301 1206

Submittal Data Information 301-1206 KV Series Vertical Close Coupled Pumps EFFECTIVE: JANUARY 31, 2004 JOB SUPERSEDES:...

0 downloads 58 Views 78KB Size
Submittal Data Information 301-1206

KV Series Vertical Close Coupled Pumps EFFECTIVE: JANUARY 31, 2004 JOB

SUPERSEDES: MARCH 21, 2003

ENGINEER ITEM NO.

1160 RPM MODEL 6095

CONTRACTOR

MODEL NO.

IMPELLER DIA.

REP.

G.P.M.

HEAD/FT.

J

H.P.

WEIGHT

ELEC. CHAR.

PUMP/MOTOR

FOUR 5⁄8 - 11 UNC THREADED MOUNTING HOLES ON A 6.62" BOLT CIRCLE

E H-TAP

F D C

B

A

G

MACHINED MOUNTING SURFACE

50 Cycle Performance Curves attached when applicable. Model No.

Conn.

6x6 6095 (152 x 152)

Motor Frame 215JM 254JM 256JM 284JM

HP Flange Size 1160 RPM ASA 5 7.5 10 15

*A & B Dimensions apply for all pump sizes. A*

B*

C

16.00 if 125 psi flange

14.00 if 125 psi flange

6

16.44 if 250 psi flange

14.44 if 250 psi flange

9.24

(152)

(406) if 860 kpa flange

(355) if 860 kpa flange

(234)

D 14.78 15.40 15.40 15.40

(375) (391) (391) (391)

E MAX 18.18 17.83 19.91 23.39

F

(462) (453) (506) (594)

G

H

8.32

10.54

0.25

(211)

(267)

(6)

J DIA 19.56 12.94 12.94 15.29

(234) (329) (329) (388)

(417) if (366) if 1720 kpa flange 1720 kpa flange English dimensions are in inches. Metric dimensions are in millimeters. Metric data is presented in ( Do not use for construction purposes unless certified.

).

Item

Casing

Impeller Wear Ring

Shaft

Shaft Sleeve Mech. Seal Seal Flush Line

BRONZE FITTED ALL IRON Std. Optional Standard Optional Pump Constr. Cast Iron Cast Iron ASTM A48 N/A ASTM A48 N/A Class 30A Class 30A Cast Iron Bronze CF ASTM A48 CF ASTM B584-836 Class 30A Bronze ASTM None None N/A B584-932 SAE660 St. Steel St. Steel Carbon Carbon AISI 416 AISI 416 Steel Steel ASTM A582 ASTM A582 Bronze St. Steel St. Steel ASTM CF AISI 303 AISI 303 B584-932 ASTM A276 ASTM A276 SAE660 Tungsten Tungsten Ceramic/ Ceramic/ Carbide/ Carbide/ EPT EPT EPT EPT Copper

Flange Pressure Temperature

CF

Stainless Steel

OPERATING SPECIFICATIONS Standard 125# 860K 250# 1720K

CF

Optional

175 PSIG* 1210 KPA

300 PSIG** 2070 KPA

CF

250°F 120°C

250°F 120°C

CF

Motors: All NEMA Standard ODP (JM Frame) * In accordance with ANSI Standard B16.1 Class 125 ** In accordance with ANSI Standard B16.1 Class 250 Dim. CF - Consult Factory N/A - Not Available

Comments: TACO, INC., 1160 Cranston Street, Cranston, RI 02920

Telephone: (401) 942-8000

TACO (Canada), Ltd., 6180 Ordan Drive, Mississauga, Ontario L5T 2B3.

FAX: (401) 942-2360.

Telephone: 905/564-9422.

FAX: 905/564-9436.

Printed in USA Copyright 2004 TACO, INC.