRE SEPARATION BARRIER. DENOTES SUITE BARRIER WALL - SMOKE PARTITION.
BUILDING OCCUPANCY EXISTING MEDICAL OFFICE:
elevation. The building shall meet all local flood code ordinances and local flood control
15"
SURGICAL SUITE, STAFF LOUNGE, SURGICAL SUPPORT 1 / 240 GROSS = 3,175 SQ. FT. = 14 OCCUPANTS. PRE-OP AND POST-OP SUITE, ADMINISTRATION, PUBLIC WAITING OUTPATIENT AREAS 1 / 100 GROSS = 3,592
CLEAR
121" MIN.
48" MAX MIN.
40" MAX
SURGERY CENTER:
17" MIN
AND ADJACENT TO FLOOD PLAIN PER FLOOD INSURANCE RATE MAP PANEL 0510, MAP NUMBER N TRUE
48375C0510C. PER MAP DESCRIBED ABOVE, BASE FLOOD ELEVATION IS INTERPOLATED TO BE BETWEEN 3647 AND
60"
12" 24"
MIN
16" TO 18"
MIN
15" 15"
MIN
34" MAX
27" MIN
9"
MIN
29" MIN
M-1 MECHANICAL DEMOLITION FLOOR PLAN M-2 MECHANICAL FLOOR PLAN M-3 MECHANICAL AIR DISTRIBUTION PLAN M-4 MECHANICAL DETAILS SCHEDULES P-1 WASTE AND VENT DEMOLITION FLOOR PLAN P-2 DOMESTIC WATER AND GAS DEMOLITION FLOOR PLAN P-3 WASTE AND VENT FLOOR PLAN P-4 DOMESTIC WATER AND GAS FLOOR PLAN P-5 PLUMBING ROOF PLAN P-6 PLUMBING DETAILS AND SCHEDULES MG-1 MEDICAL GAS FLOOR PLAN MG-2 MEDICAL GAS DETAILS AND SCHEDULES FP-1 FIRE PROTECTION FLOOR PLAN
E-1 E-2 E-3 E-4 E-5 E-6 E-7 E-8 E-9 E-10 E-11 E-12 E-13 E-14 E-15 E-16 E-17 E-18
ELECTRICAL DEMO SITE PLAN ELECTRICAL SITE PLAN LIGHTING DEMOLITION PLAN POWER DEMOLITION PLAN EQUIPMENT POWER AND DEMOLITION PLAN SPECIAL SYSTEMS DEMOLITION PLAN LIGHTING FLOOR PLAN POWER FLOOR PLAN EQUIPMENT POWER FLOOR PLAN SPECIAL SYSTEMS FLOOR PLAN FIRE ALARM FLOOR PLAN LIGHTING FIXTURE SCHEDULE AND LEGEND LIGHTING DETAILS ELECTRICAL DETAILS ELECTRICAL DETAILS PANEL SCHEDULES PANEL SCHEDULES EXTERIOR BUILDING LED TRIP LIGHTING PLAN
THE NEW SURGERY CENTER WILL BE SLAB ON GRADE WITH POST AND BEAM ROOF FRAMING EXCEPT THAT THE SOUTH PORTION WILL BE DEVELOPED OVER AN ACCESSIBLE CRAWL SPACE.
THE PROFFER SURGICAL CENTER ADDITION IS A NEW ENTITY - AN AMBULATORY SURGICAL CENTER THAT SHALL BE LICENSED THROUGH THE TEXAS DEPARTMENT OF STATE HEALTH SERVICES - PENDING.
THE SURGERY CENTER WILL HAVE TWO OPERATING ROOMS, TWO PRE-OP BAYS AND FOUR POST-OP BAYS. THIS IS DESIGNED AS A CLASS C SURGICAL FACILITY.
THIS IS ESSENTIALLY AN ADDITION TO A PHYSICIAN OFFICE BUILDING THAT WAS COMPLETED IN 2013. NEW CONSTRUCTION WORK MUST COMPLY WITH CURRENT LICENSURE REQUIREMENTS - TDSHS CHAPTER 135 - DATED NOVEMBER 25, 2010.
A NEW NURSE CALL SYSTEM WILL BE INCORPORATED. A FULLY INTEGRATED FIRE ALARM SYSTEM WILL BE INCORPORATED. THE ADDITION WILL BE FULLY FIRE SPRINKLED. ALL NEW FINISHES MEET CLASS A (NFPA 255) FLAME SPREAD RATING REQUIREMENTS.
WE ARE ALSO USING NFPA 101 - 2012 LIFE SAFETY CODE AS THIS HAS BEEN ADOPTED BY CMS AND PER PREVIOUS CONFERENCE WITH TDSHS, IT WAS ACKNOWLEDGED THAT TDSHS IS USING THIS NOW AS WELL. THE AMBULATORY SURGERY CENTER IS UNDER 10,000 SQUARE FEET GROSS, AND AS SUCH, A SEPARATE SMOKE COMPARTMENT DIVIDING THE SURGERY CENTER SPACE INTO TWO COMPARTMENTS IS NOT REQUIRED.
LABORATORY AND LAUNDRY SERVICES ARE NOT PROVIDED ON - SITE; THESE ARE CONTRACTED SERVICES. RADIOLOGY SERVICES ARE NOT PROVIDED ON SITE. THIS PROJECT IS "SELF CERTIFIED". CONSTRUCTION SHALL COMMENCE IN MARCH. DRAWINGS SHALL BE SUBMITTED TO TDSHS, TDLR, AND THE CITY OF AMARILLO FOR REVIEW.
THE SURGERY CENTER WILL BE SEPARATED FROM THE MEDICAL OFFICE BUILDING WITH TWO HOUR CONSTRUCTION TO STRUCTURE. THE EXISTING BUILDING IS FULLY FIRE SPRINKLED. THE EXISTING BUILDING IS A SLAB ON GRADE STRUCTURE WITH STEEL POST AND BEAM CONSTRUCTION.
PROJECT
PHARIS STRUCTURAL ENGINEERS 7120 I-40 WEST, SUITE 135 AMARILLO, TX 79106 806 463-7799
STRUCTURAL ENGINEER
BROWN CONSULTING ENGINEERS 3505 OLSEN BLVD. #110 AMARILLO, TX 79109 (806) 354-0141
MECHANICAL/ ELECTRICAL ENGINEERS
CTB ASSOCIATES 3003 MONTE VISTA BLVD. ALBUQUERQUE, NM 87106 (505) 268-3033
ARCHITECT
SOUTHWEST GENERAL CONTRACTORS 223 SW 4TH STREET AMARILLO, TX 79101 (806) 374-1050
CONSTRUCTION MANAGER
Stamp
Date Issued
CTB ASSOCIATES A R C H I T E C T S
P L A N N E R S
3003 MONTE VISTA BLVD. NE P. (505) 268-3033 ALBUQUERQUE, NM 87106 F. (505) 212-0354
[email protected]
Sheet No.
Sheet Name
COVER SHEET
IRRIGATION LEGEND Barbed Cross Fitting Barbed Tee or Ell as Needed
Netafim Drip Tubing 12" Dripper Spacing 0.9 gph with 6" Soil Staple to Hold in Place
PVC Supply from Electric Valve with Required Adapter - PVC to Barb Fitting
Hunter PGV with RBY Filter (sized as noted)
Netafim Dripline - Techline CV 12" Flow Spacing, .9 GPH
1-1/4" Mainline Sch. 40 - 24" min. Cover - as Needed
Lateral Line Class 200 Size as Noted - 18" min. Cover
NOTE: All pipe not labeled is to be considered as 3/4" PVC Class 200 NOTE: All Sleeves to Be Sch 40 PVC unless otherwise noted
Drip Tubing Layout NTS
PVC Sch. 40 Ell
Existing Valve to Remain
Rectangular Box with Cover Finished Grade
3 4"
PVC Sch. 40 Female Adapter PVC Class 200 Lateral Line Brick (1 of 4) Washed Gravel PVC Sch 40 Mainline Hunter PGV with Filter PVC Sch 40 Pipe
Connect to Existing Irrigation
PVC Sch 40 Tee
Hunter PGV with RBY Filter NTS
Repair Existing Irrigation As Needed
Add Valve as Necessary
2" Sch 40 Sleeve
Connect to Existing Irrigation # 1" Drip
9 GPM
Relocate Valve Out of New Parking Lot
Project
K&K
Revisions
Date Issued
1. Sheet No. 2.
3.
N TRUE
SCALE: 1/16" = 1'-0" 0
4'
8'
16'
Sheet Name
IRRIGATION PLAN
3
8'-0" 8'-0" 11
3
1
1. 2. 3. 4. 5. 6. 11'-4"
8'-10"
GENERAL NOTES
19
12
8'-0" 5'-0"
9'-0"
4
4 7/8"
10'-0"
8'-2"
8'-10"
8'-2"
8'-10"
KEYED NOTES 8'-0"
8'-0"
1.
8'-0"
8'-0" 11'-4" 8'-0"
2.
3. 4.
8'-0"
7'-2"
8'-0"
1
PACK FLUTE WITH THERMAFIBER SAFING
8'-2" 7'-2" 9'-0" 7'-2"
DENOTES 2 HOUR FIRE SEPARATION. DENOTES ONE HOUR FIRE BARRIER. DENOTES SUITE BARRIER - SMOKE WALLS TO CEILING. ALL CEILINGS ARE 8'-0" A.F.F. UNLESS NOTED OTHERWISE. FILL ALL BATHROOM WALLS WITH SOUND BATT INSULATION TO 4" ABOVE CEILING. TYPICAL SOFFIT WIDTH AT WALL CABINETS IS 2" BEYOND FACE ON CABINET OR AS SHOWN TO FACE OF PERPENDICULAR WALL.
18 8'-5 1/4"
OPEN TO SKY 10'-8 1/2" 8'-10" 10'-0"
12" 8'-0"
9'-0"
EXTEND GYP. BD. TO DECK AND SEAL WITH GYP.BD. ACOUSTICAL SEALANT
EXTEND GYP. BD. TO DECK AND SEAL WITH GYP.BD. ACOUSTICAL SEALANT
7'-2"
17
5. 6. 7. 8. 9.
7'-2" 10. 11. 12. 13. 14.
17 10
7'-2" 11
SECTION @ ROOF DECK
SECTION @ ROOF DECK
UL DES U465
UL DES U465 9'-0"
10
7'-2"
9'-0"
15. 16. 17. 18.
7'-2"
17 17
7'-2" 10
19.
8'-10"
20.
9'-0"
PAC-CLAD 12" FLUSH ALUMINUM PANELS - BLACK FINISH. MATCH EXISTING. .040 BLACK ANODIZED ALUMINUM BREAK METAL TRIM AT EXTERIOR CANOPY, BOTTOM AT 8'-51/4" A.F.F. APPROXIMATELY. FIELD VERIFY TO MATCH EXISTING CONDITION. .040 BLACK ANODIZED ALUMINUM BREAK METAL TRIM AT EXTERIOR CANOPY. BOTTOM AT 11'-014" A.F.F. EXISTING COVE AND SOFFIT TO REMAIN AS IS ADJACENT TO NEW CONSTRUCTION. NEW GYP. BD. CEILING AT PHYSICIAN OFFICE. MEDICAL GAS, POWER AND DATA OUTLETS IN CEILING. PROVIDE WITH POWER CORDS. SEE MPE DRAWINGS. 24" X 24" ACCESS DOOR. PAINT TO MATCH CEILING FINISH. VERIFY APPROPRIATE LOCATION IN FIELD FOR ACCESS ABOVE CEILING. SURGICAL LIGHT, OWNER PROVIDED, GENERAL CONTRACTOR INSTALLED. TO BE SELECTED. VENTILATION FAN REQUIRED FOR MEDICAL GAS ROOM, SEE MECHANICAL DRAWINGS FOR LOCATION. W.T.-1 - VERIFY INSIDE MOUNT TO HEAD OF WINDOW. W.T.-2 - VERIFY INSIDE MOUNT TO HEAD OF WINDOW. DECORATIVE LIGHT FIXTURE - TO BE SELECTED BY OWNER. NOT USED. FILL NORTH WALL OF OPERATING ROOM WITH SOUND BATT INSULATION TO STRUCTURE. PROVIDE SOUND BARRIER TO POST-OP BAY FOUR. FILL INTERIOR WALLS OF MECHANICAL EQUIPMENT ROOM WITH SOUND BATT INSULATION TO ROOF DECK. ROOF HATCH - MATCH EXISTING TYPE AND SIZE. CEILING TRACK FOR CUBICLE CURTAIN - CENTER ON SOFFIT. R-30 BATT INSULATION AT BOTTOM OF ROOF DECK ABOVE IN VESTIBULE - SEE WALL SECTION ALSO. FINISHED CANOPY FASCIA IS 4'-0 3 8" FROM FACE OF EXISTING GLAZING WALL TO SOUTH. MAINTAIN 4'-0" MINIMUM CLEARANCE. DECORATIVE LIGHT FIXTURE SALVAGED FROM EXISTING PHYSICIAN OFFICE - RELOCATED TO NEW - FIELD VERIFY.
7'-2" 17
9'-0" 8'-10" 7'-2"
11
1-HOUR SMOKE WALL ASSEMBLY
7'-2"
10
2" MAX 8'-10"
7'-2"
9'-0" 17 8'-0"
14
O V V
METAL DECK PERPENDICULAR TO WALL 9'-0"
7'-2"
5
6 D E E E E
8'-0"
7'-2" 8'-10"
wv
wv
2 no
2 no
N A
N A
O V V
7'-2"
D E E E E
7'-2"
7'-2"
5
8'-10"
CONTINUE GYP. BD. BEHIND STUD AT INTERSECTION
9'-0" 8'-0"
7
20
8'-0"
TIGHTLY FILL VOID AT DECK WITH THERMAFIBER SAFING MATERIAL - 4#/CF DEN. COAT SURFACES WITH ACOUSTICAL SEALANT FOR OPTIMUM SMOKE CONTROL
UL DES U465
8
UL DES U465
8'-0"
PLAN VIEW @ INTERSECTION
8'-0"
7'-2"
SECTION @ ROOF DECK
7'-2" 10'-0"
8'-10" 8'-10"
7'-2"
11
7'-2" 9'-0"
Project
7'-2"
8'-0"
7'-2"
9'-0" 15
16
7'-2"
7'-2"
9'-0" 5
8'-0"
10'-0"
15 NO CEILING
8"
TYPE "X" GYP. BD.
3-5/8" METAL STUD, 16" O.C.
THERMAFIBER SAFING INSULATION
8 7'-2"
CTB ASSOCIATES
9'-0"
A R C H I T E C T S
3-5/8" METAL STUD, ATTACH WITH ANCHORS 2'-0" O.C.
7 E E E E D
V V O
A N
A N
no 2
no 2
wv
wv
V V O
E E E E D
GYP. BD. ACOUSTICAL SEALANT
6 8'-10"
FINISH FLOOR
8'-0"
PENETRATION
1/4"
NO CEILING
P L A N N E R S
3003 MONTE VISTA BLVD. NE ALBUQUERQUE, NM 87106 P. (505) 268-3033 F. (505) 212-0354
[email protected]
7/16"
FIRE CODE COMPOUND Revisions
1
Date Issued
1.
9
UL DES U419
UL DES U465
UL NO. 605
2
Sheet No.
PLAN
SECTION @ FLOOR
2.
SECTION @ PENETRATION
NO CEILING 3.
8'-8 1/2"
N TRUE
8'-5 1/4"
NOTE: PARTITION DETAILS FOR 1-HOUR FIRE BARRIER WALLS. NOTE THAT TYPICAL PARTITION IS NON-LOADBEARING, UL DESIGN U419 - 5 8" SHEET ROCK FIRECODE CORE GYPSUM PANELS ON 3-5/8" 20 GAUGE OR 25 GAUGE STEEL STUDS AT 16" O.C.
SCALE: 1/8" = 1'-0" 0
2'
4'
Sheet Name
CEILING PLAN
8'
GENERAL NOTES 1.
COORDINATE ALL DEMOLITION WITH EXISTING GENERAL CONDITIONS, ARCHITECTURAL, STRUCTURAL, PLUMBING, FIRE PROTECTION, AND ELECTRICAL SYSTEMS.
KEYED NOTES
T
1
EXISTING SUPPLY DUCT TO REMAIN.
2
REMOVE EXISTING SUPPLY DIFFUSER AND ASSOCIATED DUCT SHOWN DASHED BACK TO MAIN. CAP MAIN AND SEAL AIR TIGHT. REPAIR INSULATION ON MAIN TRUNK TO MAINTAIN CONTINUOUS INSULATION SYSTEM.
3
REMOVE EXISTING RETURN GRILLE AND ASSOCIATED DUCT SHOWN DASHED.
4
REMOVE EXISTING THERMOSTAT AND ASSOCIATED CONTROL WIRING SHOWN DASHED BACK TO ROOFTOP UNIT. RETAIN THERMOSTAT FOR REINSTALLATION.
5
REMOVE EXISTING RETURN GRILLE SHOWN DASHED. ASSOCIATED DUCT TO REMAIN.
6
EXISTING SUPPLY DIFFUSER AND ASSOCIATED DUCT TO REMAIN.
7
EXISTING ROOF MOUNTED EXHAUST FAN AND ASSOCIATED DUCT TO REMAIN.
8
REMOVE EXISTING SUPPLY DIFFUSER SHOWN DASHED. ASSOCIATED DUCT TO REMAIN.
9
REMOVE EXISTING ROOF MOUNTED EXHAUST FAN AND ASSOCIATED DUCT SHOWN DASHED. REMOVE ASSOCIATED ROOF CURB.
T
EX RTU-3
EX EF-9
T
EX RTU-8
EX RTU-6
EX EF-8
EX EF-7
T
T
EX RTU-1 T
EX CU-1
EX FC-1
T
EX RTU-7
EX RTU-9
EX RTU-2
EX RTU-4
1
EX EF-1 2
EX RTU-5
EX EF-6
5 1 3
EX EF-2 6
T
T
T
8
2 4
EX EF-3 8 9
EX EF-5
T
7
Project
PROFFER SURGICAL CENTER ADDITION 1611 WALLACE BLVD, AMARILLO, TEXAS 79106
CTB ASSOCIATES A R C H I T E C T S
P L A N N E R S
3003 MONTE VISTA BLVD. NE ALBUQUERQUE, NM 87106 P. (505) 268-3033 F. (505) 212-0354
[email protected]
Revisions 1.
Date Issued
JANUARY 29, 2018 Sheet No.
2.
3.
N
SCALE: 1/8" = 1'-0" MECHANICAL DEMOLITION FLOOR PLAN 0
2'
4'
8'
Sheet Name
MECHANICAL DEMOLITION FLOOR PLAN
M-1
GENERAL NOTES
18
20
S
1
2
S
19
1
12x6
12x10 EF 1-18
CONTRACTOR SHALL FIELD MEASURE ALL CLEARANCES REQUIRED FOR DUCTWORK INSTALLATION PRIOR TO FABRICATION.
3.
MAINTAIN MINIMUM 25'-0" CLEARANCE BETWEEN OUTSIDE AIR INTAKES AND EXHAUST FANS, PLUMBING VENTS THRU ROOF IN PATIENT CARE AREAS. REFER TO PLUMBING ROOF PLAN ON SHEET P-5.
4.
LOW PRESSURE FLEXIBLE DUCTS TO BE MAXIMUM 3'-0" IN LENGTH. DO NOT CONNECT FLEXIBLE DUCT DIRECTLY TO DIFFUSER NECK. REFER TO DETAIL 1/M-4.
5.
ALL SUPPLY AND RETURN DUCTS SHALL BE WRAPPED WITH 2 INCH GLASS FIBER INSULATION. REFER TO SPECIFICATION SECTION 15080.
6.
ALL REFRIGERANT PIPING SHALL BE TYPE ACR HARD DRAWN COPPER.
7.
ALL THERMOSTATS AND HUMIDISTATS SHALL BE MOUNTED ON WALL AT 48 INCHES AFF.
8.
REFER TO M-3 FOR AIR DISTRIBUTION INFORMATION.
KEYED NOTES
10Ø
10Ø
6Ø
6Ø
2.
8Ø
18x12
12x6
12x6
COORDINATE ALL EQUIPMENT AND DUCTWORK WITH ARCHITECTURAL, STRUCTURAL, PLUMBING, FIRE PROTECTION, AND ELECTRICAL.
T
12x8
2
1.
1
INSTALL CONCEALED DAMPER OPERATOR IN GYP BOARD CEILING. REFER TO DETAIL 2/M-4.
2
EXTEND 12x10 EXHAUST DUCT UP THRU ROOF AND TERMINATE TO FAN USING FLEXIBLE CONNECTION. TRANSITION TO FAN AS REQUIRED. FAN OPERATION TO BE INTEGRATED INTO LIGHTING CONTROL SYSTEM BY DIVISION 16.
3
EXTEND FULL SIZE SUPPLY AND RETURN DUCTS DOWN THRU ROOF. TRANSITION TO SIZES INDICATED AND ROUTE AS SHOWN.
4
BALANCE EXISTING SUPPLY DIFFUSER TO AIRFLOW SHOWN ON M-3.
5
REINSTALL EXISTING THERMOSTAT ON NEW WALL BOX AND PULL NEW CONTROL WIRING TO EX RTU-2 AS SHOWN.
6
MOUNT HUMIDIFIER ON WALL ABOVE CEILING AND CONNECT PIPING TO INJECTION TUBE IN DUCT.
7
INSTALL STEAM INJECTION TUBE IN SUPPLY DUCTWORK. REFER TO MANUFACTURER'S INSTALLATION REQUIREMENTS.
8
EXTEND 12x8 EXHAUST DUCT UP THRU ROOF AND TERMINATE TO FAN USING FLEXIBLE CONNECTION. TRANSITION TO FAN AS REQUIRED. FAN OPERATION TO BE INTEGRATED INTO LIGHTING CONTROL SYSTEM BY DIVISION 16.
9
ROUTE 16x10 RETURN DUCT DOWN IN FURRING AND INSTALL BOTTOM OF RETURN GRILLE AT 8 INCHES AFF.
10
CONNECT NEW SUPPLY DUCT TO EXISTING AND ROUTE AS SHOWN.
11
EXTEND 12x6 EXHAUST DUCT UP THRU ROOF AND TERMINATE TO FAN USING FLEXIBLE CONNECTION. TRANSITION TO FAN AS REQUIRED. FAN OPERATION TO BE INTEGRATED INTO LIGHTING CONTROL SYSTEM BY DIVISION 16.
12
SUSPEND FAN COIL UNIT FROM STRUCTURE USING ALL-THREAD ROD AND NEOPRENE ISOLATORS. MOUNT BOTTOM OF FAN COIL UNIT EVEN WITH LIGHT FIXTURES.
13
ROUTE REFRIGERANT PIPING DOWN THRU ROOF AND TERMINATE TO FAN COIL UNIT. MAKE ROOF PENETRATION THRU CHEMCURB AND COMPLETELY FILL CURB WITH CHEMLINK COMPOUND.
14
MOUNT CONDENSING UNIT ON 24x48 ROOF PLATFORM. REFER TO DETAIL 6/M-4. SET UNIT ON NEOPRENE VIBRATION ISOLATORS AND SECURE TO PLATFORM WITH LAG SCREWS. CONNECT REFRIGERANT PIPING TO UNIT AND ROUTE AS SHOWN FOR PENETRATION THRU ROOF. INSULATE SUCTION PIPING WITH 3/4 INCH ARMAFLEX CLOSED CELL INSULATION. COVER ALL INSULATION WITH RIGID ALUMINUM JACKET AND PREFORMED FITTING COVERS. REFER TO MECHANICAL SCHEDULES FOR REFRIGERANT PIPING SIZES.
15
EXTEND 18x18 EXHAUST DUCT UP THRU ROOF AND TERMINATE TO FAN USING FLEXIBLE CONNECTION. TRANSITION TO FAN AS REQUIRED. FAN OPERATION TO BE INTEGRATED INTO LIGHTING CONTROL SYSTEM BY DIVISION 16.
16
CONNECT NEW SUPPLY DIFFUSER TO EXISTING DUCT.
17
REINSTALL EXISTING RETURN GRILLE INTO NEW GYP BOARD CEILING. PROVIDE PRICE INDUSTRIES MODEL AMF FRAME (OR EQUAL) TO ALLOW FOR LAY-IN TYPE INSTALLATION.
18
INSTALL RAYCHEM MODEL SIT-6E MOISTURE AND AMBIENT TEMPERATURE SENSOR IN CONCRETE SIDEWALK BELOW COVERED AREA.
19
INSTALL RAYCHEM MODEL CIT-1 SNOW SENSOR ON ROOF OF COVERED SIDEWALK.
20
PROVIDE RAYCHEM ELECTRIC SNOW MELT SYSTEM CABLING AND ALL ASSOCIATED CONTROLS TO SERVE SIDEWALK AREAS SHOWN SHADED.
21
INSTALL RAYCHEM MODEL SMPG1 SNOW MELT CONTROL PANEL ON WALL IN AREA SHOWN SHADED. ALL POWER AND CONTROL WIRING SHALL BE INSTALLED BY DIVISION 16.
22
PROVIDE AND INSTALL PILLA MODEL HVAC120FN1 EMERGENCY SHUT-OFF BUTTON. PROVIDE WITH ONE NORMALLY CLOSED CONTACT. LABEL SWITCH "OR 1". PULL 18 AWG, 2 CONDUCTOR WIRING FROM BUTTON TO RTU 3-18. TERMINATE WIRING TO UNIT TERMINAL STRIP TO "KILL" UNIT OPERATION WHEN BUTTON IS PRESSED.
