Notifier CBC CLASS 12

12 Clintonville Road Northford, CT 06472 (203) 484-7161 (203) 484-7118 (Fax) CBC-CLASS 1/2 Chicago Building Code Class ...

0 downloads 51 Views 2MB Size
12 Clintonville Road Northford, CT 06472 (203) 484-7161 (203) 484-7118 (Fax)

CBC-CLASS 1/2 Chicago Building Code Class I/Class II Master Control Manual Document 50685 7/09/98 PN 50685:C

www.PDF-Zoo.com

Revision: ECN 98-303

C

Installation Precautions – Adherence to the following will aid in problem-free installation with long-term reliability: WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all sources of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until this manual is read and understood. CAUTION - System Reacceptance Test after Software Changes: To ensure proper system operation, this product must be tested in accordance with NFPA 72-1993 Chapter 7 after any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring. All components, circuits, system operations or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices must also be tested and proper system operation verified. This system meets NFPA requirements for operation at 0-49O C/ 32-120O F and at a relative humidity of 85% RH (non-condensing) at 30O C/86O F. However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a nominal room temperature of 15-27O C/60-80O F.

Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to lightning induced transients. Although no system is completely immune from lightning transients and interferences, proper grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical Services Department if any problems are anticipated or encountered. Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits. Remove all electronic assemblies prior to any drilling, filing, reaming or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer and printed circuit board location. Do not tighten screw terminals more than 9 in-lbs. Over tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal. This system contains static-sensitive components Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body. Use static suppressive packaging to protect electronic assemblies removed from the unit. Follow the instructions in the installation, operating and programming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation.

Verify that wire sizes are adequate for all initiating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage.

Fire Alarm System Limitations

While installing a fire alarm system may make lower insurance rates possible, it is not a substitute for fire insurance! An automatic fire alarm system - typically made up of smoke Audible warning devices such as bells may not alert people if these detectors, heat detectors, manual pull stations, audible warning devices are located on the other side of closed or partly open doors or devices and a fire alarm control with remote notification capability can are located on another floor of a building. provide early warning of a developing fire. Such a system, however, A fire alarm system will not operate without any electrical power. If does not assure protection against property damage or loss of life AC power fails, the system will operate from standby batteries only for resulting from a fire. a specified time. Any fire alarm system may fail for a variety of reasons: Rate-of-Rise heat detectors may be subject to reduced sensitivity Smoke detectors may not sense fire where smoke cannot reach the over time. For this reason, the rate-of-rise feature of each detector detectors such as in chimneys, in walls, or roofs, or on the other side of should be tested at least once per year by a qualified fire protection closed doors. Smoke detectors also may not sense a fire on another specialist. evel or floor of a building. A second floor detector, for example, may Equipment used in the system may not be technically compatible not sense a first floor or basement fire. Furthermore, all types of with the control panel. It is essential to use only equipment listed for smoke detectors - both ionization and photoelectric types, have service with your control panel. sensing limitations. No type of smoke detector can sense every kind of fire caused by carelessness and safety hazards like smoking in bed, Telephone lines needed to transmit alarm signals from a premise to a violent explosions, escaping gas, improper storage of flammable central monitoring station may be out of service or temporarily materials, overloaded electrical circuits, children playing with matches, disabled. or arson. The most common cause of fire alarm malfunctions, however, is IMPORTANT! Smoke detectors must be installed in the same room inadequate maintenance. All devices and system wiring should be as the control panel and in rooms used by the system for the tested and maintained by professional fire alarm installers following connection of alarm transmission wiring, communications, signaling written procedures supplies with each device. System inspection and and /or power. If detectors are not so located, a developing fire may testing should be scheduled monthly or as required by National and/or damage the alarm system, crippling its ability to report a fire. local fire codes. Adequate written records of all inspections should be kept.

FCC Warning WARNING: This equipment generates, uses and can radiate radio frequency energy and if not installed and used in accordance with the nstruction manual, may cause interference to radio communications, It has been tested and found to comply with the limits for class A computing device pursuant to Subpart B of 15 of FCC Rules, which is designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference, in which case the user will be required to correct the interference at his own expense.

www.PDF-Zoo.com

Canadian Requirements This digital apparatus does not exceed the Class A limits for radiation noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications. Le present appareil numerique n'emet pas de bruits radioelectriques depassant les limites applicables aux appareils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edicte par le ministere des Communications du Canada.

