JR Communications

TECHNICAL COMPLAINCE STATEMENT Para no 1 Specifications as per T.E Specification offered 1. General (a) UPS shall be...

0 downloads 172 Views 123KB Size
TECHNICAL COMPLAINCE STATEMENT Para no

1

Specifications as per T.E

Specification offered

1. General (a) UPS shall be free from workmanship defects, sharp edges, nicks, scratches,burs, etc. All fasteners shall be fixed properly. The equipment shall be complete with all parts and all parts shall be functional. (b) Enclosures shall conform to protection requirement of IP21 to IS/IEC:60947-1/2007

(a) UPS IS free from workmanship defects, sharp edges, nicks, scratches,burs, etc. All fasteners are fixed properly. The equipment is complete with all parts and all parts are functional. (b) Enclosures shall conform to protection requirement of IP2L1 to IS/IEC:60947-1/2007

(c) Switching device shall be MOSFET or IGBT and the same shall be declared in the offer by the tenderers. (d) Switching frequency shall be above 50 Hz and shall be declared in the offer

(c) Switching device is MOSFET

7

2.Switching over time from AC mains to UPS mode on power failure should be maximum10 milli seconds . 3. Input : 160 to 280V, 50 +/- 3 Hz Single Phase AC.

2.Switching over time from AC mains to UPS mode on power failure is 10 milliseconds maximum. 3. Input : 160 to 280V, 50 +/- 3 Hz Single Phase AC.

8

4. Output :

9

(a) AVR output voltage in AC mode : 230 Volts +/- (a) AVR output voltage in AC mode : 230 Volts 9%, 50 +/- 3 Hz. +/- 9%, 50 +/- 3 Hz.

2

3

4

5

6

In tcase of non comp-laince and complaince deviations from T.E.Specn in (YES/NO) unambiguous terms

YES

YES

YES (d) Switching frequency is 50 Hz YES

YES YES

YES

10 11 12 13 14 15

(b) UPS output voltage in battery mode : 230 Volts (b) UPS output voltage in battery mode : 230 +/-10%, 50 +/- 0.5 Hz.at Load power factor of not Volts +/-10%, 50 +/-0.5 Hz.at Load power less than 0.6 lag. factor of not less than 0.6 lag. 5. Total Harmonics distortion: 40% maximum to be measued in DC mode. 6.Inverter Efficiency rated output voltage and frequency)

40% maximum to be measued in DC mode. (at

Inverter efficiency : Minimum 70%

YES

YES YES

75.80%

YES

7. Output Voltage Regulation: Total variation of voltage from no load to full load is not exceed 10% and at no point the output voltage is go beyond the permissible band of 230 Volts +/-9%

YES

17

Total variation of voltage from no load to full load shall not exceed 10% and at no point the output voltage should go beyond the permissible band of 230 Volts +/- 9% 8. Overload :

18

UPS shall withstand 10% overload for at least 10 minutes in mains mode.

UPS is withstood 10% overload for at least 10 minutes in mains mode.

YES

19

9. Protections :

16

(a) Input voltage goes outside the range 160 to 280 Volts the system shall switch over to battery mode. (b) Over voltage , short circuit , and overload protection at UPS output terminals.

(a) Input voltage goes outside the range 160 to 280 Volts the system will switche over to battery mode. (b) Over voltage , short circuit , and overload at UPS output terminals is provided

22

(c) Protection against over discharge ( The load shall be cut-off as soon as voltage of battery teminals falls below 10.5 V for 12 Volts and 21 V for 24 volts battery system.

(c) Protection against over discharge( The load shall be cut-off as soon as voltage of battery teminals falls below 10.5 V for 12 Volts and 21V for 24 volts battery system is provided

23

10. Indicators and meters :

24

Following indicators shall be provided:

20 21

YES YES

YES

YES

25 26 27 28

(a) Mains mode.

(i) Mains mode indication provided.

(b) UPS mode

(ii) UPS mode indication provided.

(c) Battery Low

(iii) Battery Low indication provided.

11. Battery Bank :

YES YES YES YES

29

(a) The batteries shall be of 12 Volts Sealed Lead Acid Valve Regulated Type (VRLA) as per JISC:8707/1992 or to JISC:8702/1998 & the supplier shall submit compliance certificate to the governing specification from OEM to the concerned D(QA) at the time of registration & inspection .

(a) The batteries are of 12 Volts Sealed Lead Acid Valve Regulated Type (VRLA) as per JISC:8707/1992 or to JISC:8702/1998 & the supplier shall submit compliance certificate to the governing specification from OEM to the concerned D(QA) at the time of inspection .