8Ø 20x12 28x12
16x10 1
12x8
3
RTU 1-18
16x10
8Ø
12x8
T
4
EX RTU-3
EX EF-9
6Ø
24x10
16x8
10Ø
32x10
EX EF-8
4
T
EX RTU-8
6Ø HUM 1-18
3
6
EX RTU-6
12x6
6Ø
24x12 4
RTU 2-18
7
EX EF-7
24x12
5 6Ø
T
8Ø
T
T P P
EX RTU-1
24x10
22 6Ø
T
EX CU-1
23 8Ø
EX FC-1
6Ø EF 2-18
EX RTU-7
18x10
T
EX RTU-4
6Ø 8
EX RTU-9
EX RTU-2
18x8
12x8
8Ø
6Ø
T H 8Ø
10Ø
12x6 VH 1-18
12x6
25
12x6
10
6Ø
6Ø EX EF-1
M
EX RTU-5
EX EF-6
17 9
16x10
EX EF-2 14x8
32x10
6Ø 12x6
16x10
RTU 3-18
16
EX EF-5
T
12x6
8Ø
7
T
EX EF-3
24x16
8Ø
8Ø
6Ø
14x10
8Ø 8Ø
8Ø 8Ø
T
3 24x12
8Ø
18x10
8Ø
8Ø
T
8Ø
H
12x8
16x10 9
1
10Ø 18x10
3 HUM 2-18
Project
RTU 4-18 14x8
30x10
12x8
16x10
18x10 10Ø
10Ø
6Ø
HUM 3-18
30x14
6
24x12
23
T
24
EXTEND 6 INCH ROUND EXHAUST DUCT UP THRU ROOF AND TERMINATE TO FAN USING FLEXIBLE CONNECTION. TRANSITION TO FAN AS REQUIRED. ROUTE DUCT AS SHOWN DOWN IN CHASE AND STUB INTO CRAWLSPACE. TERMINATE DUCT AT 6 INCHES BELOW SLAB. FAN OPERATION TO BE INTEGRATED INTO LIGHTING CONTROL SYSTEM BY DIVISION 16.
25
TRANSITION FROM VENTILATION HOOD AS REQUIRED AND ROUTE 6 INCH ROUND DUCT DOWN IN CHASE TO CRAWLSPACE. TERMINATE DUCT AT 6 INCHES BELOW SLAB. MOTORIZED DAMPER TO BE INTERLOCKED WITH EF 5-18 VIA THE LIGHTING CONTROL SYSTEM BY DIVISION 16. DAMPER SHALL POWER OPEN WHEN FAN IS ON AND SPRING RETURN CLOSE WHEN FAN IS OFF.
12x12
16x10
10Ø
8Ø 8Ø
16x8
1
15
12x6
8Ø
16x10
12x10
8Ø 8Ø
24x12
12x6
24x12 8Ø
8Ø
3 18x10
8Ø
8Ø
7
18x10
1
RTU 5-18
9
EF 4-18 12x6
12x10
PROVIDE AND INSTALL PILLA MODEL HVAC120FN1 EMERGENCY SHUT-OFF BUTTON. PROVIDE WITH ONE NORMALLY CLOSED CONTACT. LABEL SWITCH "OR 2". PULL 18 AWG, 2 CONDUCTOR WIRING FROM BUTTON TO RTU 5-18. TERMINATE WIRING TO UNIT TERMINAL STRIP TO "KILL" UNIT OPERATION WHEN BUTTON IS PRESSED.
6Ø
EF 3-18
6Ø
9
CTB ASSOCIATES A R C H I T E C T S
P L A N N E R S
3003 MONTE VISTA BLVD. NE ALBUQUERQUE, NM 87106 P. (505) 268-3033 F. (505) 212-0354
[email protected]
Revisions
1
WALL LEGEND
1
11
1611 WALLACE BLVD, AMARILLO, TEXAS 79106
T
14x8
H
PROFFER SURGICAL CENTER ADDITION
1.
12x6
FC 1-18
CU 1-18 12
21
13
SYMBOL
EF 5-18 24
JANUARY 29, 2018 Sheet No.
8Ø 14
Date Issued
6Ø
N
MECHANICAL FLOOR PLAN
DESCRIPTION
2.
1-HR ASSEMBLY
3.
2-HR ASSEMBLY
SCALE: 1/8" = 1'-0" 0
2'
4'
8'
Sheet Name
SMOKE WALL TO CEILING
MECHANICAL FLOOR PLAN
M-2
8"Ø/S-2 200 CFM
10x10/E-1 100 CFM
10x10/T-1
10x10/E-1 125 CFM
22x10/T-2
8"Ø/S-1 200 CFM
6"Ø/S-2 75 CFM
(2) - 10"Ø/S-1 275 CFM EACH
6"Ø/S-2 50 CFM
22x10/R-1
10x10/R-3 10"Ø/S-1 225 CFM 8"Ø/S-2 250 CFM
22x22/R-2
300 CFM 10x10/E-1 125 CFM
6"Ø/S-1 50 CFM
300 CFM
6"Ø/S-1 100 CFM
6"Ø/S-2 75 CFM
300 CFM 22x22/R-2 8"Ø/S-1 200 CFM
6"Ø/S-1 100 CFM
6"Ø/S-1 100 CFM 8"Ø/S-1 200 CFM 6"Ø/S-1 100 CFM 6"Ø/S-1 100 CFM
8"Ø/S-1 125 CFM
6"Ø/S-2 75 CFM
8"Ø/S-1 150 CFM 10x10/E-1 125 CFM
6"Ø/S-2 75 CFM 10x10/E-1 125 CFM
10"Ø/S-1 300 CFM
6"Ø/S-1 100 CFM 16x16/R-4
22x10/R-3 8"Ø/S-1 150 CFM
8"Ø/S-1 150 CFM 6"Ø/S-2 75 CFM
22x22/R-2 (8) - 8"Ø/S-4 175 CFM EACH
8"Ø/S-1 150 CFM
10x10/E-1 125 CFM
6"Ø/S-2 75 CFM
(2) - 8"Ø/S-7 175 CFM EACH 10x10/E-1 125 CFM
16x16/R-4
10"Ø/S-1 275 CFM
6"Ø/S-1 100 CFM
10"Ø/S-3 250 CFM 16x16/R-4
10x10/E-1 50 CFM 8"Ø/S-1 150 CFM 6"Ø/S-2 75 CFM
Project
10"Ø/S-6 400 CFM
1611 WALLACE BLVD, AMARILLO, TEXAS 79106
16x16/E-2 500 CFM
10x10/E-1 400 CFM 10"Ø/S-3 250 CFM
CTB ASSOCIATES A R C H I T E C T S
22x10/T-2
(8) - 8"Ø/S-4 175 CFM EACH
16x16/R-4
10x10/T-1
PROFFER SURGICAL CENTER ADDITION
P L A N N E R S
3003 MONTE VISTA BLVD. NE ALBUQUERQUE, NM 87106 P. (505) 268-3033 F. (505) 212-0354
[email protected]
10x10/E-1 150 CFM Revisions
6"Ø/S-5 50 CFM
1.
10x10/E-2 150 CFM
Date Issued
JANUARY 29, 2018 Sheet No.
8"Ø/S-2 250 CFM
2.
3.
N
SCALE: 1/8" = 1'-0" MECHANICAL AIR DISTRIBUTION PLAN 0
2'
4'
8'
Sheet Name
MECHANICAL AIR DISTRIBUTION PLAN
M-3
FLEXMASTER STOD SIDE TAKE-OFF WITH DAMPER
MOLDED NYLON SLEEVETYPE END BEARINGS
DUCT 2"x4" NAILER
BUTTERFLY DAMPER
1-1/2" STAND-OFF BRACKET ASSEMBLY
SECURING BOLT COUNTERFLASHING BY ROOFING SUBCONTRACTOR
3/8" SQUARE SHAFT
MITER GEARS
MANUAL LOCKING QUADRANT W/DEGREE GRADUATIONS
EXHAUST FAN
RIGID INSULATION 2 INCH THICK GLASSFIBER ROOF INSULATION BOARD BY SUB-CONTRACTOR
CANT STRIP BY ROOFING SUBCONTRACTOR
PINS MOLDED NYLON SLEEVE-TYPE INTERMEDIATE BEARING
MOUNTING FRAME
ROOFTOP UNIT VARIES
ALLEN SCREWS FACTORY FABRICATED CURB
S.A. DUCT
COUNTER FLASHING BY ROOFING SUBCONTRACTOR
ROOF FINAL FILTER
3/8" SQUARE SHAFT
FLEXIBLE CONNECTION
BACKDRAFT DAMPER
7/8" CHANNEL IRON METAL
FLASHING
2x4 WOOD BLOCKING. ROOF
RIGID ELBOW
GAS COCK
FINAL FILTER HOUSING WITH ACCESS DOOR TO FINAL FILTER
CANT STRIP
GAS PIPE
FLEXIBLE DUCT (MAXIMUM 3')
MOUNTING FRAME
VARIES GYP BOARD CEILING CEILING
NOTE: SUPPLY GRILLES SHALL HAVE RIGID ELBOWS. FLEXIBLE DUCT CONNECTED DIRECTLY TO DIFFUSER IS PROHIBITED.
SPRING WASHER
LOCK NUT
TYPICAL CEILING MOUNTED SUPPLY DIFFUSER
EXHAUST DUCT
COVER
CEILING DIFFUSER CONNECTION DETAIL FAN SCHEDULE CFM
EXHAUST FAN MOUNTING DETAIL
2"x4" NAILER
SP
HP
RPM
TYPE
DRIVE
ELECTRICAL
MAX. SONES
SECURING BOLT
EXAMPLE: COOK
MOUNTING FRAME RIGID INSULATION
COUNTERFLASHING BY ROOFING SUBCONTRACTOR
EF 1-18
350
0.5
1/8
1549
PRV
DIRECT
115/1/60
7.8
ACED-90C15DH
EF 2-18
250
0.5
1/8
1457
PRV
DIRECT
115/1/60
6.9
ACED-90C15DH
EF 3-18
150
0.3
1/8
1092
PRV
DIRECT
115/1/60
3.5
ACRUD-90R15DH
EF 4-18
1300
0.5
1/4
849
PRV
BELT
115/1/60
7.3
ACRUB-165R3B
EF 5-18
75
0.3
1/20
1332
PRV
DIRECT
115/1/60
3.6
ACED-70C15DH
22 GA. GALV. SHEET METAL
2" THICK GLASSFIBER ROOF INSULATION BOARD BY SUB-CONTRACTOR
CANT STRIP BY ROOFING SUBCONTRACTOR
3/4" PLYWOOD DECKING
TYPICAL ROOFTOP UNIT
FLASHING CANT STRIP
VARIES FLEXIBLE CONNECTION
18 GA. "Z" CHANNEL SUPPORT 24" O.C. 16 GA. FORMED CHANNEL CURB ALL SIDES
ROOF ANGLE FRAMING
NOTES:
ROOFTOP UNIT MOUNTING DETAIL - WITH FINAL FILTER BANK 4
3
18"
MARK
RETURN DUCT
FLEXIBLE CONNECTION
CONCEALED DAMPER ACTUATOR DETAIL 2
1
FILL CURB SPACE WITH 6 INCH BATT INSULATION
GAS COCK GAS PIPE
1. FANS SELECTED AT ELEVATION OF 3600 FEET.
MOUNTING FRAME
CONDENSING UNIT MOUNTING PLATFORM
2. PROVIDE FANS WITH FACTORY ROOF CURB, WIRED DISCONNECT, AND BACKDRAFT DAMPER. 3. PROVIDE DIRECT DRIVE FANS WITH FACTORY WIRED FAN SPEED CONTROLLER. FLEX. CONNECTION
4. PROVIDE BELT DRIVE FAN WITH ROTARY BELT TENSIONER.
6
FILL CURB SPACE WITH 6 INCH BATT INSULATION FRAMING AT CURB PERIMETER.
ROOFTOP UNIT MOUNTING DETAIL - RTU 1-18
HUMIDIFIER SCHEDULE MARK
SERVES
CFM
DUCT (WxH)
LBS/HR
KW
STAGES
ELECTRICAL
EXAMPLE: PURE
HUM 1-18
RTU 2-18
1500
24x12
8.5
3.0
SCR
208/3/60
ES-3
HUM 2-18
RTU 3-18
1400
24x12
8.5
3.0
SCR
208/3/60
ES-3
HUM 3-18
RTU 5-18
1400
24x12
8.5
3.0
SCR
208/3/60
ES-3
SYMBOL
AIR DISTRIBUTION SCHEDULE
CABLE SPACING
CABLE OUTPUT (W/FT)
AREA (FT²)
ELECTRICAL
4800
8"
30
108
208/1/60
EM2-XR
2
4800
8"
30
108
208/1/60
EM2-XR
NOTES:
EXAMPLE: PRICE INDUSTRIES
H
S-1
SUPPLY
CEILING
WHITE
LAY-IN
SMD, 24x24
FC
FAN COIL
S-2
SUPPLY
CEILING
WHITE
LAY-IN
SMD, 12x12, AMF FRAME
CU
CONDENSING UNIT
S-3
SUPPLY
CEILING
WHITE
LAY-IN
SMD, 24x24, AMF FRAME
CFM
CUBIC FEET PER MINUTE
S-4
SUPPLY
CEILING
STAINLESS STEEL
SURFACE
LFD3, 48x24
RPM
REVOLUTIONS PER MINUTE
S-5
SUPPLY
DUCT
WHITE
---
SCD, 12x12
HP
MARK
LOCATION
FC 1-18/CU 1-18
ELECTRICAL/INFO TECH 126
EXAMPLE: COOK
S-6
SUPPLY
DUCT
WHITE
---
SCD, 24x24
BTUH
BRITISH THERMAL UNITS PER HOUR
VH 1-18
75
0.004
8PR
S-7
SUPPLY
CEILING
WHITE
LAY-IN
SPD, 24x24, AMF FRAME
MBH
BTUH x 1000
R-1
RETURN
CEILING
WHITE
LAY-IN
80, 24x12
TSP
TOTAL STATIC PRESSURE
1. PROVIDE UNIT WITH FACTORY ROOF CURB.
R-2
RETURN
CEILING
WHITE
LAY-IN
80, 24x24
SP
STATIC PRESSURE
2. PROVIDE UNIT WITH 115V MOTORIZED DAMPER.
R-3
RETURN
CEILING
WHITE
LAY-IN
80, AMF FRAME
EAT
ENTERING AIR TEMPERATURE
R-4
RETURN
SIDEWALL
STAINLESS STEEL
SURFACE
735HF
DB
DRY BULB TEMPERATURE
E-1
EXHAUST
CEILING
WHITE
LAY-IN
80, AMF FRAME
WB
WET BULB TEMPERATURE
E-2
EXHAUST
DUCT
WHITE
LAY-IN
80
ELECTRICAL DATA
EXAMPLE: LG
LIQUID
SUCTION
INDOOR UNIT
OUTDOOR UNIT
INDOOR UNIT
OUTDOOR UNIT
T-1
TRANSFER
CEILING
WHITE
LAY-IN
80, AMF FRAME
1/4
1/2
208/1/60
208/1/60
PLA-A12EA7
PUY-A12NKA7
T-2
TRANSFER
CEILING
WHITE
LAY-IN
80, 24x12
12.0
T
THERMOSTAT
H
HUMIDISTAT
P
PUSH-BUTTON SD
NOTES:
HORSEPOWER
SP
DUCTLESS SPLIT SYSTEM SCHEDULE REFRIGERANT PIPING SIZES
HUMIDIFIER
FRAME
CFM
2. SUBMIT MANUFACTURER PRODUCED DRAWINGS FOR REVIEW PRIOR TO INSTALLATION.
NOMINAL COOLING CAPACITY (MBH)
EXHAUST FAN
MARK
NOTES:
1. ROUTE AND INSTALL CABLING PER MANUFACTURER'S REQUIREMENTS.
EF FINISH
CABLE: RAYCHEM
1
ROOFTOP UNIT
LOCATION
VENTILATION HOOD SCHEDULE WATTS
RTU
TYPE
ELECTRIC SNOW MELT SCHEDULE CIRCUIT
DESCRIPTION
MARK
1. PROVIDE HUMIDIFIERS WITH INJECTION TUBES, FLEXIBLE HOSE, AND WALL BRACKET KIT.
NOTES:
MECHANICAL LEGEND
5
1. PROVIDE INDOOR UNIT WITH CONDENSATE PUMP.
NOTES:
2. PROVIDE WITH MODEL PAR-33MAA-J WIRED THERMOSTAT.
SMOKE DETECTOR
1. COORDINATE FRAME STYLE WITH CEILING LAYOUT.
REFRIGERANT LIQUID
2. PROVIDE S-4 WITH INTERIOR THROAT OPERATED DAMPER.
REFRIGERANT SUCTION
Project
ELBOW TURNED DOWN
ROOFTOP UNIT SCHEDULE
ELBOW TURNED UP
FAN DATA MARK
COOLING DATA
HEATING DATA (S)EER
CFM
MIN OUTSIDE AIR
TSP
HP
TOTAL (MBH)
SENSIBLE (MBH)
EAT (DB/WB)
AMBIENT
RTU 1-18
1600
300
1.8
1
42.8
42.3
78.8/60.1
105
RTU 2-18
1500
300
2.5
2
41.0
39.5
79.2/60.2
RTU 3-18
1400
300
2.5
2
40.7
37.9
79.5/60.4
FINAL FILTER DATA
NOTES
EXAMPLE: AAON
INPUT (MBH)
OUTPUT (MBH)
TURNDOWN RATIO
QTY/SIZE
EFFICIENCY
SERVICE
MCA
MOCP
15.9
122.7
99.4
3.3:1
---
---
208/3/60
28
40
1, 2, 5, 9
RQ-004
105
15.9
122.7
99.4
3.3:1
(1) 24x24x12
99.96%
208/3/60
12/23
20/40
1, 3, 4, 5, 8, 9
RQ-004
105
15.9
87.7
71.0
2.8:1
(1) 24x24x12
99.96%
208/3/60
12/23
20/40
1, 3, 4, 5, 8, 9
RQ-004
CONCEALED DAMPER
RTU 4-18
2400
1000
2.6
3
77.1
73.2
86.9/63.4
105
11.4
184.1
147.3
3:1
(1) 24x24x12 / (1) 24x12x12
99.96%
208/3/60
16/37
30/60
1, 3, 4, 6, 7, 8, 9
RN-008
RTU 5-18
1400
300
2.5
2
40.7
37.9
79.5/60.4
105
15.9
87.7
71.0
2.8:1
(1) 24x24x12
99.96%
208/3/60
12/23
20/40
1, 3, 4, 5, 8, 9
RQ-004
NOTES:
1611 WALLACE BLVD, AMARILLO, TEXAS 79106
MANUAL BALANCING DAMPER
ELECTRICAL DATA
PROFFER SURGICAL CENTER ADDITION
SMOKE DAMPER SUPPLY DUCT - CROSS SECTION
CTB ASSOCIATES A R C H I T E C T S
RETURN DUCT - CROSS SECTION
P L A N N E R S
3003 MONTE VISTA BLVD. NE ALBUQUERQUE, NM 87106 P. (505) 268-3033 F. (505) 212-0354
[email protected]
EXHAUST DUCT - CROSS SECTION
Revisions
1. UNIT SELECTED AT ELEVATION OF 3600 FEET.
SUPPLY DIFFUSER WITH PATTERN
2. PROVIDE UNIT WITH FACTORY ROOF CURB, DISCONNECT, AND POWERED GFCI RECEPTACLE.
1.
3. PROVIDE UNIT WITH FACTORY ROOF CURB AND 26 INCH ROOF CURB EXTENSION TO HOUSE FINAL FILTERS.
Date Issued
JANUARY 29, 2018 Sheet No.
4. PROVIDE UNIT WITH DUAL POWER CONNECTIONS. INFORMATION ABOVE IS FOR CIRCUIT A/ CIRCUIT B. REFER TO SPECIFICATION SECTION 15781. 5. PROVIDE UNIT WITH MOTORIZED OUTSIDE AIR DAMPER.
RETURN GRILLE
2.
EXHAUST GRILLE
3.
6. PROVIDE UNIT WITH 100% OUTSIDE AIR ENTHALPY ECONOMIZER CONTROL WITH POWERED EXHAUST. CONNECT TO EXISTING
7. PROVIDE UNIT WITH VARIABLE CAPACITY COMPRESSOR FOR MODULATING COOLING CONTROL. 8. PROVIDE UNIT WITH MAGNAHELIC GAUGE AND CLOGGED FILTER SWITCH ACROSS FINAL FILTER BANK.
TAS
TEXAS ACCESSIBILITY STANDARDS
9. UNIT SHALL BE FACTORY PAINTED BLACK TO MATCH ROOFTOP UNITS ON EXISTING BUILDING.
AFF
ABOVE FINISHED FLOOR
Sheet Name
MECHANICAL DETAILS AND SCHEDULES
M-4
GENERAL NOTES 1.
COORDINATE ALL DEMOLITION ACTIVITIES WITH ARCHITECTURAL, STRUCTURAL, MECHANICAL, FIRE PROTECTION, AND ELECTRICAL.
2.
CONTRACTOR SHALL FIELD VERIFY EXACT LOCATION, SIZE, AND ELEVATION OF EXISTING UTILITIES PRIOR TO COMMENCING WORK.
3.
CONTRACTOR SHALL SAWCUT AND REMOVE EXISTING SLAB AS REQUIRED TO INSTALL NEW UNDERGROUND SEWER.
4.
ALL TRENCHES THAT ARE OPENED WITHIN EXISTING FACILITY SHALL BE BACKFILLED WITH FLOW FILL AND CONCRETE SLAB SHALL BE REPLACED TO MATCH EXISTING. DRILL AND EPOXY DOWELS INTO EXISTING CONCRETE SLAB TO REINFORCE NEW CONCRETE. DOWELS SHALL BE #3 REBAR 16 INCHES ON CENTER EMBEDDED 6 INCHES INTO EXISTING CONCRETE.
KEYED NOTES 1
REMOVE EXISTING CLEANOUT AND ASSOCIATED VERTICAL RISER PIPING DOWN TO HORIZONTAL MAIN.
2
REMOVE EXISTING CLEANOUT AND ASSOCIATED VERTICAL RISER PIPING DOWN TO HORIZONTAL MAIN AND CAP.
3
REMOVE EXISTING ROOF DRAIN AND OVERFLOW DRAIN DOWNSPOUTS SHOWN DASHED TO ABOVE CEILING. REMOVE ASSOCIATED DOWNSPOUT NOZZLES.
4
EXISTING ROOF DRAIN AND OVERFLOW DRAIN PIPING ABOVE CEILING TO REMAIN.
5
EXISTING 6 INCH ROOF DRAIN AND OVERFLOW DRAIN TO REMAIN. REMOVE ALL ASSOCIATED PIPING SHOWN DASHED.
1 EX 4" EXIST FL = 96'-0"
2
EXIST FL = 96'-0"
EX 2"
EX 4"
3
4
1
EX 4"
EXIST FL = 93'-6"
5
3
EX 6"
3
4
Project
PROFFER SURGICAL CENTER ADDITION 1611 WALLACE BLVD, AMARILLO, TEXAS 79106
CTB ASSOCIATES A R C H I T E C T S
P L A N N E R S
3003 MONTE VISTA BLVD. NE ALBUQUERQUE, NM 87106 P. (505) 268-3033 F. (505) 212-0354
[email protected]
Revisions 1.
Date Issued
JANUARY 29, 2018 Sheet No.
2.
3.
N
1/8" = 1'-0" WASTE AND VENT DEMOLITION FLOOR SCALE: PLAN 0
2'
4'
8'
Sheet Name
WASTE AND VENT DEMOLITION FLOOR PLAN
P-1
GENERAL NOTES 1.
COORDINATE ALL DEMOLITION ACTIVITIES WITH ARCHITECTURAL, STRUCTURAL, MECHANICAL, FIRE PROTECTION, AND ELECTRICAL.
2.
CONTRACTOR SHALL FIELD VERIFY EXACT LOCATION, SIZE, AND ELEVATION OF EXISTING UTILITIES PRIOR TO COMMENCING WORK.
KEYED NOTES
1 2
1
REMOVE EXISTING FREEZE PROOF WALL HYDRANT SHOWN DASHED AND ASSOCIATED PIPING BACK TO ABOVE CEILING AS INDICATED.
2
EXISTING CW PIPING TO REMAIN.
3
REMOVE EXISTING FREEZE PROOF WALL HYDRANT SHOWN DASHED AND ASSOCIATED PIPING BACK TO EXISTING ISOLATION VALVE AS INDICATED.
EX 3/4"
3
EX G
Project
PROFFER SURGICAL CENTER ADDITION 1611 WALLACE BLVD, AMARILLO, TEXAS 79106
CTB ASSOCIATES A R C H I T E C T S
P L A N N E R S
3003 MONTE VISTA BLVD. NE ALBUQUERQUE, NM 87106 P. (505) 268-3033 F. (505) 212-0354
[email protected]
Revisions 1.
Date Issued
JANUARY 29, 2018 Sheet No.
2.
3.
N
SCALE: 1/8" = 1'-0" DOMESTIC WATER AND GAS DEMOLITION FLOOR PLAN 0
2'
4'
8'
Sheet Name
DOMESTIC WATER AND GAS DEMOLITION FLOOR PLAN
P-2
GENERAL NOTES 1.
COORDINATE ALL PIPING WITH ARCHITECTURAL, STRUCTURAL, MECHANICAL, FIRE PROTECTION, AND ELECTRICAL.
2.
CONTRACTOR SHALL FIELD VERIFY EXACT LOCATION, SIZE, AND ELEVATION OF EXISTING UTILITIES PRIOR TO COMMENCING WORK.
3.