Table of Contents General Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Figure 1 CBC-CLASS 1/2 Master Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

Compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Figure 2 Cabinet and Remote Module Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Module Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Figure 3 Source-of-Energy Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Figure 4 CBC-BSM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Figure 5 City Tie Disconnect Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Kit Inventory . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Figure 6 Open Cabinet Showing Module Mounting and CBC Kit . . . . . . . . . . . . . . . . . . . . 5 Figure 7 Remote Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 The System Trouble Bell Supervision Module (CBC-BSM). . . . . . . . . . . . . . . . . . . . . 6 The City Tie Disconnect Bell Supervision Module (CBC-BSM) . . . . . . . . . . . . . . . . . 6 The City Tie Disconnect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Mounting the CBC-Master Control . . . . . . . . . . . . . . . . . . . . . . . . 7 Supplies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Mounting the Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Figure 8 Cabinet Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Mounting the Remote Bell Supervision Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Figure 9 Remote Module Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Connecting the Master Control. . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Primary Source Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Figure 10 Source-of-Energy Module to Main Power Supply Connection . . . . . . . . . . . . . . 8

Master Control to NOTIFIER® FACP Connections . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Figure 11 Connecting the CBC Master Control, System 5000, MPS-24A, Annunciator, and FCPS-24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Figure 12 Connecting the CBC Master Control to the System 5000, MPS-24B, Annunciator, and FCPS-24 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Figure 13 Connecting the CBC Master Control, AFP-200 (with RTM-8), Annunciator, and APS-6R . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Figure 14 Connecting the CBC Master Control, AFP-200 (with 4XTM), Annunciator, and APS-6R . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Figure 15 Connecting the CBC Master Control, AFP-400, Annunciator, and APS-6R . . . 13 Figure 16 Connecting the CBC Master Control, AM2020/AFP1010, MPS-24A, Annunciator, and APS-6R . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

CBC Class 1/2 Master Control PN 50685:C 7/09/98

www.PDF-Zoo.com

i

1 General Description The Chicago Building Code Class I / Class II Master Control (CBC-CLASS 1/2) was designed to comply with non high-rise Class I and Class II type building requirements of the city of Chicago, Illinois. It supplies the fire alarm control panel with two AC sources, ensuring backup if one source fails. It also provides the ability to perform the following functions from a remote location: • silencing the system trouble bell and the city tie disconnect bell • disconnecting the municipal tie fire alarm box The CBC-Master Control consists of four modules. It can be ordered with all the modules ready-mounted in a metal cabinet (Figure 1). The System Trouble and/or City Tie Disconnect Bell Supervision Modules can also be ordered separately for remote mounting. The following equipment is required for use with the CBC-CLASS 1/2 to comply with the non high-rise Class I and Class II type requirements: • An FCPS-24 Field Charging Power Supply or APS-6R Power Supply • An incandescent lamp graphic annunciator. Contact : Space Age Electronics, Inc. 406 Lincoln Street Marlboro, MA 01752 Phone: 1-800-486-1723 to purchase a 32 point graphic annunciator (model KG0662), or to custom order any other size. CBC-BSM Bell Supervision Module System Trouble Bell

City Tie Disconnect Module CBC-BSM Bell Supervision Module City Tie Disconnect Bell

Source-of-Energy Module Figure 1 CBC-CLASS 1/2 Master Control

CBC-CLASS 1/2 Master Control PN 50685:C 7/09/98

www.PDF-Zoo.com

1

General Description

Compatibility The CBC-Master Control modules are: • Chicago Building Code / Source-of-Energy Module. • Chicago Building Code / Bell Supervision Modules (CBC-BSM). One supervises the remote system trouble bell. The other supervises the City Tie Disconnect Bell. Both can be mounted remotely. • Chicago Building Code / City Tie Disconnect Module. Module energy information/specifications: • Source of Energy Module - The alarm and trouble relays are capable of withstanding a resistive load of 5A at 25V. • CBC-BSM - Lamp power requirements are 24VDC, 60 mA. The bell power requirements are 24VDC, with current dependent upon the make and model of the bell. • City Tie Disconnect Module - Lamp power requirements are 24VDC, 60 mA. The Module Descriptions section of this manual describes these modules in more detail.

Compatibility The CBC-Master Control can be used in conjunction with the following NOTIFIER® fire panels: • System 5000 Fire Control Panel • AFP-200 Analog Fire Panel • AFP-400 Analog Fire Panel • AM-2020/AFP-1010 Fire Panel

Dimensions The cabinet consists of a backbox with a locking door and two keys. The door is hinged on the left. The CBC-BSM remote mounting consists of a faceplate to be attached to a double-gang box. See Figure 2 below for dimensions.