YES

30

(b) Suppliers shall declare battery AH Capacity, battery voltage, number of batteries of each rating,make and model of batteries offered with each item of UPS corresponding to the specified minimum VAH rating of the battery bank

(b) Suppliers shall declare battery AH Capacity, battery voltage, number of batteries of each rating,make and model of batteries offered with each item of UPS corresponding to the specified minimum VAH rating of the battery bank

YES

31

(c) In case the batteries are not housed inside UPS cabinet, suitable enclousre/rack to mount these batteries shall also be supplied along with the batteries

(c) In case the batteries are not housed inside UPS cabinet, suitable enclousre/rack to mount these batteries shall also be supplied along with the batteries

YES

The batttries supplied shall be of following make onlyExide,panasonic,Amararaja,global,Rocket,Base ,Ipower,okaya,CSB,Ritar,luminous,Relicell or DGS&D registered batteries or any other make duly type tested as per JISC 8707/1992 or JISC 8702/1998 from international laboratory accrediation corporation(ILAC) or thier worldwide affiliated/recognised labs are NABL approved labs interms of the DOC correction slip no. 38 dated 18.12.2012 of DGS&D manual.

The batttries supplied shall be of following make onlyExide,panasonic,Amararaja,global,Rocket,Ba se,Ipower,okaya,CSB,Ritar,luminous,Relicell or DGS&D registered batteries or any other make duly type tested as per JISC 8707/1992 or JISC 8702/1998 from international laboratory accrediation corporation(ILAC) or thier worldwide affiliated/recognised labs are NABL approved labs interms of the DOC correction slip no. 38 dated 18.12.2012 of DGS&D manual.

YES

BATTERY Ah DETAILS

Battery Ah capacity

Battery voltage

No of batteries

Make/ Model of batteries

Charging Voltage Charging current (DC Bus Voltage)

SL no

Capacity/

Battery minimum Vah

1

0.5 Kva

84

7.2 Ah

12V

1

AmaronQuanta12AL007

13.7 V

1A

2

0.5 Kva

168

7.2 Ah

24V

2

AmaronQuanta12AL007

27.4 V

1A

3

0.5 Kva

400

18

24 V

2

AmaronQuanta12AL018

27.4 V

2A

4

0.65Kva

168

7.2 Ah

24V

2

AmaronQuanta12AL007

27.4 V

1A

5

0.65Kva

400

18 Ah

24 V

2

AmaronQuanta12AL018

27.4 V

2A

6

0.65Kva

108

9 Ah

12 V

1

AmaronQuanta12AL009

13.7 V

1A

7

0.8 Kva

168

7.2 Ah

24V

2

AmaronQuanta12AL007

27.4 V

1A

8

0.8 Kva

400

18 Ah

24 V

2

AmaronQuanta12AL018

27.4 V

2A

9

0.8 Kva

216

18 Ah

12 V

1

AmaronQuanta12AL018

13.7 V

2A

10

1.0 Kva

168

7.2 Ah

24V

2

AmaronQuanta12AL07

27.4 V

1A

11

1.0 Kva

400

18 Ah

24 V

2

AmaronQuanta12AL018

27.4 V

2A

12

1.0 Kva

216

18 Ah

12 V

1

AmaronQuanta12AL018

13.7 V

2A

13

1.0 Kva

800

42 Ah

24 V

2

AmaronQuanta12AL042

27.4V

4A

14

1.5 Kva

800

42 Ah

24 V

2

AmaronQuanta12AL042

27.4V

4A

15

1.5 Kva

600

26Ah

24 V

2

AmaronQuanta12AL026

27.4V

3A

16

2.0 Kva

800

42Ah

24 V

2

AmaronQuanta12AL042

27.4V

5A

17

2.0 Kva

1600

75Ah

24 V

2

AmaronQuanta12AL075

27.4V

7A

Monthly rate of Supplies - Line intractive UPS

SL no

Capacity/

Battery minimum Vah

Monthly Rate of Supply

Days Required

1

0.5 Kva

84

500

21 days

2

0.5 Kva

168

500

21 days

3

0.5 Kva

400

500

21 days

4

0.65Kva

168

500

21 days

5

0.65Kva

400

500

21 days

6

0.65Kva

108

500

21 days

7

0.8 Kva

168

500

21 days

8

0.8 Kva

400

500

21 days

9

0.8 Kva

216

500

21 days

10

1.0 Kva

168

300

21 days

11

1.0 Kva

400

300

21 days

12

1.0 Kva

216

300

21 days

13

1.0 Kva

800

300

21 days

14

1.5 Kva

800

200

21 days

15

1.5 Kva

600

200

21 days

16

2.0 Kva

800

200

21 days

17

2.0 Kva

1600

200

21 days