CONTRACTOR SHALL ESTABLISH GRADES AND CONNECTION POINTS TO EXISTING UTILITIES PRIOR TO COMMENCING WORK.
4.
CONTRACTOR SHALL SAWCUT AND REMOVE EXISTING SLAB AS REQUIRED TO INSTALL NEW UNDERGROUND SEWER.
5.
ALL TRENCHES THAT ARE OPENED WITHIN EXISTING FACILITY SHALL BE BACKFILLED WITH FLOW FILL AND CONCRETE SLAB SHALL BE REPLACED TO MATCH EXISTING. DRILL AND EPOXY DOWELS INTO EXISTING CONCRETE SLAB TO REINFORCE NEW CONCRETE. DOWELS SHALL BE #3 REBAR 16 INCHES ON CENTER EMBEDDED 6 INCHES INTO EXISTING CONCRETE.
6.
ROUTE STORM DRAIN PIPING AS HIGH AS POSSIBLE.
7.
REFER TO ARCHITECTURAL ELEVATIONS FOR INSTALLATION HEIGHTS OF STORM DRAIN DOWNSPOUT NOZZLES.
8.
ALL PLUMBING VENTS THRU ROOF SHALL BE MINIMUM 25'-0" FROM ANY OUTSIDE AIR INTAKE SERVING PATIENT CARE AREAS. REFER TO PLUMBING ROOF PLAN ON SHEET P-5.
CO
2" VTR
P-1
2 P-10
P-2
2" VTR
3
KEYED NOTES
4"
2"
1
CONNECT 1 INCH CONDENSATE DRAIN PIPING TO FAN COIL UNIT AND ROUTE ABOVE CEILING AS SHOWN.
2
CONNECT 3 INCH WASTE TO MOP BASIN AND ROUTE 2 INCH VENT UP IN WALL AS SHOWN.
3
3 INCH DOWNSPOUTS FROM ROOF DRAIN AND OVERFLOW DRAIN. ROUTE ABOVE CEILING AS SHOWN.
4
4 INCH DOWNSPOUTS FROM ROOF DRAIN AND OVERFLOW DRAIN. ROUTE ABOVE CEILING AS SHOWN.
5
CONNECT NEW 4 INCH SEWER TO EXISTING AND ROUTE AS SHOWN TO SERVE ADDITION.
6
CONNECT 1 INCH DRAIN TO HUMIDIFIER AND ROUTE AS SHOWN FOR TERMINATION TO OPEN SITE DRAIN. REFER TO MANUFACTURER'S INSTALLATION MANUAL FOR DRAIN PIPING CONSTRUCTION.
7
INSTALL OPEN SITE DRAIN IN VERTICAL VENT PIPING FROM FIXTURE AND TERMINATE 1 INCH DRAIN PIPING WITH AIR GAP. PROVIDE ACCESS DOOR IN CEILING TO SERVICE OSD.
8
CONNECT NEW 4 INCH PIPING TO EXISTING ROOF DRAIN AND OVERFLOW DRAIN DOWNSPOUTS. EXTEND PIPING ABOVE CEILING AS SHOWN.
9
ROUTE 6 INCH ROOF DRAIN AND OVERFLOW DRAIN PIPING DOWN IN WALL TO DOWNSPOUT NOZZLES.
10
6 INCH DOWNSPOUTS FROM ROOF DRAIN AND OVERFLOW DRAIN. ROUTE ABOVE CEILING AS SHOWN TO EXTERIOR WALL. ROUTE 6 INCH ROOF DRAIN AND OVERFLOW DRAIN DOWNSPOUTS DOWN IN WALL TO DOWNSPOUT NOZZLES.
11
ROUTE 2 INCH VENT PIPING IN WALL BELOW WINDOW AND UP IN ADJACENT WALL AS SHOWN.
12
INSTALL OPEN SITE DRAIN IN VERTICAL VENT PIPING FROM FIXTURE AND TERMINATE 1 INCH DRAIN PIPING WITH AIR GAP. PROVIDE ACCESS DOOR IN CEILING TO SERVICE OSD.
13
CONNECT NEW 6 INCH PIPING TO EXISTING ROOF DRAIN AND OVERFLOW DRAIN. EXTEND PIPING ABOVE CEILING AS SHOWN.
14
CONNECT NEW 6 INCH PIPING TO EXISTING ROOF DRAIN AND OVERFLOW DRAIN DOWNSPOUTS. EXTEND PIPING ABOVE CEILING AS SHOWN.
15
ROUTE 6 INCH ROOF DRAIN AND OVERFLOW DRAIN DOWNSPOUTS DOWN IN WALL TO BELOW FINISHED FLOOR. PENETRATE WALL AND INSTALL DOWNSPOUT NOZZLES AT 18 INCHES ABOVE FINISHED GRADE.
16
4 INCH DOWNSPOUTS FROM ROOF DRAIN AND OVERFLOW DRAIN. ROUTE ABOVE CEILING AS SHOWN TO EXTERIOR WALL. ROUTE 4 INCH ROOF DRAIN AND OVERFLOW DRAIN DOWNSPOUTS DOWN IN WALL TO DOWNSPOUT NOZZLES.
4
P-4 WCO
P-1
5 2" FD 2"
P-2 CO
4"
4"
HUM 1-18
4"
EX 4"
1" 6 2" OSD
P-4 4" P-4 WCO
7 EX 4" 8
2" 4"
6"
P-4 WCO 2"
2" VTR
2" FD
6" DSN 6" DSN
2" VTR
9
P-4 2"
2"
P-2 WCO 6" DSN
2" FD
6" DSN
2"
EX 3" VTR
4" P-1
P-2 2" FD 4"
EX 3"
EX 2"
5
4"
EX 2"
4"
EX 3"
EX 2"
EX 3"
CO EX 4" P-1
EX 3" VTR
EX 2"
EX 3"
EX 4" EX 2"
EX 4" EX 4"
EX 4"
EX 2"
10 EX 2" 13
EX 2"
2"
EX 2"
14
4"
EX 3" 4"
2"
P-1
EX 2" FS
EX 6"
P-1 P-5
P-3
EX 2" P-3
P-5
EX CO
6" DSN 6" DSN
11
EX WCO
EX 2"
EX 2"
15 2"
P-9
HUM 2-18
2" Project
P-4 3"
2"
6 HUM 3-18
P-9 WCO
1"
P-4 3" VTR 3" FS
12 P-10
OSD
11
PROFFER SURGICAL CENTER ADDITION 1611 WALLACE BLVD, AMARILLO, TEXAS 79106
2" 3"
2 2"
1"
3" FS
D
3" FS P-6 WCO
P-7
CTB ASSOCIATES
P-8
A R C H I T E C T S
P L A N N E R S
3003 MONTE VISTA BLVD. NE ALBUQUERQUE, NM 87106 P. (505) 268-3033 F. (505) 212-0354
[email protected]
4" DSN 4" DSN
CO Revisions
16 1
1.
Date Issued
JANUARY 29, 2018
2" Sheet No. 2. D
FC 1-18
2" VTR
3.
N
SCALE: 1/8" = 1'-0" WASTE AND VENT FLOOR PLAN 0
2'
4'
8'
Sheet Name
WASTE AND VENT FLOOR PLAN
P-3
GENERAL NOTES 1.
COORDINATE ALL PIPING WITH ARCHITECTURAL, STRUCTURAL, MECHANICAL, FIRE PROTECTION, AND ELECTRICAL.
2.
CONTRACTOR SHALL FIELD VERIFY EXACT LOCATION, SIZE, AND ELEVATION OF EXISTING UTILITIES PRIOR TO COMMENCING WORK.
3.
CONTRACTOR SHALL ESTABLISH GRADES AND CONNECTION POINTS TO EXISTING UTILITIES PRIOR TO COMMENCING WORK.
KEYED NOTES
FPWH
P-1
P-10
P-2
1
1
ROUTE 1-1/2 INCH CW AND 3/4 INCH HW PIPING DOWN IN WALL. CONNECT 1/2 INCH CW AND HW PIPING TO LAVATORY. EXTEND 1-1/2 INCH CW AND 1/2 INCH HW PIPING IN WALL TO SERVE FIXTURES. CONNECT 1-1/2 INCH CW PIPING TO WATER CLOSET AND 3/4 INCH CW PIPING TO FREEZE PROOF WALL HYDRANT. CONNECT 1/2 INCH CW AND HW PIPING TO MOP BASIN.
2
ROUTE 1/2 INCH CW AND HW PIPING DOWN IN WALL TO SERVE FIXTURE.
3
INSTALL HW CIRCULATION BALANCE VALVE. REFER TO SPECIFICATION SECTION 15410.
4
ROUTE 1-1/2 INCH CW AND 1/2 INCH HW PIPING DOWN IN WALL. CONNECT 1/2 INCH CW AND HW PIPING TO LAVATORY. EXTEND 1-1/2 INCH CW PIPING IN WALL TO SERVE WATER CLOSET.
5
CAP EXISTING 3/4 INCH CW PIPING ABOVE CEILING.
6
ROUTE 3/4 INCH CW PIPING DOWN IN WALL TO SERVE FREEZE PROOF WALL HYDRANT.
7
ROUTE 3/4 INCH CW PIPING DOWN IN WALL TO SERVE ICE MACHINE. INSTALL ISOLATION BALL VALVE AND WATTS SERIES LF7 DUAL CHECK VALVE ABOVE LAY-IN CEILING. COORDINATE FINAL TERMINATION TO ICE MACHINE WITH EQUIPMENT PROVIDER.
8
CONNECT NEW 1-1/2 INCH CW PIPING TO EXISTING AND ROUTE AS SHOWN TO SERVE NEW ADDITION.
9
ROUTE 1-1/2 INCH CW PIPING DOWN IN WALL TO SERVE WATER CLOSET.
10
MOUNT WATER SOFTENER ON 4 INCH CONCRETE HOUSEKEEPING PAD. REFER TO DETAIL 6/P-6 FOR PIPING CONNECTIONS.
11
1 INCH GAS PIPING DOWN THRU ROOF TO SERVE WATER HEATER. PROVIDE GAS COCK, DIRT LEG, AND FLEXIBLE CONNECTION.
12
MOUNT WATER HEATER ON 4 INCH CONCRETE HOUSEKEEPING PAD. REFER TO DETAIL 7/P-6 FOR WATER PIPING CONNECTIONS. CONNECT 3 INCH SCHEDULE 40 PVC COMBUSTION AIR INTAKE AND FLUE VENT PIPING TO WATER HEATER AND TERMINATE THRU ROOF USING MANUFACTURER PROVIDED CONCENTRIC VENT KIT.
13
INSTALL THERMOSTATIC MIXING VALVE ON WALL IN AREA SHOWN DASHED. REFER TO DETAIL 7/P-6 FOR PIPING CONNECTIONS.
14
ROUTE 3/4 INCH CW AND HW PIPING DOWN IN WALL TO SERVE FIXTURE. EXTEND 3/4 INCH CW PIPING IN WALL TO SERVE FREEZE PROOF WALL HYDRANT.
15
ROUTE 1-1/2 INCH CW AND 3/4 INCH HW PIPING DOWN IN WALL TO SERVE FIXTURES. CONNECT 1-1/2 INCH CW AND 1/2 INCH HW PIPING TO CLINICAL SERVICE SINK. EXTEND 1/2 INCH CW AND HW PIPING IN WALL TO SERVE HAND SINK.
3/4"
1-1/2" 2
3
5
1/2"
P-4 P-1 1-1/2"
P-2
3/4" 3
4
1/2" P-4
1/2"
P-4 2
3/4" 1-1/2"
FPWH
P-4 1"
6
2 7 2 3/4"
4 P-4
1-1/2"
P-2
1/2"
4
P-1
1-1/2"
8 3/4"
P-2
1-1/2" 1-1/2" 3
P-1
1-1/2"
9
9
P-1
1-1/2"
1-1/2"
2
P-1
P-5
P-3 2
2
2
P-3
P-5
1"
2
6
1-1/2"
1"
FPWH
EX G
EX WH-1 P-9
1/2"
1-1/4"
3/4"
P-4
2
Project
3
3/4" 1/2" 3/4" P-9
1-1/2"
P-4
2
SCW
3 11 1"
P-10
WS 1-18
1611 WALLACE BLVD, AMARILLO, TEXAS 79106
10 1-1/2"
2
2
12
1-1/2"
PROFFER SURGICAL CENTER ADDITION
WH 1-18 1" 13 P-6
P-8
CTB ASSOCIATES A R C H I T E C T S
14
P-7
P L A N N E R S
3003 MONTE VISTA BLVD. NE ALBUQUERQUE, NM 87106 P. (505) 268-3033 F. (505) 212-0354
[email protected]
FPWH 15 Revisions 1.
Date Issued
JANUARY 29, 2018 Sheet No.
2.
3.
N
1/8" = 1'-0" DOMESTIC WATER AND GAS FLOORSCALE: PLAN 0
2'
4'
8'
Sheet Name
DOMESTIC WATER AND GAS FLOOR PLAN
P-4
GENERAL NOTES
2" VTR
1.
COORDINATE ALL PIPING WITH ARCHITECTURAL, STRUCTURAL, MECHANICAL, AND ELECTRICAL.
2.
CONTRACTOR SHALL FIELD VERIFY EXACT LOCATION, SIZE, AND ELEVATION OF EXISTING UTILITIES PRIOR TO COMMENCING WORK.
3.
CONTRACTOR SHALL ESTABLISH GRADES AND CONNECTION POINTS TO EXISTING UTILITIES PRIOR TO COMMENCING WORK.
4.
DO NOT INSTALL PLUMBING VENTS OR EXHAUST FANS WITHIN 25'-0" OF OUTSIDE AIR INTAKES OF NEW OR EXISTING ROOFTOP UNITS SERVING PATIENT CARE AREAS.
5.
INSTALL TYPE L COPPER P-TRAP ON CONDENSATE DRAIN LINE CONNECTION FROM EACH NEW ROOFTOP UNIT. DISCHARGE CONDENSATE INTO 18x18x6 DRIP PAN ON ROOF. SECURE DRIP PAN TO ROOF USING COMPOUND COMPATIBLE WITH ROOFING ASSEMBLY.
6.
INSTALL GAS PIPING ON ROOF TO MAINTAIN SERVICE CLEARANCES FOR ALL ROOF MOUNTED EQUIPMENT.
7.
SUPPORT ALL NEW GAS PIPING ON ROOF USING MAPA MS-4 OR MS-5 ROLLER SUPPORTS. MAINTAIN MINIMUM 8 INCHES CLEARANCE BETWEEN PIPING AND FINISHED ROOF ASSEMBLY. REFER TO DETAIL 4/P-6.
8.
ALL NEW GAS PIPING ON ROOF SHALL BE PAINTED AS DIRECTED BY ARCHITECT.
9.
THE EXISTING GAS METER SERVING THE EXISTING FACILITY WILL BE REPLACED BY ATMOS ENERGY. CONTRACTOR SHALL CONTACT ATMOS ENERGY PRIOR TO CONSTRUCTION TO COORDINATE INSTALLATION OF METER. THE NEW GAS METER SHALL BE CAPABLE OF DELIVERING 1,900 CFH WITH AN OUTLET PRESSURE OF 2 PSIG. CONTACT CAL BRANNON AT (806) 379-5815.
EF 1-18
KEYED NOTES
1" 1
2" VTR 3" RD 3" OD
4" RD
EX 3" VTR
EX RTU-3 2
EX 2" VTR
EX EF-9
4" OD 25'-0"
1
CONNECT 1 INCH GAS PIPING TO ROOFTOP UNIT. PROVIDE GAS COCK, DIRT LEG, AND FLEXIBLE CONNECTION.
2
ROOFTOP DOES NOT SERVE PATIENT CARE AREAS, THEREFORE, OUTSIDE AIR INTAKE IS NOT REQUIRED TO BE MINIMUM OF 25'-0" FROM PLUMBING VENTS OR ROOF EXHAUST.
3
CONNECT 1-1/4 INCH GAS PIPING TO ROOFTOP UNIT. PROVIDE GAS COCK, DIRT LEG, AND FLEXIBLE CONNECTION.
4
ROUTE NEW GAS PIPING UP AND OVER PARAPET WALL FROM EXISTING TO NEW ROOF.
5
ROUTE 1 INCH GAS PIPING DOWN THRU ROOF TO SERVE WATER HEATER. MAKE ROOF PENETRATION THRU CHEMCURB AND COMPLETELY FILL WITH CHEMLINK COMPOUND. REFER TO P-4 FOR CONTINUATION.
6
CONCENTRIC VENT FROM WH 1-18.
7
MEDICAL VACUUM PUMP EXHAUST VENT.
8
CONNECT NEW 3 INCH GAS PIPING TO EXISTING AND ROUTE AS SHOWN TO SERVE NEW ADDITION.
EX 2" VTR
RTU 1-18
EX RTU-8
G
EX EF-8
EX RTU-6 1" EX 1-1/4" RTU 2-18
1
EX EF-7
EX 1-1/4"
1"
EX RTU-1
EX G
EX G
G
EX CU-1
25'-0"
G
EX 1-1/2"
EX RTU-4
EX RTU-9 EX RTU-7
EX G
EF 2-18
2" VTR
2" VTR
EX 1-1/4"
EX RTU-2
EX G
EX 1-1/4" EX 2"
EX 1-1/2"
EX 1-1/4"
EX 2"
EX 1-1/2"
25'-0"
EX 2"
EX G
EX G
EX EF-1
G
EX RTU-5
6" OD
1-1/4"
EX G
25'-0"
EX 3" VTR
EX 1-1/4"
EX 3" VTR
EX 3" VTR
VH 1-18
EX 3"
EX EF-2
6" RD 4
8
3"
3"
3" G
EX EF-3 RTU 3-18
EX EF-6
G
EX EF-4 EX 3/4"
2"
EX G
EX 3" EX EF-5
1"
1
G
25'-0" G
RTU 4-18 Project
1-1/2" 3 3" VTR 1-1/4" 1-1/4"
1611 WALLACE BLVD, AMARILLO, TEXAS 79106
5 6
1"
PROFFER SURGICAL CENTER ADDITION
G
RTU 5-18 1"
25'-0"
7
CTB ASSOCIATES
1 25'-0"
A R C H I T E C T S
G
EF 4-18
P L A N N E R S
3003 MONTE VISTA BLVD. NE ALBUQUERQUE, NM 87106 P. (505) 268-3033 F. (505) 212-0354
[email protected]
4" RD 4" OD
Revisions
EF 3-18
1.
Date Issued
JANUARY 29, 2018 Sheet No.
2.
EF 5-18 CU 1-18
2" VTR
3.
N
PLUMBING ROOF PLAN
SCALE: 1/8" = 1'-0" 0
2'
4'
8'
Sheet Name
PLUMBING ROOF PLAN
P-5
1/2" WATER SUPPLY FROM NEAREST WATER LINE PROVIDE ISOLATION BALL VALVE AT CONNECTION TO MAIN.
PIPING CONDENSATE/OVERFLOW DRAIN PIPING ROLLER
MIFAB M2-500 TRAP PRIMER MAY EXTEND AS WASTE OR VENT
CAST IRON FERRULE W/COUNTERSUNK BRASS CLEANOUT PLUG. WALL
INSTALL FLUSH VALVE WITH HANDLE FACING OPEN PORTION OF TAS STALL
1/8 BEND
WADE W-2452-T-6 WITH 1/2" TRAP PRIMER FITTING.
PLUGGED TEE W/ CLEANOUT
1/2"
2" WASTE OUTLET
15"x15"x6" CONCRETE SLAB FLUSH W/GRADE
45° WYE
MIFAB MI-GAP AIR GAP FITTING
WALL
FLOOR LINE
WATER CLOSET
MOUNT AIR GAPS AT SAME LEVEL
WADE W-2491-1/2x2 AIR GAP FITTING
CHROME WALL COVER & SCREW
2" ABOVE LANDSCAPED GRADE
GRADE
MAPA PRODUCTS MS-4
1/8" BEND
8"
16"-18" BALANCE OF PIPING SAME AS CLEANOUT TO GRADE
CL LONG SWEEP
FLOOR MOUNT WATER CLOSET INSTALLATION - TAS
EXTERIOR CLEANOUT DETAIL
1
WALL CLEANOUT DETAIL
2
GAS PIPE SUPPORT DETAIL
3
OPEN SITE DRAIN DETAIL
4
5
1-1/2" CW SERVICE EXPANSION TANK
1" SCW
1-1/2"
1"
1-1/4"
1-1/2" BYPASS (NORMALLY CLOSED)
SOFT COLD WATER PIPING TO SERVE WATER HEATER
1-1/2"
1-1/2" BALL VALVE
SCW
CHECK VALVE
GAS COCK
CP-1
1-1/2"
PLUMBING LEGEND
1" FROM SYSTEM
1-1/2"
G
DESCRIPTION
TO SYSTEM
6" DIRT LEG
EXTEND 1" TO FLOOR SINK
SYMBOL
1-1/2" 1"
CONNECT FULL SIZE RELIEF TO T&P VALVE AND EXTEND TO MOP BASIN
VENT THRU ROOF
1-1/2"
CLEANOUT WALL CLEANOUT SANITARY SOIL LINE
CONNECT FULL SIZE DRAIN TO CONDENSATE DRAIN AND EXTEND TO MOP BASIN
SANITARY VENT LINE COLD WATER
UNION CULLIGAN MODEL SMF-185 WATER SOFTENER
HOT WATER
THERMOSTATIC MIXING VALVE RADA MODEL 425R
CW SUPPLY
HOT WATER RETURN
MOUNT WATER HEATER IN GALVANIZED STEEL DRAIN PAN
BRINE TANK 4" CONCRETE EQUIPMENT PAD
SOFTENED COLD WATER
SCW
THERMOSTATIC RETURN LIMITER
G
GAS
D
CONDENSATE DRAIN
HW RETURN FROM SYSTEM
BALL VALVE
HW SUPPLY FROM WATER HEATER
4" CONCRETE HOUSEKEEPING PAD
WATER SOFTENER PIPING DIAGRAM
HW SUPPLY TO SYSTEM
NOTE: REFER TO PLANS FOR COMBUSTION AIR INTAKE AND FLUE VENT PIPING CONNECTIONS AND TERMINATION.
FINISHED FLOOR
CHECK VALVE
FLOW IN DIRECTION OF ARROW
WATER HEATER PIPING DETAIL
6
UNION
7
AFF
ABOVE FINISHED FLOOR
TAS
TEXAS ACCESSIBILITY STANDARD CONNECT TO EXISTING
Project
PLUMBING FIXTURE CONNECTION SCHEDULE
PROFFER SURGICAL CENTER ADDITION 1611 WALLACE BLVD, AMARILLO, TEXAS 79106
CONNECTIONS FIXTURE
MARK
CW
HW
WASTE
VENT
FPWH
FREEZE PROOF WALL HYDRANT
3/4
---
---
---
2" FD
2 INCH FLOOR DRAIN, ROUND STRAINER
---
---
2
---
3" FS
12x12x3 FLOOR SINK, FULL GRATE, DOME STRAINER
---
---
3
---
1-1/2
---
4
2
P-1
WATER CLOSET, FLOOR MOUNT, SENSOR FLUSH VALVE - TAS
P-2
COUNTER W/ INTEGRAL LAVATORY (PUBLIC) - TAS
1/2
1/2
2
2
P-3
COUNTER W/ INTEGRAL LAVATORY - TAS
1/2
1/2
2
2
P-4
COUNTER W/ INTEGRAL HAND SINK - TAS
1/2
1/2
2
2
P-5
SHOWER - TAS
1/2
1/2
2
2
P-6
WALL HUNG HAND SINK - TAS
P-7
CLINICAL SERVICE SINK
P-8
WATER SOFTENER SCHEDULE MARK
CONTINUOUS/PEAK GPM AT 15/25 PSI DROP
WS 1-18
INLET SIZE
30/40
BRINE TANK CAPACITY
1-1/2"
80 GALLONS
ELECTRICAL
CTB ASSOCIATES
EXAMPLE: CULLIGAN
120/1/60
A R C H I T E C T S
P L A N N E R S
3003 MONTE VISTA BLVD. NE ALBUQUERQUE, NM 87106 P. (505) 268-3033 F. (505) 212-0354
[email protected]
SMF-185
EXPANSION TANK SCHEDULE NOTES:
1. PROVIDE WITH INITIAL SALT FILL AND TEST KIT. SYSTEM WH 1-18
WATER HEATER SCHEDULE MARK
SIZE IN GALLONS
TYPE
INPUT (MBH)
EFFICIENCY
RECOVERY (GPH)
ELECTRICAL
EXAMPLE: A.O. SMITH
WH 1-18
60
NATURAL GAS
120.0
95%
154
120/1/60
BTH-120
1/2
1/2
2
2
1-1/2
1/2
4
2
THREE COMPARTMENT DECONTAMINATION SINK
1/2
1/2
2
2
P-9
SURGICAL SCRUB SINK, TWO STATIONS
1/2
1/2
2
2
2. PROVIDE WITH CONCENTRIC VENT KIT AND CONDENSATE NEUTRALIZATION KIT.
P-10
MOP BASIN CORNER TERRAZZO, 32x32x12
1/2
1/2
3
2
3. UNIT SHALL BE CAPABLE OF OPERATING AT ELEVATION OF 3600 FEET.
NOTES:
1. RECOVERY RATE BASED ON TEMPERATURE RISE OF 90°F.
ACCEPTANCE VOLUME @ 60 PSIG MAX WORKING PRESSURE 2.2 GALLONS
150 PSIG
EXAMPLE; STATE ETC-5X
Revisions 1.
Date Issued
JANUARY 29, 2018 Sheet No.
2.
HOT WATER CIRCULATOR SCHEDULE
3.