Figure 2 Cabinet and Remote Module Dimensions 2

www.PDF-Zoo.com

CBC-CLASS 1/2 Master Control PN 50685:C 7/09/98

General Description

Module Descriptions

Module Descriptions Chicago Building Code / Source-of-Energy Module The Chicago Building Code / Source-of-Energy Module connects the fire alarm control panel to two separate AC sources. AC Source One provides the power to the fire alarm control panel. Should AC Source One fail, the connections are automatically transferred by a supervisory relay to the other source. Failure of either source will also activate the Trouble bell. The Source-of-Energy Module has two green lamps corresponding to the two AC sources. When AC Source One is present, the light labelled LINE 1 will be lit. LINE 2 will light when AC Source Two is present. The Source of Energy Module comes with a 120 VAC cautionary label attached to TB1.

Figure 3 Source-of-Energy Module

CBC-BSM Chicago Building Code / Bell Supervision Module There are two CBC-BSM modules. One provides the connection for the remote Trouble bell. This module may be mounted in the master control cabinet, or it may be mounted in a remote location. It provides the capability of testing the bell, and silencing the bell after a Trouble condition occurs. A red incandescent lamp lights when the bell is silenced. The bell will also resound if the Trouble disconnect switch is left in the silence position and there are no Troubles present. The second module provides the connection between the City Tie Disconnect Bell and the City Tie Disconnect Module. It provides the capability of testing the bell and silencing the bell after the City Tie Disconnect has been invoked. A red incandescent lamp lights when the bell is silenced. The bell will also resound if the Trouble disconnect switch is left in the silence position and the City Tie switch is in the Normal position.

Figure 4 CBC-BSM

CBC-CLASS 1/2 Master Control PN 50685:C 7/09/98

www.PDF-Zoo.com

3

General Description

Module Descriptions

Chicago Building Code / City Tie Disconnect Module The Chicago Building Code / City Tie Disconnect Module provides the ability to disconnect the City Tie Box from a location other than the fire alarm control panel. It consists of a disconnect switch operated by a two-pole caption key-operated switch, and a white incandescent lamp that indicates when the city tie has been disconnected. Once the switch has been activated by turning the key, the key can not be removed from the lock until the city tie disconnect switch is again placed in the connect position. A Trouble condition at the panel may be obtained by cutting the option resistor R1.

Figure 5 City Tie Disconnect Module

4

www.PDF-Zoo.com

CBC-CLASS 1/2 Master Control PN 50685:C 7/09/98

General Description

Kit Inventory

Kit Inventory The CBC Master Control Kit consists of a metal cabinet with modules ready mounted (Figure 6), a CBC-KIT (Figure 6), two keys, and an Installation Manual.

The CBC-KIT includes the following 12 items (shown at left) and an Installation Guide: - Two AFP-200 switch covers - Two AFP-200 labels - Two AFP-400 switch covers - One AFP-400 label - Two AM2020/AFP1010 switch covers - Two AM2020/AFP1010 keypad overlays - One System 5000 label

Figure 6 Open Cabinet Showing Module Mounting, and CBC-KIT

When the System Trouble Bell Supervision Module is ordered as a remote module, it comes with a faceplate suitable for mounting to a 4” square double gang box.

Figure 7 Remote Mounting

CBC-CLASS 1/2 Master Control PN 50685:C 7/09/98

www.PDF-Zoo.com

5

Operation

The System Trouble Bell Supervision Module (CBC-BSM)

2 Operation The System Trouble Bell Supervision Module (CBC-BSM) 1.

Press the “BELL TEST” switch to test the System Trouble bell.

2.

The “BELL NORMAL, SILENCE” switch should remain in the “NORMAL” position until the Trouble bell sounds.

3.

Place the switch in the “SILENCE” position to silence the trouble bell. The red light labelled “BELL SILENCED” will go on. The red light will remain on until the “BELL SILENCE” switch is returned to the ”NORMAL” position.

The City Tie Disconnect Bell Supervision Module (CBC-BSM) 1. 2.

3.

Press the “BELL TEST” switch to test the City Tie Disconnect bell. The “BELL NORMAL, SILENCE” switch should remain in the “NORMAL” position until the City Tie Disconnect bell sounds. Place the switch in the “SILENCE” position to silence the City Tie Disconnect Bell. The red light labelled ”BELL SILENCED” will go on. The red light will remain on until the system “BELL SILENCE” switch is returned to the “NORMAL” position.

