TECHNICAL COMPLAINCE STATEMENT Para no
1
Specifications as per T.E
Specification offered
1. General (a) UPS shall be free from workmanship defects, sharp edges, nicks, scratches,burs, etc. All fasteners shall be fixed properly. The equipment shall be complete with all parts and all parts shall be functional. (b) Enclosures shall conform to protection requirement of IP21 to IS/IEC:60947-1/2007
(a) UPS IS free from workmanship defects, sharp edges, nicks, scratches,burs, etc. All fasteners are fixed properly. The equipment is complete with all parts and all parts are functional. (b) Enclosures shall conform to protection requirement of IP2L1 to IS/IEC:60947-1/2007
(c) Switching device shall be MOSFET or IGBT and the same shall be declared in the offer by the tenderers. (d) Switching frequency shall be above 50 Hz and shall be declared in the offer
(c) Switching device is MOSFET
7
2.Switching over time from AC mains to UPS mode on power failure should be maximum10 milli seconds . 3. Input : 160 to 280V, 50 +/- 3 Hz Single Phase AC.
2.Switching over time from AC mains to UPS mode on power failure is 10 milliseconds maximum. 3. Input : 160 to 280V, 50 +/- 3 Hz Single Phase AC.
8
4. Output :
9
(a) AVR output voltage in AC mode : 230 Volts +/- (a) AVR output voltage in AC mode : 230 Volts 9%, 50 +/- 3 Hz. +/- 9%, 50 +/- 3 Hz.
2
3
4
5
6
In tcase of non comp-laince and complaince deviations from T.E.Specn in (YES/NO) unambiguous terms
YES
YES
YES (d) Switching frequency is 50 Hz YES
YES YES
YES
10 11 12 13 14 15
(b) UPS output voltage in battery mode : 230 Volts (b) UPS output voltage in battery mode : 230 +/-10%, 50 +/- 0.5 Hz.at Load power factor of not Volts +/-10%, 50 +/-0.5 Hz.at Load power less than 0.6 lag. factor of not less than 0.6 lag. 5. Total Harmonics distortion: 40% maximum to be measued in DC mode. 6.Inverter Efficiency rated output voltage and frequency)
40% maximum to be measued in DC mode. (at
Inverter efficiency : Minimum 70%
YES
YES YES
75.80%
YES
7. Output Voltage Regulation: Total variation of voltage from no load to full load is not exceed 10% and at no point the output voltage is go beyond the permissible band of 230 Volts +/-9%
YES
17
Total variation of voltage from no load to full load shall not exceed 10% and at no point the output voltage should go beyond the permissible band of 230 Volts +/- 9% 8. Overload :
18
UPS shall withstand 10% overload for at least 10 minutes in mains mode.
UPS is withstood 10% overload for at least 10 minutes in mains mode.
YES
19
9. Protections :
16
(a) Input voltage goes outside the range 160 to 280 Volts the system shall switch over to battery mode. (b) Over voltage , short circuit , and overload protection at UPS output terminals.
(a) Input voltage goes outside the range 160 to 280 Volts the system will switche over to battery mode. (b) Over voltage , short circuit , and overload at UPS output terminals is provided
22
(c) Protection against over discharge ( The load shall be cut-off as soon as voltage of battery teminals falls below 10.5 V for 12 Volts and 21 V for 24 volts battery system.
(c) Protection against over discharge( The load shall be cut-off as soon as voltage of battery teminals falls below 10.5 V for 12 Volts and 21V for 24 volts battery system is provided
23
10. Indicators and meters :
24
Following indicators shall be provided:
20 21
YES YES
YES
YES
25 26 27 28
(a) Mains mode.
(i) Mains mode indication provided.
(b) UPS mode
(ii) UPS mode indication provided.
(c) Battery Low
(iii) Battery Low indication provided.
11. Battery Bank :
YES YES YES YES
29
(a) The batteries shall be of 12 Volts Sealed Lead Acid Valve Regulated Type (VRLA) as per JISC:8707/1992 or to JISC:8702/1998 & the supplier shall submit compliance certificate to the governing specification from OEM to the concerned D(QA) at the time of registration & inspection .
(a) The batteries are of 12 Volts Sealed Lead Acid Valve Regulated Type (VRLA) as per JISC:8707/1992 or to JISC:8702/1998 & the supplier shall submit compliance certificate to the governing specification from OEM to the concerned D(QA) at the time of inspection .