MARK
SYSTEM
GPM
HEAD (FT)
HP
ELECTRICAL
EXAMPLE: GRUNDFOS
CP 1-18
WH 1-18
4
8
1/25
115/1/60
UP15-18B5
NOTES:
1. PUMP SHALL BE LEAD-FREE CONSTRUCTION.
Sheet Name
PLUMBING DETAILS AND SCHEDULES
P-6
GENERAL NOTES 1.
COORDINATE ALL PIPING AND EQUIPMENT WITH ARCHITECTURAL, STRUCTURAL, MECHANICAL, PLUMBING, FIRE PROTECTION, AND ELECTRICAL.
2.
REFER TO ARCHITECTURAL ELEVATIONS FOR EXACT LOCATION AND ELEVATIONS OF MEDICAL GAS OUTLETS.
3.
ALL DROPS TO OUTLETS SHALL BE 1/2 INCH OXYGEN, 1/2 INCH NITROGEN, 1/2 INCH NITROUS OXIDE, 1/2 INCH MEDICAL AIR, 3/4 INCH VACUUM, AND 3/4 INCH EVACUATION UNLESS NOTED OTHERWISE.
4.
ALL CEILING MOUNTED MEDICAL GAS OUTLETS SHALL BE PROVIDED WITH HOSE KITS AND HOSE RETRACTORS. REFER TO SPECIFICATION SECTION 15482.
KEYED NOTES
2
1
INSTALL PRE/POST-OP AREA ZONE VALVE BOX (PATTONS MEDICAL ZVM-050507) IN INTERVIEW 103 WALL. DROP 1/2 INCH OXYGEN, 1/2 INCH MEDICAL AIR, AND 3/4 INCH VACUUM PIPING DOWN IN WALL TO ZONE VALVE. TERMINATE ALL PIPING TO ZONE VALVE AND ROUTE TO SERVE PRE/POST-OP AREA AS SHOWN. REFER TO DETAIL 1/MG-2.
2
INSTALL PRESSURE SWITCH IN OXYGEN, MEDICAL AIR, AND VACUUM PIPING FROM ZONE VALVE. PULL 2 CONDUCTOR, 22 AWG WIRING FROM EACH PRESSURE SENSOR SWITCH TO COMBINATION MASTER/AREA ALARM PANEL LOCATED IN NURSE STATION 107. REFER TO SPECIFICATION SECTION 15482.
3
ROUTE 1/2 INCH OXYGEN, 1/2 INCH MEDICAL AIR, AND 3/4 INCH VACUUM PIPING DOWN IN WALL TO SERVE OUTLETS.
4
INSTALL COMBINATION MASTER/AREA ALARM PANEL (PATTONS MEDICAL A1A-02VN02MOAV) TO SERVE OPERATING ROOMS AND PRE/POST-OP AREAS. TERMINATE WIRING FROM SYSTEM MANIFOLDS AND PRESSURE SWITCHES.
5
CONNECT 1/2 INCH OXYGEN, 1/2 INCH NITROGEN, 1/2 INCH NITROUS OXIDE, 1/2 INCH MEDICAL AIR, 3/4 INCH VACUUM, AND 3/4 INCH EVACUATION PIPING TO CEILING MED GAS OUTLETS. PROVIDE (1) OXYGEN, (1) NITROGEN, (1) MEDICAL AIR, (2) VACUUM, AND (1) EVACUATION OUTLETS.
6
INSTALL PRESSURE SWITCH IN EACH BRANCH LINE SERVING OPERATING ROOM AREA. PULL 2 CONDUCTOR, 22 AWG WIRING FROM EACH PRESSURE SWITCH TO COMBINATION MASTER/AREA ALARM PANEL LOCATED IN NURSE STATION 107.
7
INSTALL OPERATING ROOM ZONE VALVE BOX (PATTONS MEDICAL ZVM-0505050510) IN CORRIDOR WALL. DROP 1/2 INCH OXYGEN, 1/2 INCH NITROGEN, 1/2 INCH NITROUS OXIDE, 1/2 INCH MEDICAL AIR, AND 1 INCH VACUUM PIPING DOWN IN WALL TO ZONE VALVE. TERMINATE ALL PIPING TO ZONE VALVE AND ROUTE TO SERVE OPERATING ROOM AS SHOWN. REFER TO DETAIL 2/MG-2.
8
INSTALL NITROGEN CONTROL PANEL (PATTONS MEDICAL GCP-H-NIT) IN OPERATING ROOM WALL. ROUTE 1/2 INCH NITROGEN PIPING FROM ZONE VALVE TO CONTROL PANEL. TERMINATE PIPING TO CONTROL PANEL AND ROUTE AS SHOWN TO SERVE OPERATING ROOM. MAINTAIN 3'-0" CLEAN FROM EDGE OF DOOR TO INTERIOR OR ROOM FOR ELECTRICAL DEVICES. PIPING IS SHOWN SCHEMATICALLY FOR CLARITY.
9
INSTALL ZONE VALVE (PATTONS MEDICAL ZVM-07) IN CORRIDOR WALL. DROP 3/4 INCH VACUUM PIPING DOWN IN WALL AND TERMINATE TO ZONE VALVE. EXTEND PIPING AS SHOWN TO SERVE RECEIVING/DECON/SOILED 123.
10
ROUTE 3/4 INCH VACUUM PIPING DOWN IN WALL AND TERMINATE TO OUTLET.
11
EXTEND 2 INCH MEDICAL VACUUM DISCHARGE PIPING UP THRU ROOF. MAKE ROOF PENETRATION THRU CHEMCURB AND COMPLETELY FILL WITH CHEMLINK COMPOUND. TERMINATE INTAKE PIPING WITH GOOSENECK AT 36 INCHES ABOVE FINISHED ROOF ASSEMBLY. INSTALL STAINLESS STEEL FILTER SCREEN OVER END OF PIPING.
12
MOUNT MEDICAL VACUUM SKID ON 4 INCH CONCRETE HOUSEKEEPING PAD. REFER TO DETAIL 8/MG-2 FOR PIPING CONNECTIONS.
13
INSTALL PRESSURE SWITCH IN MEDICAL AIR MAIN. PULL 2 CONDUCTOR, 22 AWG WIRING FROM PRESSURE SWITCH TO COMBINATION MASTER/AREA ALARM PANEL LOCATED IN NURSE STATION 107.
14
MOUNT MEDICAL AIR SUPPLY MANIFOLD ON WALL AT 60 INCHES AFF. REFER TO DETAIL 5/MG-2 FOR PIPING CONNECTIONS.
15
MOUNT NITROGEN SUPPLY MANIFOLD ON WALL AT 60 INCHES AFF. REFER TO DETAIL 6/MG-2 FOR PIPING CONNECTIONS.
16
INSTALL PRESSURE SWITCH IN NITROGEN MAIN. PULL 2 CONDUCTOR, 22 AWG WIRING FROM PRESSURE SWITCH TO COMBINATION MASTER/AREA ALARM PANEL LOCATED IN NURSE STATION 107.
17
MOUNT NITROUS OXIDE SUPPLY MANIFOLD ON WALL AT 60 INCHES AFF. REFER TO DETAIL 7/MG-2 FOR PIPING CONNECTIONS.
18
INSTALL PRESSURE SWITCH IN NITROUS OXIDE MAIN. PULL 2 CONDUCTOR, 22 AWG WIRING FROM PRESSURE SWITCH TO COMBINATION MASTER/AREA ALARM PANEL LOCATED IN NURSE STATION 107.
19
MOUNT OXYGEN SUPPLY MANIFOLD ON WALL AT 60 INCHES AFF. REFER TO DETAIL 4/MG-2 FOR PIPING CONNECTIONS.
20
INSTALL PRESSURE SWITCH IN OXYGEN MAIN. PULL 2 CONDUCTOR, 22 AWG WIRING FROM PRESSURE SWITCH TO COMBINATION MASTER/AREA ALARM PANEL LOCATED IN NURSE STATION 107.
1
1"
A O V
1/2" 3-V 3-S 1-B 1-O 1-A
3 1/2"
A O V
3/4"
1/2"
3-V 3-S 1-B 1-O 1-A
4
1" 1" 3/4" V O A
1/2" 1/2"
3
A O V
3-V 3-S 1-B 1-O 1-A
3/4" V O A
3-V 3-S 1-B 1-O 1-A
1/2"
3
3/4" V O A
3-V 3-S 1-B 1-O 1-A
3/4" V O A
1/2" 3
3
1/2" 1/2" A O V
3-V 3-S 1-B 1-O 1-A
A O V
3/4"
1/2"
1"
6
5
1/2" 7
O A N20 EVAC V
3/4" N
1/2"
8
1-1/4" 1/2" N20 N A O V
Project
1611 WALLACE BLVD, AMARILLO, TEXAS 79106
11
9
10
1/2" N
8
3/4"
1-V
1/2"
V
16
NSM 1-18
NOSM 1-18
2"
18
MV 1-18
CTB ASSOCIATES
O N20
A
V
1-1/2"
EVAC V
5
3/4"
PROFFER SURGICAL CENTER ADDITION
12
15
13
N20
17
19
A R C H I T E C T S
1/2" N
1/2"
1/2"
7
A
1"
1/2"
14
MASM 1-18
O
16
NSM 1-18
NOSM 1-18
18
13
15
19
P L A N N E R S
3003 MONTE VISTA BLVD. NE ALBUQUERQUE, NM 87106 P. (505) 268-3033 F. (505) 212-0354
[email protected]
17
Revisions
OSM 1-18
20
N20
1/2"
N
1.
1/2"
1/2"
Date Issued
JANUARY 29, 2018
A
MASM 1-18
1/2"
14 O
Sheet No.
NORTH
2. OSM 1-18
REFER TO ENLARGED PLAN THIS SHEET FOR WORK IN THIS AREA
20
ENLARGED MEDICAL GAS FLOOR PLAN - MED GAS 127 1/4" = 1'-0"
N
MEDICAL GAS FLOOR PLAN
SCALE: 1/8" = 1'-0" 0
2'
4'
8'
0
1'
2'
4'
3.
8' Sheet Name
MEDICAL GAS FLOOR PLAN
MG-1
ABOVE CEILING
ABOVE CEILING
FROM SOURCE
1/2"
TEE EVAC LINE INTO VAC LINE
TO OPERATING ROOM WIRE FROM SENSORS TO COMBINATION MASTER/AREA ALARM PANEL IN CONTROL 113
3/4" 1/2" 3/4"
1" ABOVE CEILING
1/2"
ABOVE CEILING WIRE FROM SENSORS TO COMBINATION MASTER/AREA ALARM PANEL IN NURSE STATION 107
FROM SOURCE 3/4"
1/2"
O
1/2"
O
A
TO PRE/POST-OP AREA
A
V
COMBINATION MASTER/AREA ALARM PANEL LOCATED IN NURSE STATION 107
V NO NO
N
N
1/2"
ABOVE CEILING
ABOVE CEILING
FROM SOURCE
TO RECEIVING/DECON/ SOILED 123
3/4"
1/2" O A
O
A
O
A
COMBINATION MASTER/AREA ALARM PANEL LOCATED IN NURSE STATION 107
V
V
3/4"
V
WIRE FROM SENSORS TO COMBINATION MASTER/AREA ALARM PANEL IN NURSE STATION 107
NO N EV V
O A V
3/4"
NOTE: SENSORS TO BE INSTALLED ONLY OUTSIDE OF OR 1 AS SHOWN ON MG-1.
ZONE VALVE FOR EACH MED. GAS
PRE/POST-OP ZONE VALVE DETAIL
ZONE VALVE FOR EACH MED. GAS
OPERATING ROOM ZONE VALVE DETAIL
1
CONNECT ALARM SWITCH TO COMBINATION AREA/MASTER ALARM PANEL IN NURSE STATION 107
CONNECT ALARM SWITCH TO COMBINATION AREA/MASTER ALARM PANEL IN NURSE STATION 107
DECON/SOILED AREA ZONE VALVE DETAIL
2
CONNECT ALARM SWITCH TO COMBINATION AREA/MASTER ALARM PANEL IN NURSE STATION 107
BALL VALVE
BALL VALVE LP VENT
HP VENT
1/2" NITROGEN TO FACILITY BALL VALVE LP VENT
HP VENT
MASM 1-18
OSM 1-18
1/2" NITROUS OXIDE TO FACILITY BALL VALVE LP VENT
HP VENT
HP VENT
NSM 1-18
4
3
CONNECT ALARM SWITCH TO COMBINATION AREA/MASTER ALARM PANEL IN NURSE STATION 107
1/2" MEDICAL AIR TO FACILITY
1/2" OXYGEN TO FACILITY LP VENT
V
ZONE VALVE FOR EACH MED. GAS
5
NOSM 1-18
6
7
TURN DOWN WITH FILTER SCREEN. MAINTAIN MINIMUM 25'-0" CLEARANCE TO OUTSIDE AIR INTAKES
MEDICAL GAS LEGEND
NITROUS OXIDE SUPPLY MANIFOLD SCHEDULE MARK
NUMBER OF CYLINDERS
TYPE
ELECTRICAL
O
OXYGEN
A
MEDICAL AIR
V
VACUUM
4
HIGH PRESSURE
120/1/60
INSTALL PRESSURE SWITCH IN MAIN LINE AND PULL 2 CONDUCTOR, 22 AWG WIRING TO COMBINATION MASTER/AREA ALARM PANEL IN NURSE STATION 107
NITROGEN
MIDL-HHH-N20 N20 EVAC
NOTES:
36"
EXAMPLE: PATTON'S MEDICAL N
NOSM 1-18
DESCRIPTION
NITROUS OXIDE
ROOF 1-1/2"
Project V
SYMBOL
EVACUATION
2"
1. PROVIDE MANIFOLD WITH PRESSURE SWITCH/GAUGE. BALL VALVE
2. PROVIDE MANIFOLD WITH STAGGERED ARRANGEMENT BAR AND STAINLESS STEEL PIGTAILS.
EXHAUST SILENCER PROVIDED BY MFG
MAIN-LINE SHUT-OFF VALVE
PROFFER SURGICAL CENTER ADDITION 1611 WALLACE BLVD, AMARILLO, TEXAS 79106
FLEXIBLE CONNECTION
NITROGEN SUPPLY MANIFOLD SCHEDULE MARK
NUMBER OF CYLINDERS
TYPE
ELECTRICAL
EXAMPLE: PATTON'S MEDICAL
NSM 1-18
4
HIGH PRESSURE
120/1/60
MIDL-HH-NIT
MEDICAL AIR SUPPLY MANIFOLD SCHEDULE MARK MASM 1-18
NUMBER OF CYLINDERS 4
TYPE HIGH PRESSURE
ELECTRICAL 120/1/60
CTB ASSOCIATES
EXAMPLE: PATTON'S MEDICAL
A R C H I T E C T S
MIDL-HH-AIR MV 1-18
NOTES:
1. PROVIDE MANIFOLD WITH PRESSURE SWITCH/GAUGE. 2. PROVIDE MANIFOLD WITH STAGGERED ARRANGEMENT BAR AND STAINLESS STEEL PIGTAILS.
NOTES:
1. PROVIDE MANIFOLD WITH PRESSURE SWITCH/GAUGE. 2. PROVIDE MANIFOLD WITH STAGGERED ARRANGEMENT BAR AND STAINLESS STEEL PIGTAILS.
Revisions
MEDICAL VACUUM PUMP SCHEDULE MARK
HP
TANK SIZE (GALLONS)
CONFIGURATION
CFM @ 19.0" HG
ELECTRICAL
EXAMPLE: PATTON'S MEDICAL
MU 1-18
(2) 5
80
VERTICAL
38.0
208/3/60
74-22-052-PDS
NOTES:
P L A N N E R S
3003 MONTE VISTA BLVD. NE ALBUQUERQUE, NM 87106 P. (505) 268-3033 F. (505) 212-0354
[email protected]
FINISHED FLOOR
OXYGEN SUPPLY MANIFOLD SCHEDULE MARK
NUMBER OF CYLINDERS
TYPE
ELECTRICAL
EXAMPLE: PATTON'S MEDICAL
OSM 1-18
8
HIGH PRESSURE
120/1/60
MIDL-HH-OXY
3. PROVIDE UNIT WITH EXHAUST SILENCER, ISOLATION VALVE, AND VACUUM SWITCH/GAUGE.
1.
NOTES:
1. PROVIDE MANIFOLD WITH PRESSURE SWITCH/GAUGE. 2. PROVIDE MANIFOLD WITH STAGGERED ARRANGEMENT BAR AND STAINLESS STEEL PIGTAILS.
MEDICAL VACUUM PUMP PIPING DETAIL
JANUARY 29, 2018 Sheet No.
2.
3.
1. UNIT SELECTED AT ELEVATION OF 3600 FEET. 2. PROVIDE UNIT WITH FACTORY DISCONNECT SWITCH.
4" CONCRETE HOUSEKEEPING PAD
Date Issued
8
Sheet Name
MEDICAL GAS DETAILS AND SCHEDULES
MG-2
GENERAL NOTES 1.
COORDINATE ALL NEW AND EXISTING PIPING WITH ARCHITECTURAL, STRUCTURAL, MECHANICAL, PLUMBING, AND ELECTRICAL.
2.
CONTRACTOR SHALL FIELD VERIFY EXACT LOCATION, SIZE, AND ELEVATION OF EXISTING SPRINKLER PIPING PRIOR TO COMMENCING WORK.
3.
ALL NEW SPRINKLER HEADS IN FINISHED CEILINGS SHALL BE CONCEALED QUICK RESPONSE TYPE.
4.
AREAS SHOWN SHADED SHALL BE CONNECTED TO THE EXISTING WET SPRINKLER SYSTEM AND DESIGNED FOR LIGHT HAZARD OCCUPANCY IN ACCORDANCE WITH NFPA 13.
5.
AREAS SHOWN HATCHED SHALL BE CONNECTED TO EXISTING DRY SPRINKLER SYSTEM AND DESIGNED FOR LIGHT HAZARD OCCUPANCY IN ACCORDANCE WITH NFPA 13.
6.
CONTRACTOR SHALL COORDINATE ALL ACTIVITIES WITHIN THE EXISTING FACILITY WITH THE OWNER AS THE EXISTING FACILITY IS TO REMAIN IN OPERATION THROUGHOUT CONSTRUCTION.
EX F
EX 1-1/4"
KEYED NOTES 1
EX F
2
1
CONNECT NEW DRY SPRINKLER SYSTEM PIPING TO EXISTING AND EXTEND AS REQUIRED TO SERVE NEW BALCONY AREAS SHOWN HATCHED.
2
EXISTING DRY SPRINKLER SYSTEM MAIN TO REMAIN.
3
ROUTE NEW WET SPRINKLER SYSTEM PIPING MAIN ABOVE CORRIDOR CEILING TO SERVE NEW ADDITION.
4
MODIFY EXISTING SPRINKLER SYSTEM IN ROOM TO BE RENOVATED. INSTALL CONCEALED TYPE HEADS IN NEW GYP BOARD CEILING.
5
EXISTING SPRINKLER SYSTEM RISER TO REMAIN.
6
CONNECT NEW WET SPRINKLER SYSTEM PIPING TO EXISTING AND EXTEND AS SHOWN TO SERVE NEW ADDITION. PROVIDE AND INSTALL CONTROL VALVE AND FLOW SWITCH AT NEW CONNECTION TO EXISTING.
7
EXISTING 2 INCH WET SPRINKLER SYSTEM MAIN TO REMAIN.
EX F
EX 1-1/4"
F EX F
F
F
3
4
7 EX F
EX 2" 6
2 5
EX 2"
EX 1-1/4" EX F
Project
PROFFER SURGICAL CENTER ADDITION 1611 WALLACE BLVD, AMARILLO, TEXAS 79106
CTB ASSOCIATES A R C H I T E C T S
P L A N N E R S
3003 MONTE VISTA BLVD. NE ALBUQUERQUE, NM 87106 P. (505) 268-3033 F. (505) 212-0354
[email protected]
Revisions 1.
Date Issued
JANUARY 29, 2018 Sheet No.
2.
3.
N
FIRE PROTECTION FLOOR PLANSCALE: 1/8" = 1'-0" 0
2'
4'
8'
Sheet Name
FIRE PROTECTION FLOOR PLAN
FP-1
GENERAL NOTES 1.
CONTRACTOR TO VERIFY LOCATIONS OF ALL EXISTING ELECTRICAL EQUIPMENT, DEVICES, ETC. DEVICES/EQUIPMENT SHOWN MAY NOT REPRESENT ALL DEVICES/EQUIPMENT AND THE CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVING/RELOCATING DEVICES/EQUIPMENT NOT SHOWN AS REQUIRED FOR DEMOLITION.
KEYED NOTES
1 1 13
1
1
1
EXISTING POLE MOUNTED LIGHT FIXTURE TO REMAIN.
2
REMOVE EXISTING POLE MOUNTED LIGHT FIXTURE AND RETAIN FOR REINSTALLATION. REFER TO ELECTRICAL SITE PLAN FOR DETAILS.
3
EXISTING UNDERGROUND WIRING AND CONDUIT FOR LIGHTING CIRCUIT TO REMAIN. WIRING AND CONDUIT TO BE RE-USED. REFER TO ELECTRICAL SITE PLAN FOR DETAILS.
4
REMOVE AND DISCARD EXISTING UNDERGROUND WIRING AND CONDUIT FOR LIGHTING CIRCUIT.
5
REMOVE POWER CONNECTION TO IRRIGATION CONTROLLER. IRRIGATION CONTROLLER TO BE RELOCATED AND RECONNECTED TO EXISTING CIRCUIT. REFER TO ELECTRICAL SITE PLAN FOR DETAILS.
6
EXISTING MAIN DISTRIBUTION PANEL MDP TO REMAIN.
7
EXISTING UNDERGROUND SERVICE ENTRANCE TO REMAIN.
8
REMOVE AND DISCARD EXISTING PAD MOUNTED CT ENCLOSURE.
9
EXISTING METER MOUNTED ON THE SIDE OF THE EXISTING CT ENCLOSURE TO BE REMOVED BY THE UTILITY COMPANY.
10
EXISTING UTILITY COMPANY PADMOUNTED TRANSFORMER TO REMAIN.
11
EXISTING UTILITY COMPANY SERVICE LATERAL TO REMAIN.
12
EXISTING UTILITY COMPANY PRIMARY CONDUIT AND CABLES TO REMAIN.
13
EXISTING UTILITY COMPANY FEED-THRU CABINET TO REMAIN.
1
4
2 5
J
2
4
4
2 4
3
3
4
6
2
8
7
11
10 12 Project
9
PROFFER SURGICAL CENTER ADDITION 1611 WALLACE BLVD, AMARILLO, TEXAS 79106
CTB ASSOCIATES A R C H I T E C T S
P L A N N E R S
3003 MONTE VISTA BLVD. NE ALBUQUERQUE, NM 87106 P. (505) 268-3033 F. (505) 212-0354
[email protected]
Revisions 1.
Date Issued
JANUARY 29, 2018 Sheet No.
2.
3.
N
SCALE: 1/16" = 1'-0" ELECTRICAL DEMOLITION SITE PLAN 0
4'
8'
16'
Sheet Name
ELECTRICAL DEMOLITION SITE PLAN
E-1
GENERAL NOTES 1.
REFER TO POLE BASE DETAIL FOR RELOCATED POLE LIGHT FIXTURE FOR MOUNTING DETAILS AND REQUIREMENTS UNLESS NOTED OTHERWISE.
KEYED NOTES 1
EXISTING POLE MOUNTED LIGHT FIXTURE.
2
REINSTALL EXISTING POLE MOUNTED LIGHT FIXTURE IN LOCATION SHOWN. CLEAN, RELAMP, AND REPLACE BALLAST AS NECESSARY PRIOR TO REINSTALLATION. CONTRACTOR TO VERIFY LAMP AND BALLAST REQUIRED.
3
EXISTING UNDERGROUND WIRING AND CONDUIT FOR LIGHTING CIRCUIT. REVISE WIRING AND CONDUIT AS NECESSARY TO STUB-UP INTO NEW IN-GRADE JUNCTION BOX. REFER TO K.N. 4 FOR DETAILS.
4
EXTERIOR IN-GRADE JUNCTION BOX. INSTALL A QUAZITE (OR EQUAL) PC 11"X18" INGRADE JUNCTION BOX, 18" DEEP, GASKETED BOX WITH AN OPEN BOTTOM. PROVIDE A GASKETED STANDARD COVER FOR ANSI TIER 8 LOADING WITH TWO BOLT CONNECTION TO BOX AND ELECTRIC LOGO ON COVER. INSTALL A MINIMUM OF 6" GRAVEL BELOW BOX AND 6" UP SIDES AROUND BOX.
5
2-10, 1-10G, 3/4"C. 24 INCHES BELOW GRADE. STUB-UP INTO NEW IN-GRADE JUNCTION BOX AND CONNECT TO EXISTING LIGHTING CIRCUIT AS NECESSARY. REFER TO K.N. 3.
6
2-10, 1-10G, 3/4"C. 24 INCHES BELOW GRADE.
7
RECONNECT TO EXISTING IRRIGATION CONTROLLER. EXTEND EXISTING WIRING AND CONDUIT AS NECESSARY.
8
EXISTING MAIN DISTRIBUTION PANEL MDP.
9
EXISTING UNDERGROUND SERVICE ENTRANCE. CONNECT TO NEW CT ENCLOSURE.
10
1600A 208Y/120V 3Ø 4W NEMA 3R CT ENCLOSURE AND INSTRUMENT METER MOUNTED ON PAD. REFER TO POWER RISER DIAGRAM FOR DETAILS.
11
EXISTING UTILITY COMPANY PADMOUNTED TRANSFORMER.