The City Tie Disconnect Insert the key and turn clockwise to disconnect the Municipal Fire Alarm Box. The white pilot light will go on. Once the key has been inserted, it cannot be removed until returned to its normal position. Activating the switch will not set the fire alarm control panel to System Trouble unless the R1 resistor on the Chicago Building Code / City Tie Disconnect Module has been cut.

6

www.PDF-Zoo.com

CBC-CLASS 1/2 Master Control PN 50685:C 7/09/98

Mounting the CBC-Master Control

Supplies

3 Mounting the CBC-Master Control Carefully unpack the system and check for shipping damage. Mount in a clean, dry, easily accessible area. Locate the top of the cabinet approximately five feet above the floor.

Supplies Mounting the CBC Master Control cabinet will require four mounting fasteners. To mount a bell supervision module independently, one double-gang box with four screw fasteners will be required.

Mounting the Cabinet • • • • •

!

Mark and predrill four mounting bolts. Install the two upper fasteners in the wall with screw heads protruding. Using upper “keyholes”, mount the backbox over the two screws and tighten. Install the lower two fasteners. AC power wires should be pulled into the cabinet through a knockout separate from power-limited wiring. CAUTION: Sources of power should be disconnected before installation. • Power-limited wires should be pulled through other knockouts provided.

Figure 8 Cabinet Mounting

Mounting the Remote Bell Supervision Module • Install double-gang box. • Pull the six wires from the same type module in the Master CBC through one of the box knockouts and connect them to the same terminals on the remote module. • Screw faceplate onto box as indicated in Figure 9. Note: A remote module may be connected to another remote module of the same type. The terminal connections must be identical to the same type module in the CBC Master.

Figure 9 Remote Module Mounting CBC-CLASS 1/2 Master Control PN 50685:C 7/09/98

www.PDF-Zoo.com

7

Connecting the Master Control

Primary Source Connections

4 Connecting the Master Control Primary Source Connections To connect the Source-of-Energy Module to the primary power source, perform the following steps:

!

1. 2. 3.

CAUTION: Turn off the breaker at the main power distribution panel. All sources of power must be disconnected before servicing. Remove the plastic insulating cover from the TB1 terminal block. Make the following connections: • AC Source One Hot to screw terminal L1 HOT IN • AC Source One Ground to screw terminal EARTH • AC Source One Neutral to screw terminal NEUT IN • AC Source Two Hot to screw terminal L2 HOT IN • AC Source Two Ground to screw terminal EARTH • AC Source Two Neutral to screw terminal NEUT IN Refer toFigure 10 To Control Panel

Main Power

Figure 10 Source-of-Energy Module to Main Power Supply Connection

Master Control to NOTIFIER® FACP Connections Figure 11 through Figure 16 specifically illustrate the CBC Master Control connections to each of the compatible NOTIFIER® Fire Alarm Control Panels, as well as to the graphic annunciator, FCPS-24, and APS-6R.

!

8

www.PDF-Zoo.com

Before starting, review the following notes. NOTES: • CAUTION: Turn off the power at the main power distribution panel. All sources of power must be disconnected before servicing. • All notification appliance circuits must be programmed for non-silenceable operation. • Wire size should be 12 - 18 AWG. • Dress panels must be installed with all Fire Alarm Control Panels. • JP2, D31, and R63 on the FCPS-24 must be cut for this application. Refer to the FCPS-24 manual, PN 50059. • Signal Silence/Drill Switch must be covered on the control panel. Refer to the Installation Guide included in the CBC-KIT. • Original panel labels must be removed and replaced with the labels supplied with the CBC-KIT. Refer to the Installation Guide included in the CBC-KIT.

CBC-CLASS 1/2 Master Control PN 50685:C 7/09/98

Master Control to NOTIFIER® FACP Connections

Connecting the Master Control

Note: FACP Secondary Power must be installed. Figure 11 Connecting the CBC Master Control, System 5000, MPS-24A, Annunciator, and FCPS-24

CBC-CLASS 1/2 Master Control PN 50685:C 7/09/98

www.PDF-Zoo.com

9

Connecting the Master Control

Master Control to NOTIFIER® FACP Connections

*

Note: FACP Secondary Power must be installed. Figure 12 Connecting the CBC Master Control to the System 5000, MPS-24B, Annunciator, and FCPS-24