YES
30
(b) Suppliers shall declare battery AH Capacity, battery voltage, number of batteries of each rating,make and model of batteries offered with each item of UPS corresponding to the specified minimum VAH rating of the battery bank
(b) Suppliers shall declare battery AH Capacity, battery voltage, number of batteries of each rating,make and model of batteries offered with each item of UPS corresponding to the specified minimum VAH rating of the battery bank
YES
31
(c) In case the batteries are not housed inside UPS cabinet, suitable enclousre/rack to mount these batteries shall also be supplied along with the batteries
(c) In case the batteries are not housed inside UPS cabinet, suitable enclousre/rack to mount these batteries shall also be supplied along with the batteries
YES
The batttries supplied shall be of following make onlyExide,panasonic,Amararaja,global,Rocket,Base ,Ipower,okaya,CSB,Ritar,luminous,Relicell or DGS&D registered batteries or any other make duly type tested as per JISC 8707/1992 or JISC 8702/1998 from international laboratory accrediation corporation(ILAC) or thier worldwide affiliated/recognised labs are NABL approved labs interms of the DOC correction slip no. 38 dated 18.12.2012 of DGS&D manual.
The batttries supplied shall be of following make onlyExide,panasonic,Amararaja,global,Rocket,Ba se,Ipower,okaya,CSB,Ritar,luminous,Relicell or DGS&D registered batteries or any other make duly type tested as per JISC 8707/1992 or JISC 8702/1998 from international laboratory accrediation corporation(ILAC) or thier worldwide affiliated/recognised labs are NABL approved labs interms of the DOC correction slip no. 38 dated 18.12.2012 of DGS&D manual.
YES
BATTERY Ah DETAILS
Battery Ah capacity
Battery voltage
No of batteries
Make/ Model of batteries
Charging Voltage Charging current (DC Bus Voltage)
SL no
Capacity/
Battery minimum Vah
1
0.5 Kva
84
7.2 Ah
12V
1
AmaronQuanta12AL007
13.7 V
1A
2
0.5 Kva
168
7.2 Ah
24V
2
AmaronQuanta12AL007
27.4 V
1A
3
0.5 Kva
400
18
24 V
2
AmaronQuanta12AL018
27.4 V
2A
4
0.65Kva
168
7.2 Ah
24V
2
AmaronQuanta12AL007
27.4 V
1A
5
0.65Kva
400
18 Ah
24 V
2
AmaronQuanta12AL018
27.4 V
2A
6
0.65Kva
108
9 Ah
12 V
1
AmaronQuanta12AL009
13.7 V
1A
7
0.8 Kva
168
7.2 Ah
24V
2
AmaronQuanta12AL007
27.4 V
1A
8
0.8 Kva
400
18 Ah
24 V
2
AmaronQuanta12AL018
27.4 V
2A
9
0.8 Kva
216
18 Ah
12 V
1
AmaronQuanta12AL018
13.7 V
2A
10
1.0 Kva
168
7.2 Ah
24V
2
AmaronQuanta12AL07
27.4 V
1A
11
1.0 Kva
400
18 Ah
24 V
2
AmaronQuanta12AL018
27.4 V
2A
12
1.0 Kva
216
18 Ah
12 V
1
AmaronQuanta12AL018
13.7 V
2A
13
1.0 Kva
800
42 Ah
24 V
2
AmaronQuanta12AL042
27.4V
4A
14
1.5 Kva
800
42 Ah
24 V
2
AmaronQuanta12AL042
27.4V
4A
15
1.5 Kva
600
26Ah
24 V
2
AmaronQuanta12AL026
27.4V
3A
16
2.0 Kva
800
42Ah
24 V
2
AmaronQuanta12AL042
27.4V
5A
17
2.0 Kva
1600
75Ah
24 V
2
AmaronQuanta12AL075
27.4V
7A
Monthly rate of Supplies - Line intractive UPS
SL no
Capacity/
Battery minimum Vah
Monthly Rate of Supply
Days Required
1
0.5 Kva
84
500
21 days
2
0.5 Kva
168
500
21 days
3
0.5 Kva
400
500
21 days
4
0.65Kva
168
500
21 days
5
0.65Kva
400
500
21 days
6
0.65Kva
108
500
21 days
7
0.8 Kva
168
500
21 days
8
0.8 Kva
400
500
21 days
9
0.8 Kva
216
500
21 days
10
1.0 Kva
168
300
21 days
11
1.0 Kva
400
300
21 days
12
1.0 Kva
216
300
21 days
13
1.0 Kva
800
300
21 days
14
1.5 Kva
800
200
21 days
15
1.5 Kva
600
200
21 days
16
2.0 Kva
800
200
21 days
17
2.0 Kva
1600
200
21 days