12
EXISTING UTILITY COMPANY SERVICE LATERAL. UTILITY COMPANY TO CONNECT TO NEW CT ENCLOSURE.
13
EXISTING UTILITY COMPANY PRIMARY CONDUIT AND CABLES.
14
EXISTING UTILITY COMPANY FEED-THRU CABINET.
15
UNDERGROUND SERVICE ENTRANCE. REFER TO POWER RISER DIAGRAM FOR DETAILS.
16
SAWCUT AND PATCH EXISTING CONCRETE PAD AS NECESSARY TO INSTALL NEW SERVICE ENTRANCE CONDUIT AND CABLES.
17
NEW MAIN DISTRIBUTION PANEL MP.
1 1 14
1
1
1
6
7
J
2
2
6 6
2 4
4
3
3
5
5
8
2
10
9
12
11 13 Project
16 17
PROFFER SURGICAL CENTER ADDITION 1611 WALLACE BLVD, AMARILLO, TEXAS 79106
15
CTB ASSOCIATES A R C H I T E C T S
P L A N N E R S
3003 MONTE VISTA BLVD. NE ALBUQUERQUE, NM 87106 P. (505) 268-3033 F. (505) 212-0354
[email protected]
Revisions 1.
Date Issued
JANUARY 29, 2018 Sheet No.
2.
3.
N
SCALE: 1/16" = 1'-0" ELECTRICAL SITE PLAN 0
4'
8'
16'
Sheet Name
ELECTRICAL SITE PLAN
E-2
GENERAL NOTES 1.
CONTRACTOR TO VERIFY LOCATIONS OF ALL EXISTING ELECTRICAL EQUIPMENT, DEVICES, ETC. DEVICES/EQUIPMENT SHOWN MAY NOT REPRESENT ALL DEVICES/EQUIPMENT AND THE CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVING/RELOCATING DEVICES/EQUIPMENT NOT SHOWN AS REQUIRED FOR DEMOLITION.
2.
ALL LIGHT FIXTURES, SWITCHES, OCCUPANCY SENSORS, ETC. SHALL BE EXISTING TO REMAIN AND ARE SHOWN FOR REFERENCE ONLY UNLESS NOTED OTHERWISE.
D
PI
PI
D
D D
PI
1
REMOVE AND DISCARD EXISTING LIGHT FIXTURE AND ALL ASSOCIATED WIRING AND CONDUIT.
2
REMOVE AND DISCARD EXISTING SWITCH AND ALL ASSOCIATED WIRING AND CONDUIT.
D D
KEYED NOTES
3
REMOVE AND DISCARD EXISTING OCCUPANCY SENSOR AND ALL ASSOCIATED WIRING AND CONDUIT.
PI
4
REMOVE EXISTING LIGHT FIXTURE AND RETAIN FOR REINSTALLATION. REFER TO LIGHTING FLOOR PLAN FOR DETAILS.
PI/D
L20
L06
D
PI
L03
DT
PI
PI
D
PI
2 1
D D
L01 L02 L22
L25 L30
D D D
PI
PI
PI
L04
PI/D
D2
L28
D D D D D D D
L29 PI
D
X
PI/D
PI
L07 PI/D
PI
L26
PI
L14
L21
PI/D
J
L24
D D
L23
PI
J L18
L19
L16
J
PI/D
PI/ D
J
J
PI/ D
PI/ D
J
J
PI/ D
J PI D D
PI
PI/ D
J
PI
PI/D
PI
PI
J
PI/D
L15
L17
J PI/D L27
L05
J PI
L08
2 1 1
L10
1
L13
L09 L11 PI
PI
4
PI PI
2
PI
1 3
1 PI
PI
1
PI
PI
L12 PI
PI
Project
PROFFER SURGICAL CENTER ADDITION 1611 WALLACE BLVD, AMARILLO, TEXAS 79106
1
CTB ASSOCIATES A R C H I T E C T S
P L A N N E R S
3003 MONTE VISTA BLVD. NE ALBUQUERQUE, NM 87106 P. (505) 268-3033 F. (505) 212-0354
[email protected]
Revisions 1.
Date Issued
JANUARY 29, 2018 Sheet No.
2.
3.
N
LIGHTING DEMOLITION PLAN
SCALE: 1/8" = 1'-0" 0
2'
4'
8'
Sheet Name
LIGHTING DEMOLITION PLAN
E-3
GENERAL NOTES
GFI
GFI
1.
CONTRACTOR TO VERIFY LOCATIONS OF ALL EXISTING ELECTRICAL EQUIPMENT, DEVICES, ETC. DEVICES/EQUIPMENT SHOWN MAY NOT REPRESENT ALL DEVICES/EQUIPMENT AND THE CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVING/RELOCATING DEVICES/EQUIPMENT NOT SHOWN AS REQUIRED FOR DEMOLITION.
2.
ALL RECEPTACLES, FLOOR BOXES, ETC. SHALL BE EXISTING TO REMAIN AND ARE SHOWN FOR REFERENCE ONLY UNLESS NOTED OTHERWISE.
GFI GFI
WP GFI
GFI
KEYED NOTES WP GFI
1
REMOVE AND DISCARD EXISTING RECEPTACLE AND ALL ASSOCIATED WIRING AND CONDUIT.
2
EXISTING PANEL MDP TO REMAIN.
3
EXISTING PANEL A TO REMAIN.
4
EXISTING PANEL B TO REMAIN.
5
EXISTING PANEL C TO REMAIN.
6
EXISTING PANEL D TO REMAIN.
7
EXISTING LIGHTING CONTROL PANEL LCP TO REMAIN.
8
EXISTING PANEL E TO REMAIN.
GFI
GFI GFI GFI 2
2
2
2 GFI
2
GFI
GFI
1
GFI GFI
GFI GFI
2
GFI 2 GFI 2
2
GFI
2
2
1
2
2
2
GFI
GFI
2
2 GFI 2 GFI
GFI
GFI
GFI
GFI GFI
2 GFI
GFI
2
2
2
2
2
2
GFI
2 GFI GFI 2
GFI GFI
GFI
GFI
2 2
2
GFI
GFI
GFI
GFI
GFI
GFI
2
GFI
GFI
GFI
GFI
GFI
2
GFI GFI
GFI
+42
GFI
GFI +36
GFI
+36
GFI
GFI
2
2
GFI
GFI
2
GFI
+18
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
WP GFI
GFI
8 1
GFI
GFI
7
2
+48 GFI
2
1
6
GFI
GFI
GFI
GFI
GFI
2
1 1
5
4
GFI
GFI
3
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI GFI
GFI
GFI
2 GFI
GFI
GFI
+48
2
2
Project
WP GFI
PROFFER SURGICAL CENTER ADDITION 1611 WALLACE BLVD, AMARILLO, TEXAS 79106
CTB ASSOCIATES A R C H I T E C T S
P L A N N E R S
3003 MONTE VISTA BLVD. NE ALBUQUERQUE, NM 87106 P. (505) 268-3033 F. (505) 212-0354
[email protected]
Revisions 1.
Date Issued
JANUARY 29, 2018 Sheet No.
2.
3.
N
POWER DEMOLITION PLAN
SCALE: 1/8" = 1'-0" 0
2'
4'
8'
Sheet Name
POWER DEMOLITION PLAN
E-4
GENERAL NOTES
WP GFI
WP GFI
1.
CONTRACTOR TO VERIFY LOCATIONS OF ALL EXISTING ELECTRICAL EQUIPMENT, DEVICES, ETC. DEVICES/EQUIPMENT SHOWN MAY NOT REPRESENT ALL DEVICES/EQUIPMENT AND THE CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVING/RELOCATING DEVICES/EQUIPMENT NOT SHOWN AS REQUIRED FOR DEMOLITION.
2.
ALL RECEPTACLES, EQUIPMENT POWER CONNECTIONS, ETC. SHALL BE EXISTING TO REMAIN AND ARE SHOWN FOR REFERENCE ONLY UNLESS NOTED OTHERWISE.
WP GFI
KEYED NOTES
T
1
REMOVE AND DISCARD EXISTING POWER CONNECTION TO EXHAUST FAN AND ALL ASSOCIATED WIRING AND CONDUIT.
2
REMOVE AND DISCARD EXHAUST FAN SWITCH AND ALL ASSOCIATED WIRING AND CONDUIT.
3
REMOVE AND DISCARD EXISTING THERMOSTAT JUNCTION BOX AND ALL ASSOCIATED CONDUIT. THERMOSTAT AND CONTROL WIRING TO BE REMOVED BY DIVISION 15.
4
REMOVE AND DISCARD EXISTING CHRISTMAS LIGHT RECEPTACLE AND ALL ASSOCIATED WIRING AND CONDUIT.
WP GFI
T
4
GFI
EX RTU-3
EX EF-9 J
J
EX EF-8
EX RTU-8
T
J
EX RTU-6
J
EX EF-7
J
J
WP GFI
T
T
EX RTU-1 T WP GFI
J J
EX FC-1
4
EX CU-1
J
T
J
J
J
EX RTU-9
EX RTU-7
EX RTU-4
J
EX RTU-2
J
EX EF-1 J
EX RTU-5
EX EF-6 J J
EX EF-2
2
J
4 1
T WP GFI
T
3
T
WP GFI
J
EX EF-4
EX EF-3
J J
EX EF-5
T
2
WP GFI
WP GFI 2
J
J
J Project
PROFFER SURGICAL CENTER ADDITION 1611 WALLACE BLVD, AMARILLO, TEXAS 79106
CTB ASSOCIATES A R C H I T E C T S
P L A N N E R S
3003 MONTE VISTA BLVD. NE ALBUQUERQUE, NM 87106 P. (505) 268-3033 F. (505) 212-0354
[email protected]
Revisions 1.
Date Issued
JANUARY 29, 2018 Sheet No.
2.
3.
N
SCALE: 1/8" = 1'-0" EQUIPMENT POWER DEMOLITION PLAN 0
2'
4'
8'
Sheet Name
EQUIPMENT POWER DEMOLITION PLAN
E-5
GENERAL NOTES
SP
CONTRACTOR TO VERIFY LOCATIONS OF ALL EXISTING ELECTRICAL EQUIPMENT, DEVICES, ETC. DEVICES/EQUIPMENT SHOWN MAY NOT REPRESENT ALL DEVICES/EQUIPMENT AND THE CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVING/RELOCATING DEVICES/EQUIPMENT NOT SHOWN AS REQUIRED FOR DEMOLITION.
2.
ALL DATA/TELEPHONE OUTLETS, JUNCTION BOXES, PA SYSTEM DEVICES, FIRE ALARM DEVICES, ETC. SHALL BE EXISTING TO REMAIN AND ARE SHOWN FOR REFERENCE ONLY UNLESS NOTED OTHERWISE.
SP
KEYED NOTES V
SP V
SP
1.
TV
REMOVE AND DISCARD EXISTING DATA AND/OR TELEPHONE OUTLET AND ALL ASSOCIATED WIRING AND CONDUIT.
2
REMOVE AND DISCARD EXISTING TV OUTLET AND ALL ASSOCIATED WIRING AND CONDUIT.
3
REMOVE AND DISCARD EXISTING JUNCTION BOX AND ALL ASSOCIATED WIRING AND CONDUIT.
V
SP
1
V
TV
SP
J
J
1
J
J TV
J
SP
1
J
V
V
P
H V
SP
V
SP
J
V
V
S SP
SP J
J
J
J
SP SP
SP
SP
J
V
V
V
V
V
V
V
V
SP
J
J
SP
SP
SP
V
SP
V
SP
V
SP
V
V
SP
SP J
J
J
J
TV
2 TV TV
V
1 1
TV
3 SP
SP
J
J
4
J
2
Project
J DB
PROFFER SURGICAL CENTER ADDITION 1611 WALLACE BLVD, AMARILLO, TEXAS 79106
CTB ASSOCIATES A R C H I T E C T S
P L A N N E R S
3003 MONTE VISTA BLVD. NE ALBUQUERQUE, NM 87106 P. (505) 268-3033 F. (505) 212-0354
[email protected]
Revisions 1.
Date Issued
JANUARY 29, 2018 Sheet No.
2.
3.
N
SPECIAL SYSTEMS DEMOLITION PLANSCALE: 1/8" = 1'-0" 0
2'
4'
8'
Sheet Name
SPECIAL SYSTEMS DEMOLITION PLAN
E-6
GENERAL NOTES
K
D
G-2 (ON)
GL
3.
REFER TO SHEET E-18 FOR EXTERIOR MOUNTED LED STRIP LIGHT.
D PI
1
CONNECT EMERGENCY BALLAST/DRIVER OF THE FIXTURE TO THE UNSWITCHED HOT CONDUCTOR OF THE CIRCUIT. FIXTURE SHALL BE SWITCHED AND EMERGENCY BALLAST/DRIVER SHALL ONLY BE ACTIVE IF CIRCUIT IS DE-ENERGIZED.
2
CHAIN HUNG FIXTURE MOUNTED 9'-0" AFF.
PI
3
SURFACE MOUNT FIXTURE TO BOTTOM OF CEILING.
4
MOUNT FIXTURE ON WALL 9'-0" AFF.
5
INSTALL A NEW 120VAC PASSIVE INFRARED VACANCY SENSOR AND CONNECT TO EXISTING LIGHT FIXTURES AS SHOWN. REVISE EXISTING WIRING AND CONDUIT AS NECESSARY.
6
CONNECT TO EXISTING 120VAC NORMAL POWER LIGHTING CIRCUIT IN AREA BELIEVED TO BE CIRCUIT AS INDICATED. CONTRACTOR TO VERIFY. REVISE EXISTING WIRING AND CONDUIT AS NECESSARY. REVISE EXISTING PANEL DIRECTORY CARD AS NECESSARY.
7
REINSTALL EXISTING LIGHT FIXTURE REMOVED DURING DEMOLITION AND CONNECT TO NEW FIXTURES AS SHOWN. CLEAN AND RELAMP FIXTURE AS NECESSARY.
8
CONNECT FIXTURE SO THAT OUTSIDE LED ARRAY(S) ARE ON NORMAL POWER CIRCUIT AND INSIDE LED ARRAY(S) ARE ON EMERGENCY CIRCUIT. CONNECT EMERGENCY DRIVER TO THE UNSWITCHED HOT CONDUCTOR OF THE CIRCUIT. FIXTURE SHALL BE SWITCHED AND EMERGENCY DRIVER SHALL ONLY BE ACTIVE IF CIRCUIT IS DE-ENERGIZED. NORMAL AND EMERGENCY POWER FEEDS TO FIXTURE SHALL BE RUN IN SEPARATE CONDUITS. ORIENT FIXTURES SO THAT THE ASYMMETRICAL PORTION OF THE LENS IS FACING THE CENTER OF THE ROOM.
9
HOMERUN THROUGH LIGHTING CONTROL PANEL LCP2.
10
INSTALL A DOUGLAS 1-BUTTON SWITCH STATION (DOUGLAS WNS-2301, WHITE IN COLOR) TO CONTROL RESTRICTED CORRIDOR 120 LIGHTS.
11
INSTALL A DOUGLAS 1-BUTTON SWITCH STATION (DOUGLAS WNS-2301, WHITE IN COLOR) TO CONTROL HALL 106/113 LIGHTS.
12
INSTALL A DOUGLAS 1-BUTTON SWITCH STATION (DOUGLAS WNS-2301, WHITE IN COLOR) TO CONTROL NURSE STATION 107 LIGHTS.
13
INSTALL A DOUGLAS 3-BUTTON SWITCH STATION (DOUGLAS WNS-2303, WHITE IN COLOR) TO CONTROL WAITING 101, RECEPTION 102, AND INTERVIEW 103 LIGHTS.
14
INSTALL OWNER PROVIDED LIGHT FIXTURE AND CONNECT TO CIRCUIT AS SHOWN. VERIFY DETAILS AND REQUIREMENTS WITH LIGHT FIXTURE PROVIDED.
15
MOUNT FIXTURE ON WALL 10'-0" AFF.
14
GM
GM
D
GM
D
GL D
GL
G-2 (ON)
G-2 (ON)
13
1
L09
DT
G-2 (ON)
9
PI
11
CD
XY
PI
PI
D
PI
CD
L06
XY
PI
PI
GM
D
GME
13
L10
D
GL
PI/D
9 G-2 (ON)
K
PI
13
1
PI
GM
D
D
PI
GL
ALL LIGHT FIXTURES, SWITCHES, OCCUPANCY SENSORS, ETC. SHALL BE EXISTING TO REMAIN AND ARE SHOWN FOR REFERENCE ONLY UNLESS NOTED OTHERWISE.
KEYED NOTES
D D
GME
BH
LS-11 (ON)
PI
L11
XY
F
9
2.
GL
3
K
D
LS-11 (ON)
BH
REFER TO POWER FLOOR PLAN FOR PANEL LOCATIONS.
PI
K
K
9
D D
GL
1.
A D D D D D
BH
D
11
CD
PI
PI/D
PI
D D D D D D D
D
G-2 (ON)
PI
BH L05
Y
CD
BH
BH
PI/D
D
PI
L26
PI
J PI D D
J
12
Y
PI
BH
GM
CD
PI/D
PI/D
12 BH
X
L08
GM
CD
D
PI
9 BH
CR-18 D
CD
BH
L07
J
D
PI/D
GL
PI
PI/ D
J
J
PI/ D
PI/ D
J
J
PI/ D
J PI D D
CD
PI/ D
J
GL BH
CD
CD
GL
CD
PI
PI/D
CD BH
GL
G-2 (ON)
GL
PI
GME
CD GL
11 9
G-2 (ON)
1
D
A
L04
11 8 D E E E E
J O V V
J
N A 2 no wv
J
XY
8
D E E E E
N A O 2 no V wv V
PI
A
1
G-2 (ON)
BH
XY
L03
PI 3
PI 3
XY
J
PI
GH
BL
L02
BL
BL
BL
1 10
8
E
PI 3
GL
PI 3
G-6
PI 3
PI 3
8
GH
GL
GL
GL
G-4 (ON)
BH
A
A
7
PI
GH
PI
PI
1 PI
PI 4
PI
PI
BH PI
PI
D-15
GME
PI
A
J
PI
5
GME
J
GH
6
PI
BL
BL
CR-10
J
GH
PI
A
J
J PI/D
J
CR-14
PI
GME
PI
J
PI/D
GL
PI
PI
Project
BH
A
GL H
PI
8
J
8
J
E
H
1611 WALLACE BLVD, AMARILLO, TEXAS 79106
4
3
F G-8 PI
E
J CR-12
J
9
G-4 (ON)
Z
H
A H
PI
2
H
CTB ASSOCIATES
E CR-16
A R C H I T E C T S
(ON)
J E E E E D
V V O
A
J wv
wv
no 2
no 2
A
A
J
8
J
V V O
L01
8
XY
CR-16 (ON)
LE
PI
F 10
2
E
CR-16 (ON)
E
PI
LS-11 (ON)
E
LS-2
PI
Z LS-8 (ON)
Date Issued
JANUARY 29, 2018 Sheet No.
2.
K
GL
3.
9
LS-8 (ON)
Revisions
LS-4 1.
2
4
15
3
G-4 GL (ON)
4
Z
E
P L A N N E R S
3003 MONTE VISTA BLVD. NE ALBUQUERQUE, NM 87106 P. (505) 268-3033 F. (505) 212-0354
[email protected]
PI E E E E D
PROFFER SURGICAL CENTER ADDITION
N
LIGHTING FLOOR PLAN
SCALE: 1/8" = 1'-0" 0
2'
4'
8'
Sheet Name
LIGHTING FLOOR PLAN
E-7
GENERAL NOTES 1.
ALL RECEPTACLES AND WIRING IN PATIENT CARE AREAS SHALL BE HOSPITAL GRADE IN ACCORDANCE WITH NEC ARTICLE 517.
2.
REFER TO ARCHITECTURAL ELEVATIONS FOR EXACT RECEPTACLE LOCATIONS IN PATIENT BAYS IN PRE-OP, POST-OP AND TREATMENT AREAS.
3.
ALL RECEPTACLES IN O.R. 1 AND O.R. 2 SHALL MOUNTED 40" AFF UNLESS NOTED OTHERWISE. ALL RECEPTACLES, FLOOR BOXES, ETC. SHALL BE EXISTING TO REMAIN AND ARE SHOWN FOR REFERENCE ONLY UNLESS NOTED OTHERWISE.
4. GFI
S
F-38
GFI GFI
WP GFI
40
J
GFI
1
S
J
WP GFI
38
1
EXISTING PANEL MDP.
2
EXISTING PANEL A.
3
EXISTING PANEL B.
4
EXISTING PANEL C.
5
EXISTING PANEL D.
6
EXISTING LIGHTING CONTROL PANEL LCP.
7
EXISTING PANEL E.
8
NEW PANEL MP.
9
NEW PANEL F.
10
NEW PANEL G.
11
NEW PANEL H.
12
NEW 400A AUTOMATIC TRANSFER SWITCH. SEE POWER RISER DIAGRAM FOR DETAILS.
13
NEW PANEL EMDP.
14
NEW CRITICAL BRANCH PANEL CR.
15
NEW LIFE SAFETY BRANCH PANEL LS.
16
NEW EQUIPMENT BRANCH PANEL EQ.
17
NEW ISOLATION PANEL IP1 (FLUSH MOUNTED). ISOLATION PANEL SHALL BE A 208V-120V 1 PHASE 7.5KVA OPERATING ROOM ISOLATION PANEL EQUAL TO SQUARE D CLASS 4800, #SXM07BA/SIP07BAB/ST4526/SB432408, COMPLETE WITH 16-20/2 SECONDARY CIRCUIT BREAKERS AND INTEGRAL LINE ISOLATION MONITOR. NOTE THAT ALL OPERATING ROOM BRANCH CIRCUIT HOMERUNS TO PANEL SECONDARY CIRCUIT BREAKERS MUST BE 2#12 AWG TYPE XHHW-2 (ORANGE/BROWN COLOR) WITH 1-10 INSULATED GREEN GROUND IN 1/2" EMT CONDUIT. REF. NEC 517.160.
GFI
J
20
F-40
GFI
2
G-11
39
37
GFI
GFI
GFI GFI
F-3
2 BC
AC
AC
2
2
F-5
AC
35
2 BC
21
F-1
WP GFI
AC
AC
35
2
F-9
G-18
AC
J
AC
F-7
2 BC
J
2 GFI
2
GFI
AC
GFI
AC GFI GFI
32 E
20
2
F-13
E
G-9
GFI
2
2
F-15 (ON)
CR-5
GFI
AC AC GFI
D-30
2
21
D-32 D-34
2
GFI
AC GFI AC GFI
E
AC
GFI
2
2 2
2
32 AC GFI
GFI
21 E
18
GFI
2 2
23
GFI 2
E
E
CR-25
AC E/BC BC
AC
E/BC
E
BC
AC E AC
CR-3
E
2
RECEPTACLE FOR TV. VERIFY EXACT MOUNTING LOCATION WITH ARCHITECT.
22
RECEPTACLE LOCATED 6" ABOVE TOP OF COUNTERSPLASH. LOCATE TO AVOID DISPENSERS. REFER TO ARCHITECTURAL FOR DETAILS.
23
DEDICATED RECEPTACLE FOR CRASH CART. HOMERUN 2-12, 1-12G, 1/2"C.
24
DEDICATED RECEPTACLE FOR COUNTERTOP REFRIGERATOR. HOMERUN 2-12, 1-12G, 1/2"C. REFER TO ARCHITECTURAL FOR DETAILS.
25
DEDICATED RECEPTACLE FOR BLANKET WARMER. HOMERUN 2-12, 1-12G, 1/2"C.
26
DEDICATED RECEPTACLE FOR ICE MACHINE LOCATED 48 IN. AFF. HOMERUN 2-12, 1-12G, 1/2"C.
27
INSTALL A POWER/GROUND MODULE EQUAL TO SQUARE D 120 SERIES, #SGPMF4DR4, COMPLETE WITH 4 30A GROUNDING JACKS AND 4 RED 20A DUPLEX RECEPTACLES. INSTALL 4-12, 1-10G, 3/4"C. TO ISOLATION PANEL. CONNECT TWO RECEPTACLES PER HOMERUN. CONNECT GROUND WIRE TO MAIN GROUND CONNECTION IN MODULE.
28
CONNECT TO SURGICAL LIGHT CONTROL CENTER. HOMERUN 2-12, 1-10G, 3/4"C. INSTALL 3-12, 1-10G, 3/4"C. TO HUB FOR LIGHTHEAD POWER CABLES. COORDINATE DETAILS WITH EQUIPMENT PROVIDED.
29
CORD MOUNTED CONNECTOR BODY SUSPENDED FROM CEILING (TYP. OF 4). REFER TO OPERATING ROOM SUSPENDED CONNECTOR BODY MOUNTING DETAIL. REFER TO ARCHITECTURAL FOR EXACT LOCATION.
30
CONNECT TO SURGICAL SCRUB SINK INFRARED CONTROL. HOMERUN 2-12, 1-12G, 1/2"C. COORDINATE DETAILS AND REQUIREMENTS WITH EQUIPMENT PROVIDED.
31
DEDICATED RECEPTACLE FOR MICROWAVE LOCATED IN UPPER CABINET. REFER TO ARCHITECTURAL FOR EXACT LOCATION. HOMERUN 2-12, 12G, 1/2"C.
32
DEDICATED RECEPTACLE FOR COUNTERTOP STERILIZER. HOMERUN 2-12, 1-12G, 1/2"C. REFER TO ARCHITECTURAL FOR DETAILS.
33
DEDICATED RECEPTACLE FOR COUNTERTOP ULTRASONIC WASHER. HOMERUN 2-12, 1-12G, 1/2"C. REFER TO ARCHITECTURAL FOR DETAILS.