10

www.PDF-Zoo.com

CBC-CLASS 1/2 Master Control PN 50685:C 7/09/98

Master Control to NOTIFIER® FACP Connections

Connecting the Master Control

Note: FACP Secondary Power must be installed. Figure 13 Connecting the CBC Master Control, AFP-200 (with RTM-8), Annunciator, and APS-6R CBC-CLASS 1/2 Master Control PN 50685:C 7/09/98

www.PDF-Zoo.com

11

Connecting the Master Control

Master Control to NOTIFIER® FACP Connections

Note: FACP Secondary Power must be installed. Figure 14 Connecting the CBC Master Control, AFP-200 (with 4XTM), Annunciator, and APS-6R

12

www.PDF-Zoo.com

CBC-CLASS 1/2 Master Control PN 50685:C 7/09/98

Master Control to NOTIFIER® FACP Connections

Connecting the Master Control

Note: FACP Secondary Power must be installed. Figure 15 Connecting the CBC Master Control, AFP-400, Annunciator, and APS-6R

CBC-CLASS 1/2 Master Control PN 50685:C 7/09/98

www.PDF-Zoo.com

13

Connecting the Master Control

Master Control to NOTIFIER® FACP Connections

Note: FACP Secondary Power must be installed. Figure 16 Connecting the CBC Master Control to the AM2020/AFP1010, MPS-24A, Annunciator, and APS-6R 14

www.PDF-Zoo.com

CBC-CLASS 1/2 Master Control PN 50685:C 7/09/98

Master Control to NOTIFIER® FACP Connections

Connecting the Master Control

NOTES

CBC-CLASS 1/2 Master Control PN 50685:C 7/09/98

www.PDF-Zoo.com

15

Connecting the Master Control

Master Control to NOTIFIER® FACP Connections

NOTES

16

www.PDF-Zoo.com

CBC-CLASS 1/2 Master Control PN 50685:C 7/09/98

Limited Warranty NOTIFIER® warrants its products to be free from defects in materials and workmanship for eighteen (18) months from the date of manufacture, under normal use and service. Products are date stamped at time of manufacture. The sole and exclusive obligation of NOTIFIER® is to repair or replace, at its option, free of charge for parts and labor, any part which is defective in materials or workmanship under normal use and service. For products not under NOTIFIER® manufacturing date-stamp control, the warranty is eighteen (18) months from date of original purchase by NOTIFIER®'s distributor unless the installation instructions or catalog sets forth a shorter period, in which case the shorter period shall apply. This warranty is void if the product is altered, repaired or serviced by anyone other than NOTIFIER® or its authorized distributors or if there is a failure to maintain the products and systems in which they operate in a proper and workable manner. In case of defect, secure a Return Material Authorization form from our customer service department. Return product, transportation prepaid, to NOTIFIER®, One Fire-Lite Place, Northford, Connecticut 06472-1653. This writing constitutes the only warranty made by NOTIFIER® with respect to its products. NOTIFIER® does not represent that its products will prevent any loss by fire or otherwise, or that its products will in all cases provide the protection for which they are installed or intended. Buyer acknowledges that NOTIFIER® is not an insurer and assumes no risk for loss or damages or the cost of any inconvenience, transportation, damage, misuse, abuse, accident or similar incident. NOTIFIER ® GIVES NO WARRANTY, EXPRESSED OR IMPLIED, OF MERCHANTABILITY, FITNESS FOR ANY PARTICULAR PURPOSE, OR OTHERWISE WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF. UNDER NO CIRCUMSTANCES SHALL NOTIFIER® BE LIABLE FOR ANY LOSS OF OR DAMAGE TO PROPERTY, DIRECT, INCIDENTAL OR CONSEQUENTIAL, ARISING OUT OF THE USE OF, OR INABILITY TO USE NOTIFIER® PRODUCTS. FURTHERMORE, NOTIFIER® SHALL NOT BE LIABLE FOR ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF, OR AS A RESULT OF, PERSONAL, COMMERCIAL OR INDUSTRIAL USE OF ITS PRODUCTS. This warranty replaces all previous warranties and is the only warranty made by NOTIFIER®. No increase or alteration, written or verbal, of the obligation of this warranty is authorized. "NOTIFIER" is a registered trademark.

One Fire-Lite Place, Northford, CT 06472 Phone: (203) 484-7161 FAX: (203) 484-7118

Technical Publishing

www.PDF-Zoo.com

Document WARNBG-E.P65 11/08/98