34
CONNECT TO EXISTING 120VAC NORMAL POWER RECEPTACLE CIRCUIT IN AREA BELIEVED TO BE CIRCUIT AS INDICATED. CONTRACTOR TO VERIFY. REVISE EXISTING WIRING AND CONDUIT AS NECESSARY. REVISE EXISTING PANEL DIRECTORY CARD AS NECESSARY.
35
CONNECT TO POWERED DOOR OPENER. COORDINATE EXACT DETAILS WITH EQUIPMENT PROVIDED.
NEW ISOLATION PANEL IP2 (FLUSH MOUNTED). ISOLATION PANEL SHALL BE A 208V-120V 1 PHASE 7.5KVA OPERATING ROOM ISOLATION PANEL EQUAL TO SQUARE D CLASS 4800, #SXM07BA/SIP07BAB/ST4526/SB432408, COMPLETE WITH 16-20/2 SECONDARY CIRCUIT BREAKERS AND INTEGRAL LINE ISOLATION MONITOR. NOTE THAT ALL OPERATING ROOM BRANCH CIRCUIT HOMERUNS TO PANEL SECONDARY CIRCUIT BREAKERS MUST BE 2#12 AWG TYPE XHHW-2 (ORANGE/BROWN COLOR) WITH 1-10 INSULATED GREEN GROUND IN 1/2" EMT CONDUIT. REF. NEC 517.160.
36
CONNECT TO SNOW MELT SYSTEM CONTROLLER. HOMERUN 3-3, 1-8G, 1-1/4"C. COORDINATE EXACT DETAILS AND REQUIREMENTS WITH EQUIPMENT PROVIDED.
37
CONNECT TO ELECTRIC SNOW MELT CIRCUIT #1. HOMERUN 2-10, 1-10G, 3/4"C. 24" BELOW SLAB TO SNOW MELT SYSTEM CONTROLLER. COORDINATE EXACT DETAILS AND REQUIREMENTS WITH EQUIPMENT PROVIDED.
38
CONNECT TO ELECTRIC SNOW MELT CIRCUIT #2. HOMERUN 2-10, 1-10G, 3/4"C. 24" BELOW SLAB TO SNOW MELT SYSTEM CONTROLLER. COORDINATE EXACT DETAILS AND REQUIREMENTS WITH EQUIPMENT PROVIDED.
39
PROVIDE AND INSTALL 3-18 AWG SHIELDED JACKETED CABLE FROM SIDEWALK MOUNTED SENSOR TO SNOW MELT SYSTEM CONTROLLER. COORDINATE EXACT DETAILS AND REQUIREMENTS WITH EQUIPMENT PROVIDED. INSTALL IN A 3/4"C. 24 INCHES BELOW SLAB TO SNOW MELT SYSTEM CONTROLLER.
40
PROVIDE AND INSTALL 3-18 AWG SHIELDED JACKETED CABLE FROM ROOF MOUNTED SENSOR TO SNOW MELT SYSTEM CONTROLLER. COORDINATE EXACT DETAILS AND REQUIREMENTS WITH EQUIPMENT PROVIDED. INSTALL IN A 3/4"C. TO SNOW MELT SYSTEM CONTROLLER.
41
NEW LIGHTING CONTROL PANEL LCP2. CONNECT TO EXISTING LIGHTING CONTROL PANEL LCP-1. REFER TO SHEET E-13 FOR DETAILS. HOMERUN 2-12, 1-12G, 1/2"C. TO LS-12 FOR POWER.
2
2
GFI
GFI
2 2
25 GFI
F-23
GFI
2
GFI
GFI
GFI
2
GFI
GFI
GFI
E GFI
E
2
2
GFI
GFI
F-17
21
GFI
F-21
G-5
RECEPTACLE LOCATED 6" ABOVE LIP OF SINK. LOCATE TO AVOID DISPENSERS. REFER TO ARCHITECTURAL FOR DETAILS.
2
AC
CR-23
GFI
GFI
2
2
24
AC
20
2
F-19 CR-1
GFI
AC
GFI
GFI
GFI GFI
G-7
E
GFI
A-19
GFI
NEW EMERGENCY GENERATOR. SEE POWER RISER DIAGRAM FOR DETAILS.
D-28
CR-15
E
19
KEYED NOTES
2
J
35
GFI
KEYED NOTES
24
GFI
AC E
E
E
+42
GFI
GFI
E
G-17
GFI GFI
+36
GFI
+36
E GFI
AC
GFI
+18
GFI
GFI
GFI
GFI
GFI
GFI
2
G-3
2
21
2
G-19
CR-21
GFI
F-15 (ON)
21
2
F-25 CR-7
26 E
E
CR-19
20
F-11
GFI
GFI GFI
GFI
GFI
G-1
GFI
GFI
F-34 GFI
GFI
GFI
GFI
GFI
GFI
GFI
WP GFI
GFI
F-27
27
20
GFI
GFI
7
E
E
GFI
17 E E E
E E
F-30
23
GFI
CR-17
IP1-8 IP1-9 G-23
IP1-4 F-28
E
F-29
22 GFI
22
GFI
F-31
21
GFI AC
CR-11
30 F-2 J
E AC
AC GFI
AC GFI
E AC
CR-9
E AC GFI
F-4
F-20 F-18
+40
E AC
F-37
2
GFI
GFI
GFI
GFI
GFI
2
GFI
31
F-39
GFI
GFI
GFI
GFI
+48
2
2
Project
30 F-22
GFI
GFI
F-33
F-24
E
2
1
J
+40
+40
4
3
GFI
GFI
F-35 +40
GFI
GFI
+40
F-41
E AC
GFI
GFI
F-26 GFI AC
GFI
A-4
+40
GFI E
34
28
E AC
5 2
IP1-5
GFI
2
+48
+40
IP1-2 IP1-1
GFI
6 E
E
29
IP1-6 IP1-7 G-21
GFI
F-32
IP1-3
GFI
GFI
IP1-10,11
29
E AC GFI
32
AC GFI
AC GFI
WP GFI
AC GFI GFI
PROFFER SURGICAL CENTER ADDITION 1611 WALLACE BLVD, AMARILLO, TEXAS 79106
GFI
GFI GFI
F-10
IP2-5
GFI
GFI
F-12 IP2-4
E
28 F-6 IP2-1 IP2-2
E E
29 IP2-3
GFI
E E
F-16 18
GFI
GFI
E
CTB ASSOCIATES A R C H I T E C T S
E
E
29
G-15
F-36
WP GFI
E
GFI
E WP GFI
LS-10 Revisions
F-8
16 15
1.
2.
3.
8 MP-22,24
11
10
CR-13 9 2E
N
POWER FLOOR PLAN
SCALE: 1/8" = 1'-0"
36 0
G-13
JANUARY 29, 2018 Sheet No.
27
12
J
Date Issued
19
13
14
41
P L A N N E R S
3003 MONTE VISTA BLVD. NE ALBUQUERQUE, NM 87106 P. (505) 268-3033 F. (505) 212-0354
[email protected]
GFI
IP2-10,11
GFI
GFI
IP2-8 IP2-9 G-27
IP2-6 IP2-7 G-25
F-14
GFI
33
AC GFI
2'
4'
8'
Sheet Name
POWER FLOOR PLAN
E-8
GENERAL NOTES 1.
REFER TO POWER FLOOR PLAN FOR PANEL LOCATIONS.
2.
ALL RECEPTACLES, EQUIPMENT POWER CONNECTIONS, ETC. SHALL BE EXISTING TO REMAIN AND ARE SHOWN FOR REFERENCE ONLY UNLESS NOTED OTHERWISE.
KEYED NOTES
WP GFI
20
WP GFI
21
WP GFI
1
CONNECT TO ROOF TOP UNIT. REFER TO MECHANICAL EQUIPMENT CONNECTION CHART FOR DETAILS.
2
CONNECT TO CIRCUIT #2 OF ROOF TOP UNIT (FAN/HEAT/CONTROLS). REFER TO MECHANICAL EQUIPMENT CONNECTION CHART FOR DETAILS.
3
CONNECT TO CIRCUIT #1 OF ROOF TOP UNIT (COOLING). REFER TO MECHANICAL EQUIPMENT CONNECTION CHART FOR DETAILS.
4
CONNECT TO FAN COIL UNIT. REFER TO MECHANICAL EQUIPMENT CONNECTION CHART FOR DETAILS.
5
CONNECT TO CONDENSING UNIT. REFER TO MECHANICAL EQUIPMENT CONNECTION CHART FOR DETAILS.
6
2-10, 1-10G, 3/4"C. TO FC 1-18.
7
2-10, 1-10G, 3/4"C. TO CU 1-18.
8
CONNECT TO HUMIDIFICATION UNIT. REFER TO MECHANICAL EQUIPMENT CONNECTION CHART FOR DETAILS.
9
CONNECT TO EXHAUST FAN. REFER TO MECHANICAL EQUIPMENT CONNECTION CHART FOR DETAILS.
10
HOMERUN THROUGH LIGHTING CONTROL PANEL LCP2.
11
DEDICATED DOUBLE DUPLEX RECEPTACLES FOR WATER SOFTENER. HOMERUN 2-12, 1-12G, 1/2"C. VERIFY EXACT MOUNTING LOCATION WITH EQUIPMENT PROVIDED.
12
DEDICATED RECEPTACLE FOR WATER HEATER. REFER TO MECHANICAL EQUIPMENT CONNECTION CHART FOR DETAILS.
13
CONNECT TO CIRCULATION PUMP. REFER TO MECHANICAL EQUIPMENT CONNECTION CHART FOR DETAILS.
14
CONNECT TO MED GAS COMBINATION MASTER/AREA ALARM PANEL. HOMERUN 2-12, 1-12G, 1/2"C. VERIFY DETAILS AND REQUIREMENTS WITH EQUIPMENT INSTALLER.
15
CONNECT TO OXYGEN SUPPLY MANIFOLD. HOMERUN 2-12, 1-12G, 1/2"C. HOMERUN 2-12, 1-12G, 1/2"C. PROVIDE AND INSTALL A 120VAC SPST TOGGLE SWITCH FOR LOCAL DISCONNECTING MEANS. VERIFY DETAILS AND REQUIREMENTS WITH EQUIPMENT INSTALLER.
16
CONNECT TO NITROGEN SUPPLY MANIFOLD. HOMERUN 2-12, 1-12G, 1/2"C. HOMERUN 2-12, 1-12G, 1/2"C. PROVIDE AND INSTALL A 120VAC SPST TOGGLE SWITCH FOR LOCAL DISCONNECTING MEANS. VERIFY DETAILS AND REQUIREMENTS WITH EQUIPMENT INSTALLER.
17
CONNECT TO NITROUS OXIDE SUPPLY MANIFOLD. HOMERUN 2-12, 1-12G, 1/2"C. HOMERUN 2-12, 1-12G, 1/2"C. PROVIDE AND INSTALL A 120VAC SPST TOGGLE SWITCH FOR LOCAL DISCONNECTING MEANS. VERIFY DETAILS AND REQUIREMENTS WITH EQUIPMENT INSTALLER.
18
CONNECT TO MEDICAL AIR SUPPLY MANIFOLD. HOMERUN 2-12, 1-12G, 1/2"C. HOMERUN 2-12, 1-12G, 1/2"C. PROVIDE AND INSTALL A 120VAC SPST TOGGLE SWITCH FOR LOCAL DISCONNECTING MEANS. VERIFY DETAILS AND REQUIREMENTS WITH EQUIPMENT INSTALLER.
19
CONNECT TO MEDICAL VACUUM PACKAGED SKID. REFER TO MECHANICAL EQUIPMENT CONNECTION CHART FOR DETAILS.
20
RECONNECT EXISTING RECEPTACLE TO EXISTING CHRISTMAS LIGHT RECEPTACLE CIRCUIT AS INDICATED THROUGH EXISTING LIGHTING CONTROL PANEL. CONTRACTOR TO VERIFY.
21
RECEPTACLE LOCATED ON ROOF ON BACK OF PARAPET FOR CHRISTMAS LIGHTS. COORDINATE EXACT LOCATION WITH ARCHITECT.
22
2-12, 1-12G, 1/2"C. TO EF 5-18. CONNECT TO SAME CIRCUIT AS EXHAUST FAN.
23
CONNECT TO MOTORIZED DAMPER AND INTERLOCK WITH EXHAUST FAN EF 5-18. DAMPER SHALL BE POWERED OPEN WHEN EXHAUST FAN IS RUNNING AND SPRING RETURN CLOSED WHEN EXHAUST FAN IS OFF.
WP GFI
C-26
T
EF 1-18
WP GFI
21
J
10
9 H-20 (ON) T
1 GFI
H-1,3,5 RTU 1-18
J
EX RTU-3
EX EF-9 J
J
EX EF-8
EX RTU-8
T
J
HUM 1-18
J
EX RTU-6
J
RTU 2-18 2
J J
8
EX EF-7
J
J WP GFI
LS-1 T
T
H-7,9,11
EQ-1,3,5
3
J
H-2,4,6
14
T J J
21 WP GFI
EX FC-1
EX CU-1
J
T
J
10 H-20 (ON)
J
EX RTU-9
EX RTU-7
EF 2-18 EX RTU-4
9 J
J
T H
23 EX EF-1 J 22
M J H
EX RTU-5
EX EF-6 J J
VH 1-18
T
EX EF-2 RTU 3-18
J
3 T J
H-13,15,17
WP GFI
J
21
EX EF-3 EQ-7,9,11
J
WP GFI
J
EX EF-5
T
21
2
2
G-20
10
T
G-22 (ON)
WP GFI
1 H-8,10,12 J
HUM 2-18
J
HUM 3-18
10
H-19,21,23
J
WP GFI
WP GFI
2
J
J
J
11
Project
RTU 4-18
8
WS 1-18
H-14,16,18 T
1611 WALLACE BLVD, AMARILLO, TEXAS 79106
H-24
3 RTU 5-18
2 GFI
WH 1-18
J
PROFFER SURGICAL CENTER ADDITION
12 GFI
H-26 J
J
H-25,27,29
2 EQ-13,15,17
18 H
H-22 (ON)
10
J
21 G-22 (ON) 10
EF 4-18
9
H-22 (ON)
10
A R C H I T E C T S
EQ-2,4,6
10
LS-7 LS-9
MASM 1-18
LS-5 LS-3
10
J
1.
H-30
J
FC 1-18 7
J
5
OSM 1-18
H-31,33
JANUARY 29, 2018 Sheet No.
EF 5-18
J
CU 1-18 6
Date Issued
2.
15 J
P L A N N E R S
3003 MONTE VISTA BLVD. NE ALBUQUERQUE, NM 87106 P. (505) 268-3033 F. (505) 212-0354
[email protected]
Revisions
4
WP GFI
CTB ASSOCIATES
J
J J
19
17
T
9 EF 3-18
J WP GFI
G-22 (ON)
H-28 J
21
16 NSM 1-18 NOSM 1-18
MV 1-18
13
3.
N 9
EQUIPMENT POWER FLOOR PLAN
SCALE: 1/8" = 1'-0" 0
2'
4'
8'
Sheet Name
EQUIPMENT POWER FLOOR PLAN
E-9
GENERAL NOTES
SP
REFER TO POWER FLOOR PLAN FOR PANEL LOCATIONS.
2.
ALL DATA/TELEPHONE OUTLETS, JUNCTION BOXES, PA SYSTEM DEVICES, FIRE ALARM DEVICES, ETC. SHALL BE EXISTING TO REMAIN AND ARE SHOWN FOR REFERENCE ONLY UNLESS NOTED OTHERWISE.
SP
KEYED NOTES V
SP V
SP
1.
TV
1
INSTALL EMERGENCY GLASS-BREAK STOP STATION FOR GENERATOR.
2
INSTALL GENERATOR REMOTE ANNUNCIATOR. FLUSH MOUNT IN WALL IN A FLUSH MOUNT ENCLOSURE.
3
REFER TO ARCHITECTURAL ELEVATIONS FOR DATA AND/OR TELEPHONE OUTLET MOUNTING LOCATIONS.
4
NURSE CALL CENTRAL EQUIPMENT MOUNTED ON WALL. HOMERUN 2-12, 1-12G, 1/2"C. TO CIRCUIT AS INDICATED FOR POWER. PROVIDE RECEPTACLE IF REQUIRED. VERIFY REQUIREMENTS WITH EQUIPMENT PROVIDED.
5
NURSE CALL MASTER STATION.
6
INSTALL THREE WIREMOLD FS4R OR EQUAL 4" FIRESTOPS AND 4" CONDUIT SLEEVES THROUGH WALL ABOVE ACCESSIBLE CEILING FOR DATA/TELEPHONE/CABLE TV CABLING.
7
INSTALL DATA/TELEPHONE CABLE IN CONDUIT INSTALLED BELOW SLAB FROM MILLWORK TO NEAREST WALL, THEN UP IN WALL TO ACCESSIBLE CEILING SPACE.
8
EXISTING PLYWOOD TERMINAL BOARD MOUNTED ON WALL WITH CABLE TV EQUIPMENT/SPLITTERS AND 110 PUNCHDOWN BLOCKS FOR TELEPHONE CABLING.
9
EXISTING FLOOR MOUNTED RACK FOR DATA CABLING.
10
SINGLE GANG J-BOX WITH 3/4" EMT TO ACCESSIBLE CEILING SPACE FOR AHU KILL SWITCH. VERIFY ORIENTATION WITH MECHANICAL CONTRACTOR.
SP J
V
FUT
TV BC V
BC WAC
SP TV
AC
BC
J AC
CB
EM
J J
AC
J TV
3
AC
J
SP TV
AC
3
J
V
2 V
TV
1 CB J
BC
SP
V
6
V
J
SP
5 8 V
7 BC
J
10
V
3
AC
SP
CB
WAC
SP
AC
9 J
J
J
J
SP
3
SP
SP V
V
TV
V
V
V
SP
CB
3
SP
J
V
V
V
J
J
3 CB
SP
SP
SP
SP
SP
V
V
SP
TV
V
CB
V
V
SP
SP
EM
J
J
J
J
WAC
EM TV
V
TV
TV
SP
SP J
CB
J
TV
AC
Project
J
DS
DB AC AC
1611 WALLACE BLVD, AMARILLO, TEXAS 79106
DS
AC
CB
PROFFER SURGICAL CENTER ADDITION
WAC
DS AC
CTB ASSOCIATES A R C H I T E C T S
P L A N N E R S
3003 MONTE VISTA BLVD. NE ALBUQUERQUE, NM 87106 P. (505) 268-3033 F. (505) 212-0354
[email protected]
Revisions 1.
Date Issued
JANUARY 29, 2018 Sheet No.
2.
CR-27 4
3.
N
SPECIAL SYSTEMS FLOOR PLAN
SCALE: 1/8" = 1'-0" 0
2'
4'
8'
Sheet Name
SPECIAL SYSTEMS FLOOR PLAN
E-10
GENERAL NOTES 1.
REFER TO POWER FLOOR PLAN FOR PANEL LOCATIONS.
2.
ALL DATA/TELEPHONE OUTLETS, JUNCTION BOXES, PA SYSTEM DEVICES, FIRE ALARM DEVICES, ETC. SHALL BE EXISTING TO REMAIN AND ARE SHOWN FOR REFERENCE ONLY UNLESS NOTED OTHERWISE.
P
KEYED NOTES 1
NEW FIRE ALARM CONTROL PANEL. CONNECT TO CIRCUIT AS SHOWN FOR POWER.
2
INSTALL TWO TELEPHONE CABLES TO FIRE ALARM CONTROL PANEL.
3
FIRE ALARM REMOTE ANNUNCIATOR.
4
INSTALL A DUCT SMOKE DETECTOR IN RETURN AIR DUCT OF ROOF TOP UNIT AND CONNECT TO THE FIRE ALARM SYSTEM. DUCT DETECTOR SHALL HAVE A DPDT RELAY TO BE USED TO SHUTDOWN THE UNIT UPON SENSING PRODUCTS OF COMBUSTION. INSTALL A REMOTE TEST STATION IN THE CEILING NEAR THE DETECTOR. REFER TO MECHANICAL FLOOR PLAN FOR DETAILS.
5
PROVIDE NEW MONITORING MODULE AT NEW SPRINKLER SYSTEM FLOW SWITCH CONNECTED TO NEW FIRE ALARM SYSTEM.
6
PROVIDE NEW MONITORING MODULE AT NEW SPRINKLER SYSTEM TAMER SWITCH(ES) CONNECTED TO NEW FIRE ALARM SYSTEM.
H
3
P
S
D
S
D
H
P
H
3
S
P
H
S
D
S
D
4
6
SD
2
1
5
4
2
Project
H
RTU 4-18
PROFFER SURGICAL CENTER ADDITION 1611 WALLACE BLVD, AMARILLO, TEXAS 79106
CTB ASSOCIATES A R C H I T E C T S
P L A N N E R S
3003 MONTE VISTA BLVD. NE ALBUQUERQUE, NM 87106 P. (505) 268-3033 F. (505) 212-0354
[email protected]
H
Revisions 1.
Date Issued
JANUARY 29, 2018 Sheet No.
2.
LS-6 1
S
2
3.
3
P
N
FIRE ALARM FLOOR PLAN
SCALE: 1/8" = 1'-0" 0
2'
4'
8'
Sheet Name
FIRE ALARM FLOOR PLAN
E-11
LEGEND SPST WALL SWITCH, 20A, 120/277V.
E
SPST EMERGENCY WALL SWITCH, 20A, 120/277V, RED COLOR.
D
SINGLE POLE WALL DIMMER, 120/277VAC, LUTRON N XOO NOVA SERIES, WATTAGE AS REQUIRED OR NOTED. COORDINATE DETAILS W/ 0-10V DIMMING LED DRIVERS.
PI
WALL MOUNTED INFRARED VACANCY SENSOR, 120/277V, MINIMUM 800W, EQUAL TO WATTSTOPPER PW-100.
PI 3
WALL MOUNTED INFRARED MULTI-WAY VACANCY SENSOR, 120/277V, MINIMUM 800W, EQUAL TO WATTSTOPPER PW-103.
PI 4
WALL MOUNTED INFRARED MULTI-WAY VACANCY SENSOR, 120/277V, MINIMUM 800W, EQUAL TO WATTSTOPPER PW-103.
INTERIOR LIGHT FIXTURE SCHEDULE MARK
DESCRIPTION
A
2X4 LENSED RECESSED GRID MOUNTED LED TROFFER.
BL
2X2 LENSED RECESSED GRID MOUNTED LED TROFFER.
HOUSING
BALLAST
3.25" NOMINAL HEIGHT MINIMUM 22 GAUGE STEEL HOUSING, FLAT WHITE MINIMUM 20 GAUGE STEEL GASKETED DOOR FRAME, CAM OR SPRING LOADED DOOR LATCHES, PAINTED AFTER FABRICATION.
120V ELECTRONIC LED DRIVER.
3.25" NOMINAL HEIGHT MINIMUM 22 GAUGE STEEL HOUSING, FLAT WHITE MINIMUM 20 GAUGE STEEL GASKETED DOOR FRAME, CAM OR SPRING LOADED DOOR LATCHES, PAINTED AFTER FABRICATION.
120V ELECTRONIC LED DRIVER.
VOLTAGE
120V
120V
LAMP(S)
LENS/NOTES
A19 PATTERN 0.156" MINIMUM THICKNESS VIRGIN ACRYLIC LENS.
4,200 LUMEN, 35W, 4,000K LED ARRAY (PROVIDED WITH FIXTURE).
APPROVED MANUFACTURERS
A19 PATTERN 0.156" MINIMUM THICKNESS VIRGIN ACRYLIC LENS.
2,800 LUMEN, 23W, 4,000K LED ARRAY (PROVIDED WITH FIXTURE).
METALUX 22GR-LD5-28-A19/156-UNV-L840-CD1-PAF-G2 OR PRE-APPROVED EQUAL.
2X2 LENSED RECESSED GRID MOUNTED LED TROFFER.
3.25" NOMINAL HEIGHT MINIMUM 22 GAUGE STEEL HOUSING, FLAT WHITE MINIMUM 20 GAUGE STEEL GASKETED DOOR FRAME, CAM OR SPRING LOADED DOOR LATCHES, PAINTED AFTER FABRICATION.
120V ELECTRONIC LED DRIVER.
120V
A19 PATTERN 0.156" MINIMUM THICKNESS VIRGIN ACRYLIC LENS.
3,600 LUMEN, 35W, 4,000K LED ARRAY (PROVIDED WITH FIXTURE).
METALUX 22GR-LD5-36-A19/156-UNV-L840-CD1-PAF-G2 OR PRE-APPROVED EQUAL.
CD
2X2 LENSED RECESSED GRID MOUNTED LED PANEL.
0.40" NOMINAL PANEL HEIGHT EXTRUDED ALUMINUM FRAME WITH WHITE POWDER COAT FINISH AND MITERED CORNERS.
120V ELECTRONIC 0-10V DIMMING LED DRIVER.
120V
MATTE FINISH OPAL LENS.
4,000 LUMEN, 40W, 4,000K LED ARRAY (PROVIDED WITH FIXTURE).
LUMENOPTIX LUZ-22-40-EA8-40K-DU1 OR PRE-APPROVED EQUAL.
D
2X2 RECESSED GRID MOUNTED DIRECT/INDIRECT LED TROFFER.
6" NOMINAL HEIGHT DIE-FORMED CODE GAUGE STEEL HOUSING, HIGH REFLECTANCE WHITE POLYESTER POWDER COAT FINISH, PAINTED AFTER FABRICATION.
120V ELECTRONIC LED DRIVER.
120V
BAKED MATTE WHITE INDIRECT REFLECTOR, HIGH REFLECTANCE PERFORATED DIRECT REFLECTOR.
4,000 LUMEN, 42W, 4,000K LED ARRAY (PROVIDED WITH FIXTURE).
METALUX 22RDI-40-UNV-L840-CD1 OR PRE-APPROVED EQUAL.
E
4 FT. LENSED LED STRIPLIGHT.
3" NOMINAL WIDTH, STEEL HOUSING PAINTED AFTER FABRICATION, PROVIDE WITH CHAIN HANGING SET.
120V ELECTRONIC LED DRIVER.
120V
LENSED CLEAR OPTICAL SYSTEM.
4,700 LUMEN, 35W, 4,000K LED ARRAY (PROVIDED WITH FIXTURE).
METALUX 4SNLED-LD5-46SL-LC-UNV-L840-CD1AYC-CHAIN/SET OR PRE-APPROVED EQUAL.
F
4 FT. LENSED LED STRIPLIGHT.
3" NOMINAL WIDTH, STEEL HOUSING PAINTED AFTER FABRICATION.
120V ELECTRONIC LED DRIVER.
120V
LENSED CLEAR OPTICAL SYSTEM.
4,700 LUMEN, 35W, 4,000K LED ARRAY (PROVIDED WITH FIXTURE).
METALUX 4SNLED-LD5-46SL-LC-UNV-L840-CD1 OR PRE-APPROVED EQUAL.
GM
GME
GH
H
LE
XY
Y
Z
HOSPITAL GRADE DOUBLE DUPLEX RECEPTACLES, 20A, 125V. MOUNT AT STANDARD RECEPTACLE HEIGHT UNLESS DENOTED BY AC "ABOVE COUNTER" OR BC " BELOW COUNTER.
E
HOSPITAL GRADE DUPLEX EMERGENCY RECEPTACLE, 20A 125V, RED COLOR, CIRCUIT NUMBER AND PANEL ENGRAVED IN FACEPLATE. MOUNT AT STANDARD RECEPTACLE HEIGHT UNLESS DENOTED BY AC "ABOVE COUNTER" OR BC " BELOW COUNTER.
2E
HOSPITAL GRADE 4-PLEX EMERGENCY RECEPTACLE, 20A 125V, RED COLOR, CIRCUIT NUMBER AND PANEL ENGRAVED IN FACEPLATE. MOUNT AT STANDARD RECEPTACLE HEIGHT UNLESS DENOTED BY AC "ABOVE COUNTER" OR BC " BELOW COUNTER.
GFI
HOSPITAL GRADE DUPLEX RECEPTACLE, 20A 125V, GROUND FAULT INTERRUPTER. MOUNT AT STANDARD RECEPTACLE HEIGHT UNLESS DENOTED BY AC "ABOVE COUNTER" OR BC " BELOW COUNTER.
WP WP\PGFI GFI
HOSPITAL GRADE DUPLEX RECEPTACLE, 20A 125V, GROUND FAULT INTERRUPTER W/ WEATHERPROOF COVER. MOUNT AT STANDARD RECEPTACLE HEIGHT UNLESS DENOTED BY AC "ABOVE COUNTER" OR BC " BELOW COUNTER.
GFI\PE GFI E
HOSPITAL GRADE DUPLEX EMERGENCY RECEPTACLE, 20A 125V, GROUND FAULT INTERRUPTER, RED COLOR, CIRCUIT NUMBER AND PANEL ENGRAVED IN FACEPLATE. MOUNT AT STANDARD RECEPTACLE HEIGHT UNLESS DENOTED BY AC "ABOVE COUNTER" OR BC " BELOW COUNTER.
J
JUNCTION BOX MOUNTED ABOVE CEILING LINE, 4" SQUARE WITH BLANK COVER.
J
EQUIPMENT CONNECTION OR WALL JUNCTION BOX. FOR WALL JUNCTION BOX, PROVIDE 4" SQUARE BOX WITH SINGLE GANG RING AND 3/4" EMT TO CEILING SPACE. FURNISH BLANK PLATE.
RECESSED GRID OR GYPBOARD MOUNTED 6" 11W LED DOWNLIGHT.
120V ELECTRONIC LED DRIVER.
120V
WIDE BEAM DISTRIBUTION.
1,000 LUMEN, 11W, 4,000K LED (PROVIDED WITH FIXTURE).
PORTFOLIO LD6B10D010-EU6B10208040-6LBW1H-HB26 OR PRE-APPROVED EQUAL.
RECESSED GRID OR GYPBOARD MOUNTED 6" 16W LED DOWNLIGHT.
5-1/2" NOMINAL HEIGHT, 6" NOMINAL DIAMETER, ALUMINUM REFLECTOR CONE, CLEAR-ALZAK SEMI-SPECULAR REFLECTOR CONE, UPPER OPTICAL CHAMBER, SELF-FLANGED, UNIVERSAL MOUNTING BRACKET, INTEGRATED JUNCTION BOX, EXTRUDED HEAT SINK, COMPLETE WITH BAR HANGERS.
120V ELECTRONIC LED DRIVER.
120V
WIDE BEAM DISTRIBUTION.
1,500 LUMEN, 16W, 4,000K LED (PROVIDED WITH FIXTURE).
PORTFOLIO LD6B15D010-EU6B10208040-6LBW1H-HB26 OR PRE-APPROVED EQUAL.
DATA OUTLET, 4" SQUARE WITH SINGLE GANG RING AND 3/4" EMT TO CEILING SPACE. FURNISH JACKS AND PLATE AS NOTED ON DATA/TELEPHONE/CABLE TV RISER DIAGRAM. MOUNT AT STANDARD RECEPTACLE HEIGHT UNLESS DENOTED BY AC "ABOVE COUNTER" OR BC " BELOW COUNTER.
RECESSED GRID OR GYPBOARD MOUNTED 6" 16W LED DOWNLIGHT.
5-1/2" NOMINAL HEIGHT, 6" NOMINAL DIAMETER, ALUMINUM REFLECTOR CONE, CLEAR-ALZAK SEMI-SPECULAR REFLECTOR CONE, UPPER OPTICAL CHAMBER, SELF-FLANGED, UNIVERSAL MOUNTING BRACKET, INTEGRATED JUNCTION BOX, EXTRUDED HEAT SINK, COMPLETE WITH BAR HANGERS.
120V ELECTRONIC LED DRIVER + EMERGENCY BATTERY PACK.
120V
WIDE BEAM DISTRIBUTION.
1,500 LUMEN, 16W, 4,000K LED (PROVIDED WITH FIXTURE).
PORTFOLIO LD6B15D010IEM14-EU6B102080406LBW1HE-HB26 OR PRE-APPROVED EQUAL.
COMBINATION TELEPHONE AND (2) DATA OUTLETS, 4" SQUARE WITH SINGLE GANG RING AND TWO 3/4" EMT CONDUITS TO CEILING SPACE. FURNISH JACKS AND PLATE AS NOTED ON DATA/TELEPHONE/CABLE TV RISER DIAGRAM. MOUNT AT STANDARD RECEPTACLE HEIGHT UNLESS DENOTED BY AC "ABOVE COUNTER" OR BC " BELOW COUNTER.
RECESSED GRID OR GYPBOARD MOUNTED 6" 21W LED DOWNLIGHT.
5-1/2" NOMINAL HEIGHT, 6" NOMINAL DIAMETER, ALUMINUM REFLECTOR CONE, CLEAR-ALZAK SEMI-SPECULAR REFLECTOR CONE, UPPER OPTICAL CHAMBER, SELF-FLANGED, UNIVERSAL MOUNTING BRACKET, INTEGRATED JUNCTION BOX, EXTRUDED HEAT SINK, COMPLETE WITH BAR HANGERS.
120V ELECTRONIC LED DRIVER.
120V
WIDE BEAM DISTRIBUTION.
2,000 LUMEN, 21W, 4,000K LED (PROVIDED WITH FIXTURE).
PORTFOLIO LD6B20D010-EU6B10208040-6LBW1H-HB26 OR PRE-APPROVED EQUAL.
1X4 SURGICAL SUITE GYPBOARD MOUNTED LED TROFFER.
K
2
5-1/2" NOMINAL HEIGHT, 6" NOMINAL DIAMETER, ALUMINUM REFLECTOR CONE, CLEAR-ALZAK SEMI-SPECULAR REFLECTOR CONE, UPPER OPTICAL CHAMBER, SELF-FLANGED, UNIVERSAL MOUNTING BRACKET, INTEGRATED JUNCTION BOX, EXTRUDED HEAT SINK, COMPLETE WITH BAR HANGERS.
2X4 CLEANROOM SEALED GYPBOARD MOUNTED LED TROFFER.
J
SWITCH STATION FOR LIGHTING CONTROL SYSTEM. TYPE AS NOTED. NUMBER DENOTES SWITCH NUMBER. HOSPITAL GRADE DUPLEX RECEPTACLE, 20A, 125V. MOUNT AT STANDARD RECEPTACLE HEIGHT UNLESS DENOTED BY AC "ABOVE COUNTER" OR BC " BELOW COUNTER.
METALUX 24GR-LD5-42-A19/156-UNV-L840-CD1-PAF-G2 OR PRE-APPROVED EQUAL.
BH
GL
L01
4.5" NOMINAL HEIGHT, MINIMUM 20 GAUGE STEEL ONE-PIECE HOUSING, GLOSS WHITE POLYESTER POWDER-COAT FINISH, ANTIMICROBIAL FINISH ON ALL EXPOSED PAINTED SURFACES, 20 GAUGE TYPE 304 BRUSHED STAINLESS STEEL DOOR FRAME SECURED TO HOUSING WITH STAINLESS STEEL AIRCRAFT CABLES AND CAPTIVE, FLUSH MOUNTED PHILLIPS HEAD FASTENERS, INTEGRAL HEAT SINK, INSTALL FRAME FOR GYPBOARD CEILING MOUNTING.
120V ELECTRONIC LED DRIVER.
4.5" NOMINAL HEIGHT, MINIMUM 20 GAUGE STEEL ONE-PIECE HOUSING, GLOSS WHITE POLYESTER POWDER-COAT FINISH, ANTIMICROBIAL FINISH ON ALL EXPOSED PAINTED SURFACES, 18 GAUGE TYPE 304 BRUSHED STAINLESS STEEL DOOR FRAME SECURED TO HOUSING WITH STAINLESS STEEL AIRCRAFT CABLES AND CAPTIVE, FLUSH MOUNTED PHILLIPS HEAD FASTENERS, INTEGRAL HEAT SINK, INSTALL FRAME FOR GYPBOARD CEILING MOUNTING.
TWO 120V ELECTRONIC LED DRIVERS WITH EMERGENCY BATTERY PACK FOR ASYMETRICAL (INTERIOR) SIDE OF FIXTURE.
SYMMETRIC OPTIC, DIFFUSED IMPACT RESISTANT ACRYLIC LENS.
5,640 LUMEN, 49W, 4,000K LED ARRAY (PROVIDED WITH FIXTURE).
KENALL CSEDO-24-45L40K-DCC-DV-5F-2H-SYM-AMF-IF OR PRE-APPROVED EQUAL.
WAC
ONE DATA CABLE LOCATED ABOVE CEILING FOR WIRELESS ACCESS POINT (BY OTHERS). PROVIDE RJ-45 JACK ON END OF CABLE. PROVIDE MINIMUM OF 25 FEET OF COILED CABLE TO ALLOW FOR FUTURE RELOCATION.
TV
F-TYPE TV OUTLET. TYPE AS NOTED ON DATA/TELEPHONE/CABLE TV RISER DIAGRAM. REFER TO ARCHITECTURAL FOR EXACT MOUNTING LOCATION.
FUT
J
SINGLE GANG J-BOX FOR FUTURE USE LOCATED AT STANDARD RECEPTACLE HEIGHT WITH ONE 3/4" EMT TO ACCESSIBLE CEILING SPACE. PROVIDE BLANK COVER. GENERAL DUTY NON-FUSED SAFETY SWITCH, AMPACITY AND NUMBER OF POLES AS NOTED. FURNISH NEMA 1 OR NEMA 3R ENCLOSURE AS REQUIRED. SEE MECHANICAL EQUIPMENT CONNECTION CHART.
RECESSED GRID OR GYPBOARD MOUNTED 6" 11W LED SQUARE LENSED DOWNLIGHT.
6-1/4" NOMINAL HEIGHT, 6" SQUARE, ALUMINUM REFLECTOR CONE, PAINTED BLACK REFLECTOR AND FLANGE, UPPER OPTICAL CHAMBER, SELF-FLANGED, UNIVERSAL MOUNTING BRACKET, INTEGRATED JUNCTION BOX, EXTRUDED HEAT SINK, COMPLETE WITH BAR HANGERS.
WALL MOUNTED CUTOFF TYPE LED WALL PACK.
ONE PIECE DIE-CAST HOUSING IN SQUARE WEDGE SHAPE, WET LOCATION GASKETED DIE-CAST HINGED ALUMINUM DOOR FRAME WITH STAINLESS STEEL FASTENERS FOR STANDARD FACE-DOWN MOUNTING, ELECTROSTATICALLY APPLIED BLACK PAINT AFTER FABRICATION.
COMBINATION L.E.D. EXIT SIGN/EMERGENCY LIGHTING UNIT.
THIN PROFILE WHITE ALUMINUM HOUSING, WHITE ALUMINUM STENCIL FACE, NUMBER OF FACES AND DIRECTIONAL ARROWS AS INDICATED ON DRAWINGS, DIFFUSE RED FACE PANEL(S), INTEGRAL LED EMERGENCY LIGHTS IN A LOW-PROFILE DESIGN PROTECTED BY A POLYCARBONATE SHIELD, UNIVERSAL MOUNTING.
-
EMERGENCY LIGHTING UNIT.
NORMALLY EXPOSED FLAT DOOR AND FRAME POWDER COATED WITH A TEXTURED OFF-WHITE FINISH, HEAVY DUTY GALVANIZED STEEL BACK-BOX CONCEALED IN CEILING, T-BAR HANGERS AND GYPBOARD HANGERS INCLUDED, LAMPS NORMALLY CONCEALED IN HOUSING AND UNIT DOOR ROTATES 180° TO EXPOSE LAMPS AND ILLUMINATE THE PATH OF EGRESS UPON POWER FAILURE.
LONG LIFE NICKEL CADMIUM BATTERY, 40W UNIT CAPACITY, PULSE-PLUS BATTERY CHARGER, AUTOMATIC BATTERY DISCONNECT WHEN BATTERY REACHES 87% OF ITS NOMINAL VOLTAGE.
HIGH IMPACT THERMOPLASTIC W/ OFF WHITE FINISH.
LONG LIFE NICKEL CADMIUM BATTERY.
EMERGENCY LIGHTING UNIT.
120V
TELEPHONE OUTLET, 4" SQUARE WITH SINGLE GANG RING AND 3/4" EMT TO CEILING SPACE. FURNISH JACKS AND PLATE AS NOTED ON DATA/TELEPHONE/CABLE TV RISER DIAGRAM. MOUNT AT STANDARD RECEPTACLE HEIGHT UNLESS DENOTED BY AC "ABOVE COUNTER" OR BC " BELOW COUNTER.
120V ELECTRONIC LED DRIVER.
120V ELECTRONIC LED DRIVER + EMERGENCY BATTERY PACK.
120V
ASYMETRIC/SYMETRIC INTERNAL LINEAR PRISMATIC LENS. FIXTURE MEETS OR EXCEEDS FCC CFR PART 15 AND MIL-STD-461F REQUIREMENTS.
120V
REGRESSED PRISMATIC LENS.
120V
RECTANGULAR WIDE THROW DISTRIBUTION, SURGE PROTECTION PROVIDED WITH FIXTURE, PROVIDED W/ A BUTTON TYPE PHOTOCELL.
120V
NI-CAD BATTERY PACK AND CHARGER WITH TEST SWITCH AND CHARGING INDICATOR, 20 YEAR RATED LAMP LIFE, MUST MEET UL 924 REQUIREMENTS.
8,894 LUMEN, 87W, 4,000K LED ARRAY (PROVIDED WITH FIXTURE).
GENERAL DUTY FUSED SAFETY SWITCH, AMPACITY AND NUMBER OF POLES AS NOTED. FURNISH NEMA 1 OR NEMA 3R ENCLOSURE AS REQUIRED. SEE MECHANICAL EQUIPMENT CONNECTION CHART.
KENALL MEDMASTER M4SEDI-14-76L-40K8-DCC-120-5F-2HASYM-LEL-IF-2C OR PRE-APPROVED EQUAL.
1,100 LUMEN, 14W, 4,000K LED (PROVIDED WITH FIXTURE).
PRESCOLITE LF6SQSL-DM1-6SQSL-11L-40K-BC-PL-B24 OR PRE-APPROVED EQUAL.
3,898 LUMEN, 33W, 4,000K LED (PROVIDED WITH FIXTURE).
MCGRAW-EDISON IST-AF-600-LED-E1-RW-BK-CWB-LCF-P OR PRE-APPROVED EQUAL.
BRANCH CIRCUIT DESIGNATION. IF NO CROSS MARKS ARE SHOWN, CIRCUIT CONTAINS TWO CURRENT CARRYING CONDUCTORS AND ONE GROUNDING CONDUCTOR. IF MORE THAN TWO CURRENT CARRYING CONDUCTORS ARE REQUIRED, CROSS LINES INDICATE THE FOLLOWING: SHORT CROSS LINE INDICATES NEUTRAL CONDUCTOR, LONG CROSS LINE INDICATES HOT OR SWITCHED CONDUCTOR, LONG CROSS LINE WITH DOT INDICATES ADDITIONAL ISOLATED GROUNDING CONDUCTOR.
B-12
L.E.D. (FURNISHED).
P
FIRE ALARM MANUAL PULL STATION.
H
FIRE ALARM AREA HEAT DETECTOR.
EXITRONIX 400C SERIES OR PRE-APPROVED EQUAL.
SD S
120V
SEALED DUST-TIGHT RELAY, TEST SWITCH, DUAL DIAGNOSTIC LED INDICATOR LIGHT.
(2) MR-16 LED 6W LAMPS SUPPLIED WITH UNIT.
EMERGI-LITE REVELATION SERIES RT-M-40-2(LJ)-ADNA OR PRE-APPROVED EQUAL.
ARROW WITH CIRCUIT NUMBER INDICATES HOMERUN AND PANEL CIRCUIT NUMBER.
H
Project
FIRE ALARM DUCT SMOKE DETECTOR. FIRE ALARM AREA SMOKE DETECTOR.
PROFFER SURGICAL CENTER ADDITION 1611 WALLACE BLVD, AMARILLO, TEXAS 79106
FIRE ALARM HORN STROBE.
FIRE ALARM STROBE. 120-277V MVOLT
CURRENT LIMITING CHARGER, TEST SWITCH, SINGLE MULTICOLOR LED INDICATOR LIGHT.
(2) 1.5W L.E.D. (FURNISHED)
LITHONIA ELM2 OR PRE-APPROVED EQUAL.
S
FIRE ALARM CEILING MOUNTED SPEAKER STROBE. FIRE ALARM CEILING MOUNTED STROBE.
CTB ASSOCIATES A R C H I T E C T S
GENERAL NOTES: A.
B.
D
ELECTRONIC DRIVERS: 1.
REFER TO THE SPECIFICATIONS FOR COMPLETE DETAILS.
2.
REFER TO THE FIXTURE DESCRIPTION FOR DRIVER VOLTAGE.
3.
PROVIDE SPARE DRIVERS AS REQUIRED IN THE SPECIFICATIONS. DELIVER TO THE OWNER AT THE COMPLETION OF THE PROJECT.
FIXTURES: 1.
ALL TROFFER ACRYLIC LENSES SHALL HAVE A MINIMUM THICKNESS OF 0.125" WITH STRAIGHT PYRAMIDAL PRISM SIDES AND A MINIMUM WEIGHT OF 7.8 OUNCES PER SQUARE FOOT.
2.
WHERE A "FIXTURE SERIES" IS LISTED, ALL LISTED MANUFACTURER'S SERIES ARE PRE-APPROVED PROVIDED THE ACTUAL PRODUCTS MEET THE DESCRIPTION. ALL OTHERS REQUIRE PRE-APPROVAL. WHERE ONLY ONE OR TWO SPECIFIC FIXTURES ARE LISTED, ALL OTHER MANUFACTURER'S PRODUCT SUBSTITUTIONS REQUIRE PRE-APPROVAL.
3.
FIXTURE CATALOG NUMBERS FOR "FIXTURE SERIES" ARE NOT COMPLETE AND ARE INTENDED ONLY TO INDICATE THE GENERAL FIXTURE SERIES TO BE PROVIDED.PROVIDE COMPLETE CATALOG NUMBERS UPON SUBMITTAL TO MATCH ALL FIXTURE REQUIREMENTS DESCRIBED.
FIRE ALARM MAGNETIC DOOR HOLDER. FIRE ALARM RELAY OR MODULE AS NOTED.
EM
NURSE CALL EMERGENCY STATION.
CB
NURSE CALL CODE BLUE STATION.
DS
NURSE CALL DUTY STATION. NURSE CALL DOME LIGHT.
4.
ALL LIGHTING FIXTURES INSTALLED IN INACCESSIBLE CEILINGS SHALL BE SERVICEABLE FROM BELOW, WHERE COMPONENT SERVICE (SUCH AS DRIVER REPLACEMENT) IS REQUIRED.
P L A N N E R S
3003 MONTE VISTA BLVD. NE ALBUQUERQUE, NM 87106 P. (505) 268-3033 F. (505) 212-0354
[email protected]
T
SINGLE GANG J-BOX WITH 3/4" EMT TO ACCESSIBLE CEILING SPACE FOR SPACE TEMPERATURE SENSOR. VERIFY ORIENTATION WITH MECHANICAL CONTRACTOR.
H
SINGLE GANG J-BOX WITH 3/4" EMT TO ACCESSIBLE CEILING SPACE FOR SPACE HUMIDITY SENSOR. VERIFY ORIENTATION WITH MECHANICAL CONTRACTOR.
Revisions 1.
Date Issued
JANUARY 29, 2018 Sheet No.
2.
3.
Sheet Name
LIGHT FIXTURE SCHEDULE AND LEGEND
E-12
TYPICAL RELAY PANEL
RELOCATED POLE AND POLE MOUNTED FIXTURE
CONNECT GROUND WIRE TO POLE & TO SYSTEM GROUND WIRE
EXISTING NUT COVERS
PROVIDE NEW LEVELING NUTS & WASHERS
1 IN. MAX. NON-SHRINKING GROUT BETWEEN BASE PLATE & TOP OF POLE BASE
EXISTING SQUARE STEEL BASE PLATE 1IN. EDGE CHAMFER
32 IN.
3 - #4 REBAR TIES
RUBBED FINISH ABOVE GRADE
FINISH GRADE
#6 BARE CU GROUND WIRE UPTO 4 RELAYS PER OUTPUT
PROVIDE NEW 3/4" x 25" x 3" ANCHOR BOLTS
SEE PANEL SCHEDULES FOR EXACT AMOUNTS
12 IN.
CLASS 2 - LOW VOLTAGE
CLASS 1 - LINE VOLTAGE
80 IN.
MIN. 24 IN. DEEP PVC CONDUIT,
1/2 IN. X 6 FT. CU CLAD GROUND ROD - (INSTALL SEPARATE FROM BASE)
ROUND SHAFT W/ 3000# CONCRETE 12 FT. 4-#6 VERT. REBARS W/#4 HORIZ. REBAR TIES @ 12 IN. O.C.
2
2
2
BUTTON 1
BUTTON 1
2
BUTTON 1
2
BUTTON 2 BUTTON 1
BUTTON 2 BUTTON 3
TW
TW
TO NEXT PANEL FROM PREVIOUS PANEL
LOW VOLTAGE DATALINE SWITCH WNS-2301
TW
BUTTON 2
LOW VOLTAGE DATALINE SWITCH WNS-2302
BUTTON 3
TW
LOW VOLTAGE DATALINE SWITCH WNS-2303
TW
BUTTON 4
TO NEXT DATALINE SWITCH
MINIMUM 4 IN. LARGER THAN DIAGONAL DISTANCE ACROSS POLE BASE PLATE
LOW VOLTAGE DATALINE SWITCH WNS-2304
RELOCATED POLE BASE DETAIL NO SCALE
TYPICAL MASTER PANEL
N
LIGHTING CONTROL PANEL LCP2 SCHEDULE
PHOTOCELL HEAD
DESCRIPTION
TW
UPTO 4 RELAYS PER OUTPUT
CCT
RELAY
LOCAL SWITCH
T/C GROUP
P/C GROUP
RESTRICTED CORRIDOR 120 LTS.
G-4
1
L01/L02
7
-
HALL 106/113 LIGHTS
G-2
2
L03/L04/ L05/L06
8
-
NURSE STATION 107 LIGHTS
CR-18
3
L07/L08
9
-
WAITING 101 LIGHTS
G-2
4
L09/L10/L11
10
-
RECEPTION 102 LIGHTS
G-2
5
L09/L10/L11
10
-
INTERVIEW 103 LIGHTS
G-2
6
L09/L10/L11
10
-
EXTERIOR CANOPY LIGHTS
LS-11
7
-
-
1
CHRISTMAS LIGHT RECEPTACLES (WEST)
G-20
8
-
-
6
CHRISTMAS LIGHT RECEPTACLES (SOUTHWEST)
C-22
9
-
-
6
EF 1-18 / EF 2-18
H-20
10
-
5
-
EF 3-18 / EF 4-18
H-22
11
-
5
-
EF 5-18 / VH 1-18
H-30
12
-
6
-
EXTERIOR LED STRIP LIGHT
G-10
13
-
7
-
SPARE
-
14
-
-
-
SPARE
-
15
-
-
-
SPARE
-
16
-
-
-
SPARE
-
17
-
-
-
SPARE
-
18
-
-
-
SPARE
-
19
-
-
-
SPARE
-
20
-
-
-
SPARE
-
21
-
-
-
SPARE
-
22
-
-
-
SPARE
-
23
-
-
-
TO LOW VOLTAGE COMPARTMENT OF NEAREST RELAY PANEL
TW
TW
2
TW
2
24VAC POWER
TW
2
24VAC POWER
2
24VAC POWER
24VAC POWER
S
S
S
S
LOW VOLTAGE SWITCH 1-DEVICE
LOW VOLTAGE SWITCH 2-DEVICE
LOW VOLTAGE SWITCH 3-DEVICE
LOW VOLTAGE SWITCH 4-DEVICE
SEE PANEL SCHEDULES FOR EXACT AMOUNTS TYPICAL WNS-230X DATALINE SWITCH STATION CONNECTIONS
ONE LINE DIAGRAM
Project
TO NEXT PANEL
TYPICAL LOW VOLTAGE SWITCH CONNECTION
S
FROM PREVIOUS PANEL
LEGEND #
TW
#18AWG WIRING REQUIRED ADD A MINIMUM OF 10% SPARE CONDUCTORS. BELDEN CABLE #8471 WIRING REQUIRED RUN (2) PAIRS OF WIRES.
SPARE
-
24
-
-
- 1 COMMON - PLUS +1 PER SWITCH
TW
MOUNTING TABS
* REFER TO PLANS FOR EXACT LOCATION AND QUANTITY OF LOW VOLTAGE SWITCHES REQUIRED * NETWORK TOPOLOGY OPTIONS: - BUS TOPOLOGY CONFIGURATION (SHOWN) MAX TOTAL WIRING DISTANCE IS 8500FT WITHOUT A REPEATER - FREE-TOPOLOGY (STAR-CONFIGURATION) MAX TOTAL WIRING DISTANCE IS 1600FT WITHOUT A REPEATER
LEGEND TC/PC- = TIME/PHOTO CONTROLLER - CHANNEL
-
CONSISTS OF: 1-DOUGLAS PWE3-W24M-S3 RELAY PANEL (SURFACE MOUNTED) 24-DOUGLAS WR-6161 1-POLE 120V HID RELAYS 1- DOUGLAS WRS-2224 PROGRAMMABLE RELAY SCANNER 1-DOUGLAS WR-4075-120/277 TRANSFORMER
CTB ASSOCIATES A R C H I T E C T S
LINE VOLTAGE
LINE VOLTAGE
MASTER
PANEL
PANEL
LCP2
WALL BOX
LAB
EL SWITCH MODULE WNS-2300 SERIES
N
LOW VOLTAGE
P L A N N E R S
3003 MONTE VISTA BLVD. NE ALBUQUERQUE, NM 87106 P. (505) 268-3033 F. (505) 212-0354
[email protected]
LCP SYSTEM NOTES:
PROFFER SURGICAL CENTER ADDITION 1611 WALLACE BLVD, AMARILLO, TEXAS 79106
#
CLASS 1 - LINE VOLTAGE
CLASS 2 - LOW VOLTAGE
NO SCALE
Revisions 1.
LOW VOLTAGE
Date Issued
JANUARY 29, 2018 Sheet No.
2.
2 SNAP-ON PLASTIC COVER PLATE WN-80300 SERIES
EXTERIOR PHOTOCELL
TW
TYPICAL LIGHTING CONTROL CONNECTION DIAGRAM
LIGHTING CONTROL RISER DIAGRAM
SWITCH STATION INSTALLATION DETAIL
NO SCALE
NO SCALE
NO SCALE
3.
Sheet Name
LIGHTING DETAILS
E-13
EXISTING 4-1/0, 1-6 GND, 2"C. EXISTING 4-500KCM, 1-3 GND, 3"C. EXISTING 4-3, 1-8 GND, 1-1/4"C. EXISTING 4-1, 1-6 GND, 1-1/2"C. EXISTING 4-1, 1-6 GND, 1-1/2"C. EXISTING 4-1/0, 1-6 GND, 2"C.
EXISTING UTILITY COMPANY PADMOUNTED 208Y/120V 3∅ 4W TRANSFORMER.
EX PANEL MDP
EXISTING METER TO BE REMOVED BY UTILITY CO.
EXISTING UTILITY COMPANY FEED-THRU CABINET LOCATED AT NORTHEAST CORNER OF THE PROPERTY.
EXISTING CONCRETE HOUSEKEEPING PAD.
EX PANEL A
EX PANEL B
EX PANEL C
EX PANEL D
EX PANEL E
EX PANEL SM
REMOVE AND DISCARD EXISTING 800A CT CABINET.
FINISHED FLOOR GRADE
EXISTING TWO 3"C. EACH WITH 4-500KCM, 36" BELOW GRADE.
EXISTING UTILITY COMPANY GROUNDING GRID.
EXISTING 4/0 BARE GROUND FROM METER CUBICLE GROUND BAR TO TRANSFORMER GROUND GRID. EXISTING UTILITY COMPANY SERVICE LATERAL.
EXISTING 1-3/0 GND, 1"C. TO 3/4" X 10' CW GROUND ROD, FOUNDATION REBAR, STRUCTURAL STEEL & METALLIC COLD WATER LINE. CONNECT TO GROUND BAR IN PANEL MDP.
EXISTING UTILITY CO. PRIMARY CABLES IN POLY CONDUIT BETWEEN FEED-THRU CABINET AND PADMOUNTED TRANSFORMER. EXISTING UTILITY CO. PRIMARY CABLES IN POLY CONDUIT BETWEEN FEED-THRU CABINET AND PADMOUNTED TRANSFORMER LOCATED AT MED CENTER LEAGUE HOUSE.
DEMOLITION POWER RISER DIAGRAM NO SCALE
1.
ALL UTILITY RELATED WORK SHALL BE COORDINATED WITH AL HUTCHINGS (806)-640-6450 AT XCEL ENERGY. INCLUDE ALL UTILITY WORK RELATED COSTS IN THE BID. DO NOT EXCLUDE UTILITY RELATED COSTS. EXISTING 4-1/0, 1-6 GND, 2"C. TWO 2"C. EACH WITH 4-2/0, 1-3 GND.
EXISTING 4-500KCM, 1-3 GND, 3"C.
2-8, 1-8 GND, 1"C.
4-4/0, 1-4 GND, 2-1/2"C. 2-8, 1-8 GND, 1"C.
EXISTING 4-3, 1-8 GND, 1-1/4"C. 4-1, 1-6 GND, 1-1/2"C.
EXISTING UTILITY COMPANY PADMOUNTED 208Y/120V 3∅ 4W TRANSFORMER.
4-4/0, 1-4 GND, 2-1/2"C.
EXISTING 4-1, 1-6 GND, 1-1/2"C.
CONTRACTOR TO PROVIDE 1600A 208Y/120V 3 PHASE 4 WIRE PADMOUNTED METERING CUBICLE (ERICKSON, AMP, OR EQUAL). CUBICLE TO BE DESIGNED TO ACCEPT UTILITY COMPANY BAR OR WINDOW CTS AS REQUIRED (COORDINATE W/ UTILITY CO.).
4-1, 1-6 GND, 1-1/2"C. 4-1, 1-6 GND, 1-1/2"C.
EXISTING 4-1, 1-6 GND, 1-1/2"C. EXISTING 4-1/0, 1-6 GND, 2"C. INSTRUMENT METER (BY UTILITY CO.) AND METER CAN PROVIDED BY UTILITY CO. CONTRACTOR TO MOUNT METER CAN ON METERING CUBICLE AND INSTALL INTERCONNECTING 1-1/2"C. METER CABLE BY UTILITY CO.
N EX PANEL MDP
350/3 600V MOLDED CASE CIRCUIT BREAKER FURNISHED WITH GENERATOR.
EX PANEL A
EX PANEL B
EX PANEL C
EX PANEL D
EX PANEL E
EX PANEL SM
NEW PANEL MP
NEW PANEL F
NEW PANEL G
NEW PANEL H
L
NEW PANEL EMDP
NEW PANEL CR
NEW PANEL LS
NEW PANEL EQ
NEW ISOLATION PANEL IP1
NEW ISOLATION PANEL IP2
E EXISTING UTILITY COMPANY FEED-THRU CABINET LOCATED AT NORTHEAST CORNER OF THE PROPERTY.
4-1, 1-6 GND, 1-1/2"C. EXISTING CONCRETE HOUSEKEEPING PAD.
NEW EMERGENCY GENERATOR 80KW/100KVA
Project
8 IN. CONCRETE PAD FOR GENERATOR.
FINISHED FLOOR
GRADE 1-3/0 GND, 1"C. TO 3/4" X 10' COPPER CLAD GROUND ROD, FOUNDATION REBAR, STRUCTURAL STEEL & METALLIC COLD WATER LINE. CONNECT TO GROUND BAR IN PANEL MP.
PROFFER SURGICAL CENTER ADDITION 1611 WALLACE BLVD, AMARILLO, TEXAS 79106
TWO 3"C. EACH WITH 4-500KCM, 36" BELOW GRADE. TWO 2"C. EACH WITH 4-2/0, 1-3 GND. 36" BELOW GRADE. EXISTING UTILITY COMPANY GROUNDING GRID. EXISTING UTILITY CO. PRIMARY CABLES IN POLY CONDUIT BETWEEN FEED-THRU CABINET AND PADMOUNTED TRANSFORMER. EXISTING UTILITY CO. PRIMARY CABLES IN POLY CONDUIT BETWEEN FEED-THRU CABINET AND PADMOUNTED TRANSFORMER LOCATED AT MED CENTER LEAGUE HOUSE.
EXISTING 4/0 BARE GROUND FROM METER CUBICLE GROUND BAR TO TRANSFORMER GROUND GRID. EXISTING UTILITY COMPANY SERVICE LATERAL.
1-1/0 GROUNDING ELECTRODE CONDUCTOR IN 3/4"C. TO EXTERIOR 3/4" X 10' COPPER CLAD GROUND ROD. CONNECT TO GENERATOR FRAME.
EXISTING 1-3/0 GND, 1"C. TO 3/4" X 10' CW GROUND ROD, FOUNDATION REBAR, STRUCTURAL STEEL & METALLIC COLD WATER LINE. CONNECT TO GROUND BAR IN PANEL MDP.
TWO EXISTING 3"C. EACH WITH 4-500KCM, 36" BELOW GRADE. CONNECT TO NEW CT ENCLOSURE. CONTRACTOR TO VERIFY.
CTB ASSOCIATES A R C H I T E C T S
P L A N N E R S
3003 MONTE VISTA BLVD. NE ALBUQUERQUE, NM 87106 P. (505) 268-3033 F. (505) 212-0354
[email protected]
NEW POWER RISER DIAGRAM NO SCALE
Revisions 1.
Date Issued
JANUARY 29, 2018 Sheet No.
2.
3.
Sheet Name
ELECTRICAL DETAILS
E-14
EXISTING FLOOR MOUNTED RACK. INSTALL NEW PATCH PANELS AS REQUIRED FOR DATA CABLING.
SEE THE ATTACHED DIAGRAM FOR SHORT CIRCUIT LEVELS FOR THE 208Y/120V SYSTEM EQUIPMENT. SHORT CIRCUIT LEVELS ARE CALCULATED BASED ON MAXIMUM RMS SYMMETRICAL FAULTS, 150KVA SERVICE TRANSFORMER WITH 1.6% IMPEDANCE, ESTIMATED FEEDER LENGTHS, AND 10KA PRIMARY FAULT CURRENT CONTRIBUTION. ALL PANELS AND THEIR CIRCUIT BREAKERS SHALL BE AIC RATED AS FOLLOWS.
ONE RG-6 COAXIAL CABLE FROM EACH F-TYPE JACK TO TELE 14 TERMINAL BOARD. PROVIDE F-TYPE TERMINATION AT TERMINAL BOARD END TO ALLOW FOR CONNECTION TO EQUIPMENT/SPLITTERS (BY OTHERS). EXISTING ONE #6 GND TO EXISTING RACK.
ONE WHITE CAT5E TELEPHONE CABLE (TYP.) TWO BLUE CAT 5E DATA CABLES AND ONE WHITE CAT5E TELEPHONE CABLE (TYP.)
PANEL MP: PANEL F:
XCEL CONNECT.
ONE BLUE CAT 5E DATA CABLE (TYP.) ONE 3/4" EMT TO ACCESSIBLE CEILING SPACE.
EXISTING 110 STYLE PUNCHDOWN BLOCKS. INSTALL NEW 110 STYLE PUNCHDOWN BLOCKS AS REQUIRED FOR TELEPHONE CABLING.
SERVICE TRANSFORMER PRIMARY
TYPICAL 4 POSITION DATA OUTLET WITH ONE RJ-45 DATA JACK FOR WIRELESS ACCESS POINT.
WAC
EXISTING CABLE TV SPLITTERS.
PANEL G: 10,000 AMPS 3P
PANEL H: PANEL EMDP: PANEL CR:
SERVICE TRANSFORMER
ONE BLUE CAT 5E DATA CABLE (TYP.)
PANEL LS: ONE 3/4" EMT TO ACCESSIBLE CEILING SPACE. PROVIDE A WIDE SWEEP BEND AT TOP OF CONDUIT AND AN INSULATING BUSHING TO PREVENT CABLE DAMAGE.
PANEL EQ:
28,410 AMPS 3P
EXISTING TELEPHONE EQUIPMENT.
22 KAIC ON ALL CIRCUIT BREAKERS. 22 KAIC ON ALL CIRCUIT BREAKERS OR USE 10 KAIC CIRCUIT BREAKERS IF PANEL F FEEDER CRICUIT BREAKER IN MAIN PANEL MP IS 22 KAIC SERIES RATED. 22 KAIC ON ALL CIRCUIT BREAKERS OR USE 10 KAIC CIRCUIT BREAKERS IF PANEL G FEEDER CRICUIT BREAKER IN MAIN PANEL MP IS 22 KAIC SERIES RATED. 22 KAIC ON ALL CIRCUIT BREAKERS OR USE 10 KAIC CIRCUIT BREAKERS IF PANEL H FEEDER CRICUIT BREAKER IN MAIN PANEL MP IS 22 KAIC SERIES RATED. 22 KAIC ON ALL CIRCUIT BREAKERS. 22 KAIC ON ALL CIRCUIT BREAKERS OR USE 10 KAIC CIRCUIT BREAKERS IF PANEL CR FEEDER CRICUIT BREAKER IN PANEL EMDP IS 22 KAIC SERIES RATED. 22 KAIC ON ALL CIRCUIT BREAKERS OR USE 10 KAIC CIRCUIT BREAKERS IF PANEL LS FEEDER CRICUIT BREAKER IN PANEL EMDP IS 22 KAIC SERIES RATED. 22 KAIC ON ALL CIRCUIT BREAKERS OR USE 10 KAIC CIRCUIT BREAKERS IF PANEL EQ FEEDER CRICUIT BREAKER IN PANEL EMDP IS 22 KAIC SERIES RATED.
SVC ENT EXISTING CABLE TV EQUIPMENT.
TYPICAL F-TYPE COAX TV JACK.
TV
TWO 3/4" EMT TO ACCESSIBLE CEILING SPACE. PROVIDE A WIDE SWEEP BEND AT TOP OF CONDUIT AND AN INSULATING BUSHING TO PREVENT CABLE DAMAGE.
EXISTING ONE #6 TO GROUND BAR IN MAIN DISTRIBUTION PANEL MDP.
EXISTING 3/4" PLYWOOD TERMINAL BOARD IN TELE 14.
GRADE
MAIN PANEL MP 13,320 AMPS 3P
TYPICAL SINGLE POSITION DATA OUTLET WITH ONE RJ-45 DATA JACK.
EXISTING TELECOMMUNICATIONS MAIN GROUNDING BUSBAR.
TYPICAL 1 POSITION TELEPHONE OUTLET WITH ONE WHITE CATEGORY 5E RJ-45 TELEPHONE JACK MOUNTED IN UPPER LEFT POSITION. INSTALL BLANK INSERTS IN ALL UNUSED POSITIONS.
TELE 14
PNL F FDR
PNL G FDR
PNL H FDR
PNL F
PNL G
PNL H
11,562 AMPS 3P
11,264 AMPS 3P
PNL EMDP FDR
MAIN PANEL EMDP 11,799 AMPS 3P
12,077 AMPS 3P
TYPICAL 4 POSITION COMBINATION DATA/TELEPHONE OUTLET W/ TWO BLUE CATEGORY 5E RJ-45 DATA JACKS MOUNTED IN LOWER TWO POSITIONS AND 1 WHITE CATEGORY 5E RJ-45 TELEPHONE JACK MOUNTED IN UPPER LEFT POSITION. INSTALL A BLANK INSERT IN UPPER RIGHT POSITION.
EXISTING ONE 4 INCH CONDUIT FOR TELEPHONE SERVICE ENTRANCE. EXISTING ONE 3 INCH CONDUIT FOR CABLE TV SERVICE ENTRANCE.
PNL CR FDR
PNL LS FDR
PNL EQ FDR
PNL CR
PNL LS
PNL EQ
TYPICAL 1 POSITION TELEPHONE OUTLET WITH ONE RJ-45 ANALOG TELEPHONE JACK FOR WALL PHONE.
10,917 AMPS 3P
DATA/TELEPHONE/CABLE TV RISER DIAGRAM
SHORT CIRCUIT DIAGRAM
NO SCALE
NO SCALE
1/2 INCH LOCKNUT EQUAL TO HUBBELL 00322001LPK50 TO SECURE CORD GRIP TO COVER PLATE.
PUNCH HOLE IN COVER TO ACCOMMODATE CORD GRIP FITTING INSTALLATION.
10,652 AMPS 3P
11,078 AMPS 3P
4" SQUARE J-BOX WITH SINGLE GANG P-RING.
STAINLESS STEEL SINGLE GANG J-BOX BLANK COVER PLATE EQUAL TO HUBBELL SS13L. STAINLESS STEEL CORD GRIP EQUAL TO HUBBELL CG410SST.
CEILING MOUNTED SMOKE DETECTOR.
END OF LINE RESISTOR (TYP.) TYPICAL STROBE.
TYPICAL MONITOR MODULE AT TAMPER SWITCH(ES). TYPICAL DUCT SMOKE DETECTOR.
SIGNAL AND LINE CIRCUIT #1 H
P
H
S
SD
2-10, 1-10G, 3/4"C.
END OF LINE RESISTOR (TYP.)
2-12, 1-12G, 3/4"C.
12/3 SOOW CORD AS REQUIRED.
J
NAC WIRING TYPICAL HORN/STROBE.
FIRE ALARM PULL STATION (TYP.)
ANNUNCIATOR CABLING AS REQUIRED BY GENERATOR MANUFACTURER.
TYPICAL MONITOR MODULE AT TAMPER SWITCH(ES).
G-12 (ON)
G-14,16
EMERGENCY GENERATOR
J
120V BATTERY HEATER PAD
208V 1.5KW WATER JACKET HEATER
TYPICAL MONITOR MODULE AT SPRINKLER SYSTEM FLOW SWITCH(ES).
J
J
J
CONTROL PANEL CONNECTION
2-12, 1-12G, 3/4"C. G-12 (ON)
ANNUNCIATOR WIRING
STOP CIRCUIT
Project
2 WIRE START CONNECTION (2 #12, 1 #12 GND, 1/2"C.)
EMERGENCY POWER FEED FROM GENERATOR MCB.
120VAC-24VDC BATTERY CHARGER. REMOTE ANNUNCIATOR.
INSTALL TWO CAT5E CABLES (WHITE) FROM TELEPHONE INPUTS OF FIRE ALARM CONTROL PANEL TO THE TELEPHONE TERMINAL BOARD. TERMINATE CABLES AT TERMINAL BOARD ON A 110 BLOCK.
ANNUNCIATOR WIRING
400A 4P AUTOMATIC TRANSFER SWITCH
ANNUNCIATOR WIRING 2 #16, 1/2" C. (24V)
ADDRESSABLE FIRE ALARM CONTROL PANEL LS-6
1611 WALLACE BLVD, AMARILLO, TEXAS 79106
E N
PROFFER SURGICAL CENTER ADDITION
NORMAL POWER
L
EMERGENCY/NORMAL POWER OUT TO EMDP.
HOSPITAL GRADE CONNECTOR BODY EQUAL TO HUBBELL HBL8319C SUSPENDED 48 IN. AFF. REMOTE BREAK-GLASS STOP. FLUSH MOUNTED REMOTE ANNUNCIATOR.
FIRE ALARM RISER DIAGRAM
OPERATING ROOM SUSPENDED CONNECTOR BODY MOUNTING DETAIL
EMERGENCY GENERATOR CONNECTION DETAIL
NO SCALE
NO SCALE
NO SCALE
CTB ASSOCIATES A R C H I T E C T S
P L A N N E R S
3003 MONTE VISTA BLVD. NE ALBUQUERQUE, NM 87106 P. (505) 268-3033 F. (505) 212-0354
[email protected]
Revisions 1.
Date Issued
JANUARY 29, 2018 Sheet No.
2.
3.
Sheet Name
ELECTRICAL DETAILS
E-15
Project
PROFFER SURGICAL CENTER ADDITION 1611 WALLACE BLVD, AMARILLO, TEXAS 79106
CTB ASSOCIATES A R C H I T E C T S
P L A N N E R S
3003 MONTE VISTA BLVD. NE ALBUQUERQUE, NM 87106 P. (505) 268-3033 F. (505) 212-0354
[email protected]
Revisions 1.
Date Issued
JANUARY 29, 2018 Sheet No.
2.
3.
Sheet Name
PANEL SCHEDULES
E-16
Project
PROFFER SURGICAL CENTER ADDITION 1611 WALLACE BLVD, AMARILLO, TEXAS 79106
CTB ASSOCIATES A R C H I T E C T S
P L A N N E R S
3003 MONTE VISTA BLVD. NE ALBUQUERQUE, NM 87106 P. (505) 268-3033 F. (505) 212-0354
[email protected]
Revisions 1.
Date Issued
JANUARY 29, 2018 Sheet No.
2.
3.
Sheet Name
PANEL SCHEDULES
E-17
GENERAL NOTES 1.
REFER TO POWER FLOOR PLAN FOR PANEL LOCATIONS.
2.
ALL LIGHT FIXTURES, SWITCHES, OCCUPANCY SENSORS, ETC. SHALL BE EXISTING TO REMAIN AND ARE SHOWN FOR REFERENCE ONLY UNLESS NOTED OTHERWISE.
KEYED NOTES 1 1
1
INSTALL LED STRIP LIGHTING ON EXTERIOR OF BUILDING. STRIP LIGHTING SHALL BE DIODE LED HYDROLUME PLUS DI-24V-HLP65-72-XX IN BLUE COLOR MOUNTED IN HYDROLUME MOUNTING CHANNEL DI-HL-MTCH. MOUNT AT SAME HEIGHT AS EXISTING. REFER TO MANUFACTURER'S INSTALLATION INSTRUCTIONS FOR MOUNTING REQUIREMENTS. TERMINATE WIRE ENDS PER MANUFACTURER'S INSTALLATION INSTRUCTIONS. CONTRACTOR TO FIELD VERIFY EXACT LED STRIP DISTANCE FOR CUSTOM CUT ORDER. MAX RUN OF LED STRIP NOT TO EXCEED 32.6 FT.
2
INSTALL DRIVER ABOVE ACCESSIBLE CEILING SPACE. DRIVER SHALL BE A DIODE LED LO-PRO JUNCTION BOX AND DRIVER COMBO DI-DM-MW-24V90W-0-10V-LPL. INSTALL CORD AND PLUG ON DRIVER AND CONNECT TO RECEPTACLE LOCATED ABOVE CEILING. REFER TO MANUFACTURER'S INSTALLATION INSTRUCTIONS FOR MOUNTING REQUIREMENTS.
3
2-12, 1-12G, 1/2"C. BETWEEN DRIVER AND LED STRIP.
4
HOMERUN THROUGH LIGHTING CONTROL PANEL LCP2.
5
HOMERUN 2-12, 1-12G, 1/2"C.
6
NEW RECEPTACLE LOCATED ABOVE CEILING FOR LED STRIP DRIVER(S). HOMERUN 2-12, 1-12G, 1/2"C.
1
END OF RUN 1 3 3 G-10 (ON)
4
5
2
4 G-10 (ON)
5
2
6
6
END OF RUN
J
J
1
J J
J
J
J
J
G-10 (ON)
2
J
4
WALL PENETRATION 6
3
5
1 J
J
J
D E E E E
O V V
N A
N A O V wv V
2 no
2 no
wv
D E E E E
END OF RUN
1
4 2 G-10 (ON) G-10 (ON)
2
4
5
3
5
Project
WALL PENETRATION 6
1
6 1
PROFFER SURGICAL CENTER ADDITION 1611 WALLACE BLVD, AMARILLO, TEXAS 79106
3
WALL PENETRATION 4 1
6
CTB ASSOCIATES
2
A R C H I T E C T S
5 G-10 (ON) E E E E D
V V O
wv
wv
no 2
no 2
A
A
V V O
P L A N N E R S
3003 MONTE VISTA BLVD. NE ALBUQUERQUE, NM 87106 P. (505) 268-3033 F. (505) 212-0354
[email protected]
E E E E D
END OF RUN Revisions 1.
2.
3.
N
1/8" = 1'-0" EXTERIOR BUILDING LED STRIP LIGHTING SCALE: PLAN 1
WALL PENETRATION
JANUARY 29, 2018 Sheet No.
1 3
END OF RUN
Date Issued
0
2'
4'
8'
Sheet Name
EXTERIOR BUILDING LED STRIP LIGHTING PLAN
E-18